FIRE PROTECTION, INC. <br /> PO BOX 12642 <br /> MILL CREEK,WA 98082 <br /> 14251290-9600 OR 1-800-681-1125 FAX 14251353-4546 February 1,2011 <br /> City of Everett - PLAN REVIEW <br /> RE; FIRE ALARM SYSTEM <br /> Please find enclosed plans for a Low Voltage FIRE ALARM SYSTEM <br /> installation in a an existing Non-Sprinkled Building. The system <br /> has been designed per City of Everett Retro Requirements, NFPA 72 , <br /> 2013 edition requirements as well as WAC, IBC, IFC 1103 . 7 . 6, NEC <br /> and your additional requirements . <br /> The building is Non-Sprinkled. The system shall monitor by zone <br /> activation as well as separate trouble signals . Monitoring shall <br /> be provided via UL listed Central Station, The Alarm Center LACEY, <br /> WA via a UL listed Wireless Communicator. Audibility shall be in <br /> compliance with NFPA standards with a outdoor horn/strobe located <br /> on the outside of the building in the top 25% with a 110 candela <br /> strobe facing the first in-coming FIRE DEPARTMENT vehicles for <br /> easy building location. A full service and monitoring agreement is <br /> in force for the proper service and maintenance per NFPA <br /> requirements . A full pre-test and NFPA form shall be conducted and <br /> completed prior to calling the AHJ for acceptance testing. <br /> INSTALLATION COMPANY <br /> Fire Protection, Inc. <br /> 1730 Gibson Rd. Everett, WA 98204 <br /> WSCL# FIREPI*021ML UL CERT #608242-002 <br /> JOB SITE ADDRESS <br /> Evergreen Place Apartments <br /> 5631 Highway Place <br /> Everett, WA 98203 <br /> APPROVED UL MONITORING COMPANY <br /> Alarm Center, Inc. /FPI <br /> 4300 3rd Ave . SE Lacey, WA 800-429-0991 <br /> UL CERT #902799-02 <br />