My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
1125 80TH ST SW 2016-01-01 MF Import
>
Address Records
>
80TH ST SW
>
1125
>
1125 80TH ST SW 2016-01-01 MF Import
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/18/2017 9:09:17 PM
Creation date
4/18/2017 9:08:47 PM
Metadata
Fields
Template:
Address Document
Street Name
80TH ST SW
Street Number
1125
Imported From Microfiche
Yes
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
229
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
ti FIRE DEp"rmEmr <br /> TO: Justin Osemene, Planning <br /> 1ANG <br /> FROM: Warren M. Baty, Assistant Fire Marshal <br /> DATE: March 21, 1995 <br /> SUBJECT: SEPA #22-95 <br /> 80th STREET SW <br /> DENNIS PETROLEUM WAREHOUSE/OFFICE BUILDING + PARKING <br /> 1. Access - The Uniform Fire Code requires that all new structures shall provide Fire Department <br /> access roads to within 150 feet of all portions of the ground floor. Fire Department access <br /> roads (Fire Lanes) shall provide a minimum of 20 feet in width of unobstructed, all-season <br /> driving surface with a minimum clear height of 13'6". Fire Lanes will be posted and <br /> maintained as required by the Fire Department. <br /> 2. Access - O.K. as shown on the site plan reviewed. <br /> 3. Fire lanes shall be provided as required in Everett Municipal Code 46.44. Fire lanes shall be <br /> identified by red curbs with white stenciling stating "NO PARKING - FIRE LANE" and <br /> vertical signs stating "NO PARKING - FIRE LANE - TOW AWAY ZONE." Location shall <br /> be approved by the Fire Marshal. <br /> 4. Security Fence - Any security fence erected around the construction site shall be located so as <br /> to not obstruct any existing hydrant, fire protection equipment, or Fire Department access. If <br /> Fire Department access is obstructed, gates or other openings shall be provided for access. <br /> 5. Premise Identification - Premises shall be clearly identified by the correct address at the street <br /> entry. Buildings shall be clearly identified so as to be visible and legible from the access road. <br /> Individual apartments and suites, where applicable, shall be clearly and legibly identified from <br /> the access road. <br /> 6. 1lydrants - Two (2) available hydrants arc required. They shall be located within 200 driving <br /> feet but no closer than 50 feet of every structure. Location of hydrants shall be approved by <br /> the Fire Marshal. <br /> 7. Fire Hydrants - Locations as shown on the site plan are acceptable. <br /> 8. PREMISE IDENTIFICATION AND ALL REQUIRED FIRE DEPARTMENT ACCESS <br /> ROADS AND FIRE HYDRANTS SHALL BE IN SERVICE PRIOR TO <br /> COMMENCEMENT OF CONSTRUCTION. <br /> 9. Based upon 29,750 square feet of Type V-N, sprinklered constriction, the lire ILnv <br /> requirement is 2,375 gpm. <br /> EVERETT FIRE DEPARTMENT• 2811 Oakes Ave. • Everett,WA 98201 • (206) 259.8709• Fax(206)259.8781 <br />
The URL can be used to link to this page
Your browser does not support the video tag.