HEH 12VDC or 24VDC Low Profile Evacuation Horn
<br /> Model Number Part Number Nominal Reverberant dBA In Anechoic Room
<br /> Voltage @ 1 Oft.,per UL 464 dBA @10ft.
<br /> HEH24-WR 0500-05880 24VDC 62-82 100
<br /> HEH24-WW 0500-05890 24VDC 62-82 100
<br /> HES3 12VDC or 24VDC Selectable Candela Low Profile Evacuation Strobe
<br /> Model Part Nominal Candela
<br /> Number Number Voltage UL 1971
<br /> HES3-12WR 0500-05900 12 VDC 15, 30,60, 75 Model Designations:
<br /> HES3-12WW 0500-05910 12 VDC 15, 30,60, 75 W=Wall mount R= Red faceplateW= Off-white
<br /> HES3-12PWR 0500-05920 12 VDC 15, 30,60, 75 faceplateP = Plain (no lettering)
<br /> HES3-12PWW 0500-05930 12 VDC 15, 30, 60, 75
<br /> HES3-24WR 0500-05940 24 VDC 15, 30,60, 75, 110 ALERT bezel available
<br /> HES3-24W 0500-05950 24 VDC 15,30,60, 75, 110 AGENT bezel available.
<br /> W
<br /> HES3-24PWR 0500-05960 24 VDC 15, 30,60, 75, 110
<br /> HES3-24PWW 0500-05970 124 VDC 15, 30,60, 75, 110
<br /> HEC3 12VDC or 24VDC Selectable Candela Low Profile Evacuation Horn/Strobe
<br /> Model Part Nominal Candela Reverberant dba @ In Anechoic Room
<br /> Number Number Voltage (UL 1971) 1Oft., per UL 464 dBA @ 1Oft.
<br /> HEC3-12WR 0500-05980 12 VDC 15 30 60 75 62-82 100
<br /> HEC3-12WW 0500-05990 12 VDC 15, 30, 60, 75 62-82 100
<br /> HEC3-12PWR 0500-06000 12 VDC 15 30 60 75 62-82 100
<br /> HEC3-12PWW 0500-06010 12 VDC 15, 30, 60, 75 62-82 100
<br /> HEC3-24WR 0500-06020 24 VDC 15, 30, 60, 75, 110 62-82 100
<br /> HEC3-24WW 0500-06030 24 VDC 15, 30, 60, 75, 110 62-82 100
<br /> HEC3-24PWR 0500-06040 24 VDC 15, 30, 60, 75, 110 62-82 100
<br /> HEC3-24PWW 0500-06050 24 VDC 15, 30, 60, 75, 110 62-82 100
<br /> HE3-12 Product Strobe Current Ratings HE3-24 Product Strobe Current Ratings
<br /> Candela 15cd 30cd 60cd 75cd Candela 15cd 30cd 60cd 75cd 110cd
<br /> 12VDC 106mA 131 mA 186mA 237mA 24VDC 30mA 35mA 66mA 80mA 103mA
<br /> UL Max 92mA 141 mA 260mA 312mA UL Max 42mA 58mA 97mA 116mA J161mA
<br /> HE3-12 Product Horn Current Ratings NOTES:
<br /> Horn Mode Minimum dBA Minimum dBA Regulated 12VDC • Operating temperature: 32°to 120°F (0°
<br /> @ 1 Oft., per @ 1 Oft.,per Max.Operating @ to 49° C). The HE Series is not listed for
<br /> UL 464(HIGH) UL 464(LOW) High Setting (mA) outdoor use.
<br /> Temp 3 2400Hz 76 69* 29 •The sound output for the temporal 3
<br /> Temp 3 Mechanical 75 68* 26 tone is rated lower since the time the horn
<br /> Temp 3 Chime 62* 60* 13 is off is averaged into the sound output
<br /> Continuous 2400Hz 79 74* 29 rating. While the horn is producing a tone
<br /> Continuous Mechanical 78 72* 26 in the temporal 3 mode its sound pressure
<br /> Continuous Chime 63* 61* 13 is the same as the continuous mode.
<br /> Whoop 78 71* 55 • For nominal and peak current across UL
<br /> HE3-24 Product Horn Current Ratings regulated voltage range for filtered DC
<br /> Horn Mode Minimum dBA Minimum dBA Regulated 24VDC power and unfiltered(FWR [Full Wave
<br /> @ 10ft., per @ 10ft.,per Max.Operating @ Rectified]) power, see installation manual.
<br /> 12VDC models are DC only.
<br /> UL 464(HIGH) UL 464(LOW) High Setting (mA) e
<br /> r
<br /> Temp 3 2400Hz 78 71* 28 • Hochiki does not recommend using a
<br /> Temp 3 Mechanical 76 70* 25 coded or pulsing signaling circuit with any
<br /> of our strobe products (see Technical
<br /> Temp 3 Chime 70* 66* 15
<br /> Bulletin 014).
<br /> Continuous 2400Hz 81 74* 28
<br /> Continuous Mechanical 80 72* 25
<br /> Continuous Chime 70* 66* 15
<br /> Whoop 1 82 69* 56
<br /> *Operating the horn in this mode at this voltage will result in not meeting the minimum UL reverberant sound level
<br /> required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use.
<br /> Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always
<br /> private mode).
<br /> RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the
<br /> listed voltage range (16-33VDC for 24VDC units) (8-17VDC for 12VDC units). For strobes the UL max current is
<br /> usually at the minimum listed voltage (16VDC for 24VDC units) (8VDC for 12VDC units). For audibles the max current is
<br /> usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual.
<br /> Hochiki America Corporation HE Series Selectable Candela Evacuation Sginals Specifications subject to change without notice.
<br />
|