KirklandDvnamics <br /> Section 1—Processing Facility Building Information <br /> Occupancy: F-1 minimum required/Processing within an <br /> identified Control Area designed to WSBCC Fire <br /> Code Rules <br /> Extraction Equipment Manufacturer: Terpp Extractors <br /> 219 N Timberline Rd <br /> Fort Collins, CO 80524 <br /> Extraction Equipment Models: Terpp MK 4c <br /> Spark Proof Recovery Pump <br /> Weight Scale <br /> Solvents Used: Flammable Gas (IsoButane/ nButane)— <br /> Liquified/Gas <br /> ONLY RATED FOR BUTANE (R600/ R600a) <br /> Solvent Quantity: Not to exceed 150 lbs(30 Gallons) Per Control <br /> Area (See local codes) <br /> Lab Construction: IBC/IFC Control Area Design or H-2 Type, NFPA <br /> 70 Electrical Design protection measure K <br /> option may be used or Classified Electrical to <br /> Class I Division 2,static resistant floor. <br /> (Processing Lab design/approval not included <br /> in this report) <br /> 9/1/2015 Project: 150703 Terpp MK IV CLE Report Page 4 of 44 <br /> KD Doc. 150703ER <br />