SYMBOL LEGEND: GROUNDING NOTES: <br /> MGB 1. GROUNDING SHALL COMPLY WITH LATEST EDITION OF THE NATIONAL ELECTRICAL CODE <br /> T . Sprint)� <br /> 7r MASTER GROUND BAR I/4'k4"X24"COPPER <br /> 2. MINIMUM BENDING RADIUS FOR GROUND CONDUCTOR IS 8'. <br /> AGB 3. NO SPLICES PERMITTED IN GROUND CONDUCTORS. <br /> ACCESSORY GROUND BAR 1/4'xd'x12'OR <br /> 7- 1/4'x4wv COPPER 4. ALL GROUNDING CONNECTORS TO BE CLEAN AND FREE OF PAINT AT THEIR MATING <br /> SURFACES AND INSTALLED PER MANUFACTURER'S RECOMMENDATIONS.USE PENETROX Ll <br /> PROJECT INFORMATION: <br /> EXPOSED WIRING OR EQUIVALENT ANTIOXIDANT GREASE. <br /> ----- UNDERGROUND WIRING 5. ALL GROUND BAR CONNECTIONS ARE TO BE 2 HOLE LUG COMPRESSION TYPE.STACKED <br /> CONNECTIONS ARE NOT ACCEPTABLE.BACK TO BACK CONNECTIONS ON OPPOSITE SIDES BROADWAY <br /> CADWELD OF THE GROUND BAR WILL BE PERMITTED. SE63XC209 <br /> • MECHANICAL CONNECTION 6. ENSURE ALL MECHANICAL CONNECTORS ARE TORQUED TO THE MANUFACTURER'S <br /> SPECIFIED VALUES. <br /> O 518k$COPPER CLAD STEEL GROUND ROD 2517 HOWARD AVE <br /> 7, MULTIPLE BONDS ON GROUND RODS TO BE SEPARATED BYATLEAST6". EVERETT,WA 98203 <br /> INSPECTION PORT 8. MAXIMUM RESISTANCE OF THE COMPLETED GROUND SYSTEM SHALL NOT EXCEED A <br /> RESISTANCE OF 5 OHMS TO EARTH. TISSUED FOR: <br /> EXOTHERMIC(CADWELD)BELOW GROUND 9. GROUND WIRES SHALL NOT BE INSTALLED THROUGH HOLES IN ANY METAL OBJECTS OR I <br /> SUPPORTS;TO PRECLUDEESTABLISHINGA'CHOKE"POINT. L BUILDING PERMIT <br /> 10. GROUND BARS SHALL NOT BE FIELD MODIFIED. REVISION HISTORY: <br /> 11. GROUND RING BURIAL DEPTH SHALL BE 30'. NO. DATE: DESCRIPTION: CNK. <br /> BY: <br /> 12. ACERTIFIED CONTRACTOR WILL MAKE ALL MEASUREMENTS REQUIRED TO TEST THE <br /> GROUNDING SYSTEM USING A MEGGER OR EQUIVALENT.THE ACCEPTABLE RESISTANCE <br /> MEASURED FOR THE GROUNDING SYSTEM WILL NOT EXCEEDS OHMS RESISTANCE.THREE <br /> DISTANCES SHALL BE USED:1 AT 100 FEET,1 AT 70 FEET,AND I AT 35 FEET.THESE <br /> DISTANCES ARE SUBJECT TO A SITE BY SITE BASIS.T-MOBILE-WTS SHALL BE GIVEN 24 <br /> X HOURS NOTICE ALL COSTS ASSOCIATED WITH GROUND TESTING WILL BE AT THE <br /> - X EXPENSE OF THE CONTRACTOR. <br /> X <br /> X k <br /> - X \X <br /> x \ QI > 1272014 SHEET Ai ADDED. BJT <br /> / Q 1/132014 ISSUED DESIGN REVIEW BJT <br /> PLANS PREPARED BY: <br /> i <br /> I - B. J. THOMAS, P.E. <br /> x 7607 BOTH AVE NE <br /> I MARYSVILLE, WA 98270 <br /> 206.851-1106 <br /> x DRAWN BY: CHK.BY: <br /> FjL BJ <br /> LICENSURE: <br /> (P)MECHANICAL CONNECTION <br /> F� <br /> BOND FROM(P)RRH 8 AGB >,4 Q <br /> z <br /> ANTENNA TO(E)AGB <br /> i.7S1E �'�a <br /> sSbN4L 6�' <br /> - (E)AGB MOUNTED NEAR ANTENNAS EQUIPMENT: <br /> ---- -- INSTALL(3)NEW ANTENNAS 8(3)NEW EQUIPMENT. <br /> DRAWING INFORMATION: <br /> DO NOT SCALE DRAWINGS.CONTRACTOR MUST VERIFY <br /> ALL DIMENSIONS AND ADVISE CONSULTANTS OF ANY <br /> ERRORS AND OMISSIONS.ALL PREVIOUS ISSUES OF THIS <br /> DRAWING ARE SUPERSEDED BY THE LATEST REVISION. <br /> THE INFORMATION CONTAINED IN THIS SET OF <br /> DOCUMENTS IS PROPRIETARY BY NATURE,ANY USE OR <br /> DISCLOSURE OTHER THAN WHICH IS RELATED TO NAMED <br /> CLIENT IS STRICTLY PROHIBITED. <br /> DRAWING TITLE: <br /> ELECTRICAL <br /> GROUNDING PLAN <br /> DRAWING NUMBER: <br /> ELECTRICAL GROUNDING PLAN <br /> E-1 22x34 SCALE:12"=1' <br /> 11x17 SCALE:1/4"=1' Eml <br />