PURL/C WO/ Drs <br /> ADMINISTRATIVE ACTION <br /> DATE: February 18, 1999 <br /> PROJECT: City Hall, City of Everett <br /> SUBJECT: Type of Construction, Section 603.5 <br /> ACTION: Acceptance of wood bracing for parapet <br /> FINDINGS: <br /> • With exception, wood is not permitted within the roof/ceiling construction in Type II <br /> buildings. The wood in question is used as a voluntary seismic retrofit to brace a <br /> non-combustible parapet. <br /> • The wood is by definition within the roof/ceiling assembly, but is built over the <br /> ceiling slab and is therefore not part of the fire-resistive attributes of the assembly. <br /> • The wood is covered by the roofing material (Class A)thereby leaving no exposure <br /> threat. <br /> • Te wo d bracing is analogous to the wooden sleepers on the same roof that support <br /> t e ro op mechanical units, which are permitted per code. <br /> Tim Tyler, Building Official <br /> CITY OF EVERETT• 3200 Cedar Street • Everett, WA 98201 • (425) 257-8800 • Fax(425) 257-8856 <br />