Laserfiche WebLink
I� <br />F R A N K L I N 75 4rh Avenuc PH 425 827.3324 <br />uite 202 FAX 425 627-6252 <br />ENGINEERING 01an,+ WA 98033 hvac0franklmeng.com <br />AV7o7-Qsz- <br />July 28, 2007 <br />ENVELOPE SUMMARY <br />RE: Tyco Valves <br />830 80"' St SW Ste 400 <br />Everett, WA <br />Heated space applies to Office space. <br />Vertical Glazing: Double pane, 1/2" space Air, low-e 1 ", fixed. Or certified tested <br />assembly per NFRC. U=0.55, defeult. SHGC=0.45. <br />Doors (Opaque): Wood, U=0.50, default. <br />Other Roof Type 1: R-38 batt insulation on T-bar ceiling. U=0.029, calculated. <br />Other Roof Type 2 (Restrooms): R-30 batt insulation in metal framing, GWB ceiling. <br />U=0.076, calculated. <br />Wall Type 1 (Opaque, Exterior): Concrete, min. 6" thick, furred with metal studs, 3-1/2", <br />24" oc with R-15 batt insulation, U = 0.101, calculated. <br />Wall -type 2 (Opaque, Warehouse): Metal studs, min. 5.1/2", 24" oc with R-21 batt <br />insulation, U =0.090 default. <br />Slab on Crade: No Insulation, F=0.73, default. <br />Please note that these values are minimum insulation requiren,unts for code compliance. <br />Higher insulation values may be installed. <br />SHGC = Solar Heat Gain Coefficient <br />