<br /> GRILLE, REGISTER AND DIFFUSER SCHEDULE e'
<br /> �
<br /> EQUIP. SERVICE MANUFACTURER MODEL DESCRIPTION u
<br /> ID N0. SiYLE MATERIAL FRAME FRAME MODEL FACE SIZE NECK SIZE MAX CFM BRANCH DUCT NC COLOR NOTES �
<br /> At CEILING DIfFUSER TITUS MCD MOD CORE STEEL LAY-IN BORDER iYPE 3 24z24 8X8 100 6 <15 [7] [3], [4] � a
<br /> A2 CEILING DIFFUSER TITUS MCD MOD GORE STEEL LAY-IN BORDER iYPE 3 24x24 1OX10 210 8 <15 [7] [3], [4]
<br /> A3 CEILING DIFFUSER TITUS MCD MOD CORE STEEL LAY-IN BORDER TfPE 3 24x24 12Xi2 375 10 <15 [�) �3�� �4� ARCHITECTUFZE 7124THAVE.S.
<br /> A4 CEILING DIFFUSER TITUS MCD MOD CORE STEEL IAY-IN BORDER 1YPE 3 24z24 14X14 550 12 18 [7] [3�, [4] PLANNING NASHVILLE,TN 37210
<br /> Bi REfURN OR EXHAUST GRILLE . TITUS 50F EGGCRATE ALUMINUM LAY-IN BORDER iYPE 3 24z12 22X10 600 PER PLAN <12 [7] (�], (4� INTERIORS (Fj 615.244.814�
<br /> 82 RETURN OR EXHAUST GRILLE TITUS 50F EGGCRATE ALUMINUM LAY-IN BORDER iYPE 3 24x24 22X22 1200 PER PL1N <12 [7] (�], (4] GRAPHICS www.mjmarch.com
<br /> D1 R�fURN OR EXHAUST GRILLE TITUS 350RS SINGLE DEF STEEL SURFACE BORDER iYP� 1 24x16 22z14 1250 PER P�N — [7) [1], [4]
<br /> D2 RETURN OR EXHAUST GRILLE TITUS 350RS SINGLE DEF STEEL SURFACE BORDER TYPE 1 48x36 46x34 6300 PER PLAN — (7] [1], [4]
<br /> D3 RETURN OR EXHAUST GRILLE TITUS 350RS SINGLF DEF STEEL SURFACE BORDER 1YPE 1 38z32 36x30 4000 PER PLAN — [7] [i], [4]
<br /> P�- � � �r
<br /> Et SUPPLY GRILLE TITUS 300RS DOUBLE DEF STEEL SURFACE BORDER IYPE 1 14X8 12z6 250 8 19 [7] [1] �O �� W AstiiO�j•
<br /> � G' v
<br /> E2 SUPPLY GRILLE TITUS 300RS DOUBLE DEF STEEL SURFACE BORDER T(PE 1 14X10 12X8 285 8 15 [7] [1) Q' ,��;. o
<br /> E3 SUPPLY GRILLE TITUS 300RS DOUBLE DEF STEEL SURFACE BORDER iYPE 1 16X12 14X10 440 PER PLAN 16 [7] [1] � �`
<br /> E4 SUPPLY GRILLF TITUS 300RS DOUBLE DEF STEEL SURFACE BORDER IYPE 1 18X18 16X16 800 PER PLAN 19 [7] [1], [5]
<br /> � 35240 �O ���
<br /> ��'�` �FG'/STER \�
<br /> Fl ROOF(OP SYSTEM RUSKIN 570-36 DOUBLE DEF ALUMINUM SURFACE N/A 36X9 N/A 4400 PER P�N 30 [7] [2], �5], [6] �SS/p N A�E�G
<br /> F2 ROOFTOP SYSTEM RUSKIN 570-40 DOUBLE DEF ALUMINUM SURFACE N/A 40X11 N/A 7000 PER PLAN 30 [7] [2], [5], [6]
<br /> NOTES:
<br /> 1. PROVIDE PLENUM CAN FOR DUCTED SYSTEM OR SOUND 900T AS INDICATED ���»���I� J
<br /> 2. NEVER USE BORDER iYPE 77 �
<br /> 3. FOR LIMITED CEILING HEIGHT APPLICATIONS, PROVIDE SIDE INLEi CAN OTHERWISE PROVIDE SQUARE TO ROUND ADAPTOR W/ TOP INLET �
<br /> 4. DIFFUSER OR GRILLE MAY ALSO BE USED FOR HARDLID APPLICATIONS WHERE A TITUS "iRM" RAPID MOUNT fRAME IS PROVIDED, FRAME AS INDICATED ON PLANS. TRM PROVIDES ACCESS ABOVE CEILING. �
<br /> 5. PROVIDE TRANSITION FROM DIFFUSER NECK TO BRANCH DUCT SIZE INDICATED.
<br /> 6. PLENUM CAN PROVIDED W1TH DIFFUSER
<br /> 7. COORDINATE COLOR WITH ARCHITECT PRIOR TO ORDERING
<br /> CEILING FAN SCHEDULE
<br /> TAG BAF-101 BAF-102 ' UNIVERSITY
<br /> SERVICE EXERCISE AREA FXERCISE AREA M��HANICAL
<br /> LOCATION CEIIING CEILING CONTRACTORS� INC.
