kTELLIKNIGHT ACCESSORY <br /> Model SD500-ARM <br /> Addressable Relay Module <br /> Engineering Specifications <br /> The contractor shall furnish and install where indicated on the plans, addressable relay <br /> modules, Silent Knight SD500-ARM. The modules shall be UL listed compatible with Silent <br /> Knight's Intelliknight FACPs. <br /> The relay module must provide two Form C dry contacts rated at 2.0 amps at 30 VDC or .6 <br /> amp at 120 VAC. <br /> The relay module must be suitable for mounting in a standard 4-square electrical box and <br /> must include a plastic cover plate. The relay module board must provide an LED that is <br /> visible from the outside of the cover plate. <br /> The relay must be fully programmable for such applications as are required by the <br /> installation. <br /> FRONT VIEW <br /> CAUTION <br /> REMOVE POWER PRIOR TO SERVICING <br /> J.0 <br /> On z <br /> O <br /> 1 <br /> Q <br /> 4-7/8" 1/4` <br /> 1" <br /> Model SD500-ARM Addressable Relay Module Dimensions <br /> SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA <br /> KNIGHT to keep our product information up-to-date and accurate.We cannot cover <br /> all specific applications or anticipate all requirements.All specifications are FORM#350218 Rev. D <br /> subject to change without notice. For more information,contact Silent <br /> by Honeywell Knight 12 Clintonville Road, Northford,CT 06472-1610. ©2010 Honeywell International Inc. <br /> Phone:(800)328-0103, Fax: (203)484-7118. www.silentknight.com <br />