Laserfiche WebLink
FRANKLIN <br />ENGINEERING <br />MECHANICAL CONSULTING <br />625 4th Avenue PH 425 827-3324 <br />5wte 202 FAX 425 827-6252 <br />Kirkland, WA 98033 hvacOfrank lineng.com <br />8 b709 - bZC, <br />September 6, 2007 <br />ENVELOPE SUMMARY <br />RE: Emerald City Labels TI <br />80'" St SW, Bldg A <br />Everett, WA <br />Heated space applies to Office space. <br />Vertical Glazing: U=0.55, SHGC=0.45. Unlabeled glazing - 1/2" space Air, low-e 10101, <br />fixed, default. Or certified tested assembly per NFRC. <br />Doors (Opaque): Wood, U=0.50, default. <br />Other Roof Type 1: R-30 batt insulation on T-bar ceiling. U=0.037, calculated. <br />Other Roof Type 2 (Restrooms): R-30 bait insulation in metal framing with GWB ceiling. <br />U=0.076, calculated. <br />Wall Type 1 (Opaque, Exterior, Floor to Ceiling): Concrete, min. 6" thick, furred with <br />metal studs, 3-1/2", 24" oc with R-15 batt insulation, U=0.10, calculated. <br />Wail Type 2 (Opaque, Demising): Metal studs, min. 5-1/2", 16" oc with R-19 batt <br />insulation, U=0.10 default. <br />Wall Type 3 (Opaque, Warehouse): Metal studs, min. 5-1/2", 24" oc with R-21 batt <br />insulation, U = 0.085 default. <br />Slab on Grade: No Insulation, F=0.73, default. <br />Please note that these values are minimum insulation requirements for code compliance. <br />Higher insulation values may be installed. <br />SHGC = Solar Heat Gain Coefficient <br />