My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
840 N BROADWAY 2017-08-21
>
Address Records
>
N BROADWAY
>
840
>
840 N BROADWAY 2017-08-21
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
8/21/2017 8:59:01 AM
Creation date
8/8/2017 1:35:52 PM
Metadata
Fields
Template:
Address Document
Street Name
N BROADWAY
Street Number
840
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
46
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Z1000 Standard Connection Diagram <br /> <2> For floating, impedance grounded,or asymmetrically grounded networks,disconnect the internal EMC filter by moving the SWI <br /> and SW2 screws to the OFF position. <br /> <3> A 24 V power supply option is required to supply power to the control circuit separately from the main circuit. <br /> <4> This figure illustrates an example of a sequence input to S1 through S7 using a non-powered relay or an NPN transistor. Install <br /> the wire link between terminals SC-SP for Sink mode,between SC-SN for Source mode,or leave the link out for external power <br /> supply. Never short terminals SP and SN, as it will damage the drive. <br /> <5> This voltage source supplies a maximum current of 150 mA. <br /> <6> The maximum output current capacity for the+V terminal on the control circuit is 20 mA. Never short terminals+V and AC, as <br /> it can cause erroneous operation or damage the drive. <br /> <7> Use jumper S1 to select between a voltage or current input signal to terminals Al and A2. The default setting is for voltage <br /> input. <br /> <8> Set DIP switch S2 to the ON position to enable the termination resistor in the last drive in a MEMOBUS/Modbus network. <br /> <9> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not <br /> intended for use as a feedback-type signal. <br /> <10> Use jumper S5 to select between voltage or current output signals at terminals FM and AM. Set parameters 1-14-07 and 1-14-08 <br /> accordingly. <br />
The URL can be used to link to this page
Your browser does not support the video tag.