Laserfiche WebLink
EJECTOR PUMP STATION SCHEDULE (1) Z E= <br /> 0 � a <br /> SUMP BASIN DIMENSIONS ELECTRICAL(EACH PUMP) CAPACITY(EACH PUMP) Z e $$ <br /> DISCHARGEti <br /> NUMBER OF DAMETER DEPTH TYPE DIAMETER AMPS VOLTAGE/ TOTAL DEVELOPED Q o s <br /> TAG DESCRIPTION DESCRIPTION MANUFACTURER MODEL PUMPS (INSIDE CLEAR) (INSIDE CLEAR) (FLA) HP PHASE FLOW HEAD NOTES 0 .+ <br /> EJECTOR GRINDER PUMP STATION D3672LSG FIBERGLASS m <br /> EPS-1 TASK#i (SERVES ANNEX BASEMENT) LIBERTY (PACKAGE) 2 30' 72' (PRE FAB) 1-1/4' 15 2.0 HP 208Vl1P 25.0 GPM 80 FT (2)(3)(5) z a <br /> V <br /> c <br /> TASK#2 NO SCOPE -- -- -- --- — -- — -- — --- <br /> W <br /> EJECTOR GRINDER PUMP STATION D3672LSG FIBERGLASS <br /> EPS-3E TASK#3 LIBERTY 2 30' 96' 1-1!4' 15 2.0 HP 208V/1 P 25.0 GPM 80 FT (2)(3)(5) Z a E 8 <br /> (SERVES NORTH TOWER-EAST) (PACKAGE) (PREFAB) s k; <br /> EJECTOR PUMP STATION BASIN-EPS(4) FIBERGLASS <br /> EPS-4W TASK#4 LIBERTY 2 30" 72' 2' 6 314 HP 208Vl1 P 25.0 GPM 25 FT (2)(3)(5) _ •9 <br /> (SERVES NORTH TOWER-WEST) PUMPS-EPS <br /> (PREFAB) . "On <br /> EPS-SE TASK#5 PUMPS ELIMINATED FROM SCOPE -- — -- -- — -- — — — -- — -- — <br /> EPS-6W TASK#6 PUMPS ELIMINATED FROM SCOPE — — -- -- — — — -- — — -- —• -- Qt1ER(� <br /> �OC <br /> EJECTOR PUMP STATION BASIN-EPS(4) FIBERGLASS <br /> EPS-7 TASK#7 (SERVES PARKING GARAGE) LIBERTY PUMPS-LE102M2 2 36' 72' (PRE FAB) 2' 8 1 HP 208Vl1P 75.0 GPM 25 FT (2)(3)(5) <br /> NOTES: <br /> 1.WITH ALL OPTIONS AS NEEDED FOR A COMPLETE OPERATING SYSTEM. S'r '.F1 <br /> 2.PROVIDE DUPLEX CONTROL PANEL,FLOAT SWITCH ASSEMBLY,HIGH WATER ALARM,PUMP FAILURE ALARM AND ALL ASSOCIATED COMPONENTS NECESSARY TO MEET DESIGN INTENT AS PRESENTED ON PLANS. SUMP BASIN ELEVATIONS <br /> 3.COORDINATE W/OWNER FOR SPACE USAGE AND PROVIDE APPROPRIATE ACCESS COVER DURABILITY OPTION(MINIMUM SHALL BE STEEL). (MEASURED FROM BOTTOM OF BASIN) <br /> 4.CUSTOM BASIN SYSTEM:CONTRACTOR TO PROVIDE MANUFACTURER WITH SPECIFICATIONS GIVEN IN THIS SCHEDULE FOR CUSTOM PUMP/BASIN PACKAGE. <br /> 5.BASIN DEPTH BASED ON INVERTS PROVIDED BY CONTRACTOR. PUMPS OFF 12 in <br /> LEAD PUMP ON 27 in <br /> LAG PUMP ON 30 in Z <br /> O <br /> HIGH WATER ALARM 33 in <br /> INLET 36 in > <br /> w <br /> FINISHED FLOOR(TOP OF BASIN) 72 in <br /> SEQUENCE OF OPERATIONS-EJECTOR PUMP STATION a <br /> 0 <br /> PUMP DOWN CYCLE: <br /> O <br /> Z <br /> 1. BASIN FILLS TO'LEAD PUMP ON'LEVEL(SEE SUMP BASIN ELEVATIONS). <br /> 2. "LEAD PUMP'FLOAT ACTUATES AND POWERS ON LEAD PUMP. <br /> 3. LEAD PUMP OPERATES UNTIL LEVEL OF WATER IN BASIN REACHES"PUMPS OFF"FLOAT LEVEL. <br /> 4. 