SECTION IV — SYSTEM DESIGN <br /> UL EX. 3470 ULC CEx747 Page 4-1 <br /> 10-1-02 REV. 5 <br /> SYSTEM DESIGN ►GENERAL INFORMATION <br /> The Ansul R-102 Restaurant Fire Suppression System may be 1. Nozzles must be located 2-8 in.(5-20 cm)into the center of the <br /> used on a number of different types of restaurant cooking appli- duct opening, discharging up.See Figure 1. <br /> ances and hood and duct configurations.The design information <br /> listed in this section deals with the limitations and parameters of <br /> this pre-engineered system.Those individuals responsible for the <br /> design of the R-102 system must be trained and hold a current <br /> Ansul certificate in an R-102 training program. <br /> The R-102 and the PIRANHA systems use compatible agents and <br /> components, therefore, they may be used together for cooking <br /> appliance, hood, and duct protection. The primary ANSUL <br /> AUTOMAN Release can be either an R-102 or a PIRANHA <br /> ANSUL AUTOMAN Release and can actuate up to two additional - <br /> R-102 or PIRANHA Regulated Actuators. In systems utilizing a <br /> 101 remote release, any combination of the maximum number of <br /> regulated actuators can be used. ( -e <br /> (5—200 <br /> cm) <br /> • Both systems must actuate simultaneously. r <br /> • Each system must be designed and installed per its appropri- FIGURE 1 <br /> ate manual. 030173 <br /> • Adjacent appliances requiring protection must be protected 2.In installations where a UL listed damper assembly is <br /> with the same type of system, either R-102 or PIRANHA, employed, the duct nozzle can be installed beyond the 8 in. <br /> unless the center-to-center spacing between the adjacent (20 cm) maximum, to a point just beyond the damper assem- <br /> R-102 and PIRANHA nozzles is no less than 36 inches. bly that will not interfere with the damper.Exceeding the maxi- <br /> When appliances are protected with R-102 nozzles, the hood mum of 8 in. (20 cm) in this way will not void the UL listing of <br /> and connecting duct above those appliances cannot be pro- the system. <br /> tected with PIRANHA nozzles. 3.Previously listed 3 flow number and 5 flow number duct pro- <br /> Mixing systems in a common plenum is not allowed. tection detailed in earlier published manual, Part No.418087- <br /> One of the key elements for restaurant fire protection is a correct 06, can also still by utilized. <br /> system design.This section is divided into ten sub-sections: Noz- DUCT SIZES UP TO 50 IN.(127 cm) <br /> zle Placement Requirements, Tank Quantity Requirements, Actu- PERIMETER/ 16 IN.(41 cm)DIAMETER <br /> ation and Expellant Gas Line Requirements, Distribution Piping <br /> Requirements, Detection System Requirements, Manual Pull Sta- One 1100 nozzle(Part No.430912)=one flow number <br /> tion Requirements, Mechanical Gas Valve Requirements, Electri- 50 in. (127 cm)perimeter maximum <br /> cal Gas Valve Requirements, Electrical Switch Requirements, and <br /> Pressure Switch Requirements. Each of these sections must be 16 in.(41 cm)diameter maximum <br /> completed before attempting any installation. System design <br /> sketches should be made of all aspects of design for reference DUCT SIZES UP TO 100 IN.(254 cm) <br /> during installation. PERIMETER/32 IN.(81.3 cm)DIAMETER <br /> NO72LE PLACEMENT REQUIREMENTS One 2W Nozzle(Part No.419337)=two flow numbers <br /> This section gives guidelines for nozzle type, positioning, and 100 in.(254 cm)perimeter maximum <br /> quantity for duct, plenum,and individual appliance protection.This 32 in.(81.3 cm)diameter maximum <br /> section must be completed before determining tank quantity and A 2WH nozzle (Part No. 78078) must be substituted for a 2W <br /> piping requirements. nozzle for any installation using Option 2 of the 1.5 gallon sys- <br /> Duct Protection—Single Nozzle tem coverage (duct and plenum protection only).A 2WH nozzle <br /> is limited to a maximum of 75 in. (190 cm)perimeter or a maxi- <br /> All duct protection is UL listed without limitation of maximum duct mum diameter of 24 in.(61 cm)of coverage. <br /> length (unlimited length).This includes all varieties of ductworks <br /> both horizontal and vertical including ducts that run at angles to The chart below shows the maximum protection available from <br /> the horizontal and ducts with directional bends. each duct nozzle. <br /> The R-102 system uses different duct nozzles depending on the Part 3.0 Gallon 1.5 Gallon <br /> ,.size of duct being protected. Description No. System System <br /> 2W Nozzle 419337 Maximum Maximum <br /> 100 in.(254 cm) 100 in.(254 cm) <br /> Perimeter Perimeter <br /> 1100 Nozzle 430912 Maximum Maximum <br /> 50 in.(127 cm) 50 in.(127 cm) <br /> Perimeter Perimeter <br /> q1 Z <br />