Laserfiche WebLink
FRANKLIN <br />ENGINEERING <br />MECHANICAL CONSULTING <br />March 14, 2006 <br />PAVN57 Cam 6c)601o�/q <br />625 40 Avenue PH 425 827-3324 <br />Suite 202 FAX 425 627.6252 <br />Kirkland. WA 98033 hvac4franklineng.com <br />ENVELOPE SUMMARY <br />RE: Bray International <br />80'" St SW <br />Everett, WA <br />Heated space applies to Office space. <br />Vertical Glazing Type 1 (Exterior): U=0.55, SHGC=0.45. Unlabeled glazing - 1/2" <br />space Air, low-e 101 ', fixed, default. Or certified tested assembly per NFRC. <br />Vertical Glazing Type 2 (Re-lite to Warehouse): U =0.90, SHGC =exempt. Unlabeled <br />glazing — double pane, fixed, default. Or certified tested assembly per NFRC. <br />Doors (Opaque): Wood, U=0.50, default. <br />Other Roof Type 1 (T-bar ceiling): R-30 batt insulation on vented T-bar ceiling. U=0.037, <br />calculated. <br />Other Roof Type 2 (Restrooms): R-19 batt insulation in metal framing, 24" oc, on GWB <br />ceiling. U = 0.09, calculated. <br />Wall Type 1 (Opaque, Exterior, Floor to 9'-0" AFF): Concrete, min. 6" thick, furred with <br />metal studs, 3-1/2", 24" oc with R-15 batt insulation, U=0.10, calculated. <br />Wall Type 2 (Opaque, Demising): Metal studs, min. 7-1/2", 16" oc with R-25 batt <br />insulation, U=0.091 default. <br />Wall Type 3 (Opaque, Warehouse): Metal studs, min. 5-1/2", 24" oc with R-19 batt <br />insulation, plus R-1 continuous foam board, U=0.084 default. <br />11 <br />