'PUMPS OFF'FLOAT ACTUATES AND TURNS LEAD PUMP OFF. w <br /> 5. BASIN FILLS TO'LAG PUMP ON'LEVEL(SEE SUMP BASIN ELEVATIONS). uj <br /> 6. 'LAG PUMP'FLOAT ACTUATES AND POWERS ON LAG PUMP. O N <br /> 7. LAG PUMP OPERATES UNTIL LEVEL OF WATER IN BASIN REACHES'PUMPS OFF"FLOAT LEVEL. � ,^ <br /> 8. CYCLE REPEATS. V I <br /> 00 <br /> a LW J Q (31f <br /> * -- Q I--I <br /> NOTES: Q Q Z <br /> IF WATER LEVEL REACHES"HIGH WATER ALARM','HIGH WATER ALARM'FLOAT SHALL ACTUATE AND SHALL ACTIVATE AUDIBLE F uj LOL <br /> AND VISUAL ALARM(ALARM TO OPERATE CONTINUOUSLY ONCE ACTUATED UNTIL DEACTIVATED MANUALLY BY SERVICE 7o L <br /> TECHNICIAN).PROVISIONS ARE TO BE MADE TO ALLOW OWNER TO CONNECT THIS ALARM SIGNAL TO THEIR BUILDING 2 Q Uj J <br /> AUTOMATION SYSTEM. a <br /> Q UJ <br /> IF ANY PUMP FAILS,AUDIBLE AND VISUAL ALARM SHALL ACTIVATE AND ALTERNATING PUMP FUNCTION SHALL CEASE TO OPERATE w Q Q <br /> (REMAINING FUNCTIONING PUMP SHALL OPERATE EXCLUSIVELY WHEN CALL FOR ANY PUMP(ANY'PUMP OW FLOAT ACTUATES) = O U W <br /> OCCURS.ALARM TO OPERATE CONTINUOUSLY ONCE ACTUATED UNTIL DEACTIVATED MANUALLY BY SERVICE TECHNICIAN). O O w <br /> PROVISIONS ARE TO BE MADE TO ALLOW OWNER TO CONNECT THIS ALARM SIGNAL TO THEIR BUILDING AUTOMATION SYSTEM. <br /> Lr_ N <br /> M <br /> IF ANY PUMP RUNS FOR LONGER THAN THREE MINUTES WITHOUT CYCLING OFF(INFLOW IS GREAT ENOUGH TO REQUIRE THE N <br /> PUMP TO RUN LONGER THAN THREE MINUTES TO PUMP DOWN TO'PUMPS OFF-FLOAT LEVEL),SYSTEM SHALL POWER ON <br /> SECOND PUMP(PUMP NOT ALREADY PUMPING).BOTH PUMPS SHALL OPERATE UNTIL LEVEL OF WATER IN BASIN REACHES <br /> "PUMPS OFF"FLOAT LEVEL.BOTH PUMPS SHALL TURN OFF WHEN LEVEL OF WATER REACHES'PUMPS OFF'FLOAT LEVEL. <br /> ALTERNATING OPERATION AS DESCRIBED ABOVE SHALL RESUME. SHEET TITLE: <br /> PARKING <br /> OIL/SAND SEPARATOR SCHEDULE SCHEDULES <br /> N CONNECTIONS(2) <br /> TAG DESCRIPTION MANUFACTURER MODEL CAPACITY NOTES <br /> INLET OUTLET VENT(TANK) <br /> SOS-7 OIL 8 SAND SEPARATOR <br /> (SERVES PARKING GARAGE) STRIEM OS-75 75 GPM 6'0 610 310 (1)(2x3) <br /> DATE: 1/27/2017 <br /> NOTES: CONSTRUCTION SET <br /> 1.WITH ALL OPTIONS AS NEEDED FOR A COMPLETE OPERATING SYSTEM. <br /> 2.CONNECTIONS ARE NOT STANDARD:CONTRACTOR TO CONFIRM SPECIAL ORDER WITH MANUFACTURER. ONE INCH AT FULL SCALE. <br /> 3.WITH TRAFFIC RATED LID. IF NOT,SCALE ACCORDINGLY <br /> SHEET: <br /> a <br /> P5.72 <br /> 4 <br /> fi SHEET OF <br /> 8 <br />