Laserfiche WebLink
1997 UNIFORM FIRE CODE APPENDIX 114 <br />APPENDIX II-1 <br />OZONE GAS -GENERATING EQUIPMENT <br />SECTION 1 — 5a;OPE <br />Equipment having a maximum ozone -generating capacity of <br />112 pound (0.23 kg) or mo.. over a 24-hour period shall be in ac- <br />cordance with Appendix 11-1. <br />EXCEPTION: Ozone -generating equipment used in Group R. Di. <br />vision 3 Occupancirs. <br />SECTION 2 — DEFINIT60NS <br />For the purpose of Appendix 11-1, certain terms are defined ss fol- <br />lows: <br />OZONE GENERATOR is equipment which causes lire pro- <br />duction of ozone. <br />SECTION 3 — STANDARDS <br />The following standard is intended for use as a guide in the de- <br />sign, fabrication, testing and use of equipment regulated by <br />Appendix 11.1: <br />National Electric Manufacturers Association <br />2101 L Street, NAV. <br />Suite 300 <br />Washington, DC 20037 <br />Standard 250, Enclosures for Electrical Equipment <br />SECTION 4 — LOCATION <br />4.1 General. Ozone generators shall be located in approved <br />cabinets or ozone -generator rooms in accordance with Section 4. <br />EXCEPTION: A generator within an approved pressure vessel <br />need nor be in a cabinet or ozone -generator rwtm when baled outside <br />or buildings <br />4.2 Cabinets. Ozone cabinets shall be constmztcd of approved <br />materials compatible with ozone in accordance with nationally <br />recognized standards. Cabinets shall display an approved sign <br />stating, OZONE GAS GENERATOR —HIGHLY TOXIC —OX- <br />IDIZER. See Section 3. <br />Cabinets shall be braced for seismic activity in accordance with <br />the Building Code. <br />Cabinets shall be mechanically ventilated with a minimum of <br />six air changes per hour. Exhausted air shall be directed to a treat- <br />ment system designed to reduce the discharge concentration of <br />the gas to one half of the IDLH value at the point of discharge to <br />the atmosphere. <br />The average velocity of ventilation at makeup air openings <br />with cabinet doors closed shall not be less than 200 feet per min. <br />ale (1.02 m/s). <br />4.3 Ozone -generator Rooms. Ozone -generator rooms shall be <br />mechanically ventilated with a minimum of six air changes per <br />hour. Exhausted air shall be directed to a treatment system de. <br />signed to reduce the discharge concentration of gas to one half of <br />the IDLH value at the point of discharge to the atmosphere or <br />ozone -generator rooms shall be equipped with a continuous <br />gas -detection system which will shut off the generator and sound <br />a local alarm when concentrations above the permissible expo. <br />sure limit occur. <br />Ozone -generator rooms shall not be normally occupied, and <br />such rooms shall be ke, free of combustible and hazardous mate- <br />rial storage. Room access doors shall display an approved sign <br />stating, OZONE GAS GENERATOR —HIGHLY TOXIC —OX- <br />IDIZER. <br />SECTION 5 -- PIPING VALVES AND FITTINGS <br />5.1 General. Piping, valves, fittings and related components <br />used to convey ozone shall be in accordance with Section 5. <br />5.2 Secondary Containment. Secondary containment, such as <br />double -walled piping or exhausted enclosures, shall be provided <br />for piping, valves, fiuing:i and related components. Secondary <br />containment shall be capable of directing a sudden release to an <br />approved treatment system. <br />EXCEFTION: Welded stainless steel piping and tubing. <br />5.3 Materials. Materials shall be compatible with ozone and <br />shall be rated for the design operating pressures. <br />5.4 Identification. Piping shall be identified "Ozone Gas — <br />Highly Toxic —Oxidizer." <br />SECTION 6 — AUTOMATIC SHUTDOWN <br />Ozone generators shall be designed to automatically shut down <br />under the following conditions: <br />1. When the dissolved ozone concentration in the water being <br />treated is above saturation when measured at the point where the <br />water is exposed to the atmosphere, <br />2. When the process using generated ozone is shut down, <br />3. Failure of the ventilation system for the cabinet or ozone - <br />generator norm, or <br />4. Failure of the gas -detection system. <br />SECTION 7 — MANUAL SHUTDOWN <br />Manual shutdown controls shall be provided at the generator and, <br />if in a room, within 10 feet (3048 ram) of the main exit or exit -ac- <br />cess door. <br />1_997 <br />