Laserfiche WebLink
� ' <br /> FIRE PROTECTION, INC. <br /> po Box�zsaz <br /> MILL CREEK,WA 98082 <br /> [4251 290-9600 OR 1-800-681-1125 FAX [4251353-4546 August 2,2016 <br /> City of EVERETT - PLAN REVIEw <br /> RE; FIRE ALARM SYSTEM <br /> Please find enclosed plans for FIRE AT.ARM SYSTEM Retrof�it for an <br /> existing residential building. The system has been designed per <br /> NFPA 72 , 2013 edition requirements as well as WAC, IBC, IFC <br /> 1103 . 7 . 6, NEC and your additional requirements . <br /> The building is Non-Sprinkled. The system shall monitor by zone <br /> activation as well as separate trouble signals . Monitoring shall <br /> be provided via UL listed Central Station, The Alarm Center LACEY, <br /> WA via the FACP' s DACT and 2 x telephone lines . Audibility shall <br /> be in compliance with NFPA standards with a outdoor horn/strobe <br /> located on the outside of the building in the top 25� with a 110 <br /> candela strobe facing the first in-coming FIRE DEPARTMENT vehicles <br /> for easy building location. Interior DB shall be 75 DB minimum <br /> throughout. A full service and monitoring agreement is in force <br /> for the proper service and maintenance per NFPA requirements . A <br /> full pre-test and NFPA form shall be conducted and completed prior <br /> to calling the AHJ for acceptance testing. <br /> INSTALLATION COMPANY <br /> Fire Protection, Inc. <br /> 1730 Gibson Rd. Everett, WA 98204 <br /> WSCL# FIREPI*021ML UL CERT #608242-002 <br /> JOB SITE ADDRESS <br /> Fountainhead Apartments <br /> 7333 Beverly Lane <br /> Everett, WA <br /> APPROVED UL MONITORING COMPANY <br /> Alarm Center, Inc. /FPI <br /> 4300 3rd Ave. SE Lacey, WA 800-429-0991 <br /> UL CERT #902799-02 <br /> . <br /> � <br /> ..�- <br /> , � , � <br />