UI�C�s <br /> Meg Haley <br /> From: Meg Haley <br /> Sent: Friday, June 16, 2017 10:39 AM <br /> To: 'Justin Cobb' <br /> Cc: Gene Timmons; Danny Klumper <br /> Subject: RE:Verification of compliance with cooling tower requirements in Washington State <br /> Energy Code (WSEC) <br /> Hi Justin, <br /> The economizer is required for all new equipment installations where indicated by code. There is not a grandfather for when <br /> equipment is replaced that you are referring to for"like for like" in the code. The other systems downstream do not have to be <br /> upgraded, but the energy code follows the theory of "you touch it you fix it" in all of the code training classes I have attended,since <br /> the state has mandated increased energy efficiency in each adopted code cycle. <br /> I included the information I sent you by e-mail in the folder, signed off for building, and the permit is now ready for structural <br /> review. <br /> Meg <br /> -----Original Message----- <br /> From:Justin Cobb [mailto:JustinC@Enviromech.com] <br /> Sent: Friday,June 16, 2017 10:19 AM <br /> To: Meg Haley <br /> Cc:Gene Timmons; Danny Klumper <br /> Subject: RE:Verification of compliance with cooling tower requirements in Washington State Energy Code(WSEC) <br /> Meg, <br /> On page CE-123 (the last page of the documents you sent me). We are installing the cooling tower under option B for cooling tower <br /> economizer. No requirements for economizer because it is the replacement of the same or smaller unit(like for like replacement). <br /> The rest of the minimum requirements we talked about on the phone are met(controls related). <br /> Thanks, <br /> Justin Cobb <br /> Retrofit Coordinator I ENVIROMECH <br /> 430 SW 153rd Street I Burien,WA 98166 <br /> o 206.762.1960 1 c 360.525.7883 <br /> -----Original Message----- <br /> From: Meg Haley [mailto:MHaley@everettwa.gov] <br /> Sent: Friday,June 16, 2017 9:43 AM <br /> To:Justin Cobb<JustinC@Enviromech.com> <br /> Subject:Verification of compliance with cooling tower requirements in Washington State Energy Code(WSEC) <br /> RE: M1706-050 840 N BROADWAY <br /> Hi Justin, <br /> I am preparing the submittal for sign-off, and noting that an economizer is required. Please review the attached excerpts from the <br /> WSEC and confirm that these minimum requirements are met by replying to this e-mail. I find the easiest way to review the code is <br /> to use the electronic version and search on cooling tower. The commercial energy code is linked on our website at <br /> everettwa.gov/codes <br /> Thanks! <br /> 1 <br />