Laserfiche WebLink
Project: Boeing Medical Trailers Updated Plan-ID: 2.5 Ton Page: 3 <br /> : . Model Number:T30H1-AF8WP4XXE Option <br /> Quantity: 1 <br /> -formance Qa Project Parameters Supply fir Performance <br /> Total Cooling Capacity 28,000 Btuh Total Supply Air 1000 cfm <br /> Sensible Capacity 20,900 Btuh Blower Motor 1/3 hp <br /> Efficiency (at AHRI) 11.00 EER ECM Blower Motor <br /> Outdoor DB Temp 95.0 °F Non-Ducted <br /> Entering DB Temp 80.0 °F <br /> Entering WB Temp 67.0 of Air flow is based on Wet Coil <br /> Leaving DB Temp 60.6 °F Electrical Data <br /> Leaving WB Temp 58.3 °F <br /> HP Heating Performance Power Supply 108/230 Volts <br /> Phase <br /> HP Capacity @47.0°F 26,400 Btuh 60 Hertz <br /> HP Capacity �a 17.0°F 16,500 Btuh Minimum Circuit Ampacity 24 Amps <br /> HP COP city @1@47.0 F 36, Maximum External Fuse or 35 Amps <br /> HP COP @17.0°F 2.2 Circuit Breaker <br /> Field Power Wire Size 8 <br /> Ground Wire 10 <br /> Electric Resistance Heat z Minimum Circuit Ampacity 42 Amps <br /> Nominal Heat Size g kW Maximum External Fuse or 45 Amps <br /> e 240 Volts Circuit Breaker <br /> Electric Heat Voltage Field Power Wire Size 8 <br /> Heat Output 27,304 Btuh Ground Wire 10 <br /> Maximum KW that can operate with the heat pump on is 8KW.Full <br /> heat available during Emergency Heat Mode. Based on 75C copper wire,All wiring must conform to the National <br /> Electrical Code and all local codes <br /> Caution:When more than one field power circuit is run through one <br /> conduit,the conductors must be derated.Pay special attention to note <br /> 8 of Table 310 regarding Ampacity Adjustment Factors when more <br /> than three(3)current carrying conductors are in a raceway. <br /> Approximate instalied Wei.; <br /> Unit Weight 400 Ib <br /> Option Weight 46 Ib <br /> Total Weight 446 Ib <br /> Factory Options Selected <br /> F8 - 8 KW - 2 circuits <br /> * Unit is shipped for one circuit, requires field modification for 2 circuits <br /> W -Telecom Economizer Ventilation Option - Enthalpy Control <br /> P - 2-Inch Pleated MERV 8 <br /> 4 - Buckeye Gray <br /> X - Front Outlet <br /> X - Standard Coils <br /> E - Standard Controls + LAC <br /> Field Installed Accessories <br /> 3�0 <br />