Laserfiche WebLink
� <br /> • � <br /> 1 <br /> 5. Provide minimum R-10 rigid insulation at headers in exterior walls. Show requirement on <br /> plans in section drawings. <br /> 6. Insulate walls of skylight shaft to minimum R-21. Show on plans. <br /> 7. R-10 Rigid insulation installed on the exterior of the slab-on-grade shall extend to the top <br /> of the foundation and shall be protected from impact and exposure to ultra-violet light. <br /> Provide detail reflecting these requirements. <br /> 8. Concrete foundations supporting wood construction sha�l extend minimum 6 inches above <br /> the finished grade. Show on plans. <br /> 9. The application submitted is for a "Hobby Room". Please change references to a "Shed"to <br /> "Hobby Room", since a shed is considered an uninhabitable space. <br /> 10. Washington State Energy Code requires R-49 insulation in the roof structure, unless using <br /> single rafter or joist-vaulted framing members. <br /> 11. Specify U-Value for all fenestration. Show on plans. <br /> If you have any questions, please email or call me at (425) 257-8976. Upon submittal of the <br /> drawings, your application will be given priority and plan reviews will recommence. All required <br /> submittals shall be sufFicient detail and contain sufficient information to ensure that the proposed <br /> structure will be constructed in compliance with all adopted codes. <br /> Please prepare a response letter showing where each item in this correction <br /> letter is addressed on the plan set. <br /> Sincerely, <br /> ]eff Fleilman <br /> Development Technician <br /> City of Everett Public Works Department <br /> 3200 Cedar St, Everett, WA 98201 <br /> OfFice: 425-257-8810 � Direct: 425-257-8976 <br /> Page 2 of 3 <br /> CITY OF EVEREfT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax (425) 257-8857 <br />