Laserfiche WebLink
or <br /> PUBLIC WOROU ropy <br /> August 12, 1991 <br /> Mr. Alfred Harris <br /> 11731 43rd Dr. S.F. <br /> Everett, WA. 98208 <br /> RE: Owner: Everett 526 Commerce Ctr./Northshore Christian Church <br /> Job Address 1410 80th 5t. S.Y. <br /> Flan Check No. 91/27021 <br /> Dear Mr. Harris: <br /> In response to ,your application for a construction permit, your plane have <br /> been examined and ,you are advised that the issuance of a permit is being <br /> withheld for the reasons listed below. <br /> 1. The code Information given an sheet T1 pertains to the buildings it <br /> their shell atage. The code Information included in your drawings <br /> should pertain to what ,you are intending to do. <br /> As we see it, you are adding an A2.1 occupancy Into a building <br /> intended for B2 use of Type III-N construction. A2.1 occupancies <br /> are nor permitted with type III-N construction (See UBC TBL.SC). <br /> Since one building cannot be of two construction types, your only <br /> option appears to be to divide the building with an area separation <br /> wall complying with UBC 505(e). you then could use Type III-1118. <br /> construction (See Table 17-A). <br /> 2. Valls and ceilings of corr4dors are required to be of I-IiR <br /> fire-resistive construction. Section 3305(g). An architectural <br /> section through the corridor in necessary to determine how this is <br /> accomplished. <br /> I <br /> 3. An occupant load sign is required to .h- Chapel end Foyer per UBC <br /> 3302(c). These occupant loads must be determtried per 3302(a), using <br /> the load factors of TBL.33A. <br /> CITY OF EVERETT•3200 Cedar Strent-Everen,WA 98201 •t206)259-8800•Fax(206)259.8882 $ <br />