<br /> We Build Value
<br /> EQUIPMENT
<br /> MANUFACTURER BIG ASS FAN BIG ASS FAN 11611 49th Place West, �
<br /> MODEL PFX3-08 PFX3-OS Mukilt2o, Washington 98275 �
<br /> Phone: 206) 364-9900
<br /> FAN iYPE CEIUNG CEIi ING Fax: 206) 361-2126 Q
<br /> DRI4E DIRECT DIRECT www.umci.com
<br /> DIAMETER g' g' �
<br /> PERFORMANCE �
<br /> CFM N/A N/A t/�
<br /> TSP N/A N/A Z
<br /> RPM N/A N/A o
<br /> ELECTRICAL V
<br /> BHP 1.0 1.0
<br /> HP 1.0 1.0
<br /> AMPS 20 20
<br /> VOLT/PHASE 208/1 208/1 ,���:�.,
<br /> ��, �,
<br /> � POWER NORMAL NORMAL _��:�' y
<br /> STARTER VFD-FACTORY VFD-FACTORY � �y§
<br /> �1� ; / ,
<br /> --fURNISHED�INSTALLED MC � EC MC � EC � ���� � �-���
<br /> DISCONNECT BY DIV. 26 BY DIV. 26 �,.' ,'
<br /> —FURNISNED/INSTALLED EC / EC EC / EC
<br /> PHYSICAL
<br /> `,`
<br /> � WEIGHT 222 222 `� � � � • '�
<br /> MINIMUM SIDE CLFA.RANCE 2' 2' '�--� -
<br /> ,� t"_
<br /> � ��
<br /> NOTES . �.�
<br /> 1,2,3 1,2,3 ;:..:
<br /> "°TES: P LAN E�T
<br /> i. COORDINATE COLOR SCHEME WITH ARCHITECT PRIOR TO ORDERING
<br /> 2. COORDINATE LENGTH OF EXTENSION TUBE WITH ARCHITECT PRIOR TO ORDERING �I�1 tl E�'� � T N
<br /> 3. PROVIDF WITH WALL MOUNTED CONTROLI ER IN MANAGERS OFFICE
<br /> �
<br /> 1�1
<br /> 161 BELLE FGREST RD. �
<br /> #208 �
<br /> NASHVILLE, l"N 37221 �
<br /> DUCT INSU�ATION SCHEDU�E
<br /> TEMP RANGE INSUlATION R—VALUE
<br /> DUCT TYPE [7,8] LOCATION (DEGREES F) REQUIREMENT INSULATION TYPE
<br /> OUTSIDE AIR [1,2,9] UPSTREAM Of DAMPER [3] ALL R-18 [4] fIBERGLASS
<br /> DOWNSTREAM OF DAMPER, UNCONDITIONED SPACE ALL R-6 FIBERGLASS
<br /> DOWNSTREAM OF DAMPER, CONDITIONED SPACE ALL R-8 FIBERGfASS
<br /> SUPPLY AIR (5,6,9] UNCONDITIONED SPACE ALL R-6 FIBERGLASS
<br /> OUTSIDE THE BUILDING ALL R-8 FIBERGLASS
<br /> $��' � CONDITIONED SPACE <55 OR >105 R-3.3 FIBERGL4SS
<br /> �;
<br /> r� CONDITIONED SPACE 55-105 NONE NA �L/`'�N E.T
<br /> �;' REfURN AIR [5,6] UNCONDITIONED SPACE ALL R-6 [6] FIBERGLASS
<br /> F� FITNE�>S
<br /> CONDITIONED SPACE NA NONE [10] NA
<br /> �' OUTSIDE THE BUILDING ALL R-8 FIBERGLASS
<br /> �..
<br /> ;f� �
<br /> `� � EXHAUST AIR UPSTREAM OF DAMPER ALL NONE NA �
<br /> � L � ALL R-18 [4] FIBERGLASS
<br /> � DOWNSTREAM OF DAMPER 3
<br /> —
<br /> �
<br /> CASCADE PL,AZA �
<br /> {,
<br /> 7621 EVERGFtEEN WAY �
<br /> �" COMPLIANT WITH 2O15 WA STATE ENERGY CODE, COMMERCIAL PROVISIONS (WSEC) AND 2015 SEATfLE COMMERCIAL ENERGY CODE (SCEC). EVERETT, W��. �
<br /> NOTES: p�y
<br /> � l
<br /> �� 1. OUTSIDE AIR DUCTS SERVING INDIVIDUAL SUPPLY NR UNITS WITH LESS THAN 2,800 CFM TOTAL SUPPLY ONLY NEED R-7 INSULATION. �
<br /> �.
<br /> r� 2. NOT REQUIRED IN UNHEATED EQUIPMENT ROOMS WITH COMBUSTION AIR LOUVERS PROUIDED THE ROOM IS ISOLATED fROM CONDITIONED SPACE WITH R-11 INSULP,TION.
<br /> ��s
<br /> t3
<br /> 3. INSULATE BEiWEEN EXTERIOR ENVELOPE (WALL OR ft00F PENEfRATION) AND ISO(ATION DAMPER.
<br /> :;;
<br /> �.,
<br /> 4. MINIMUM R-VALUE FOR OUTSIDE AIR DUCTS IS SAME AS FOR METAL FRAMED WALL PER TABLE C402.1.2. R-18 MEEfS THIS EXTERIOR WALL REQUIREMENT fOR
<br /> E;� ' � CLIMATE ZONES 4 AND 5. KING COUNiY IS ZONE 4C. USE R-21 FOR ZONE 6: FERRY, OKANOGAN, PEND OREILLE, AND STEVENS COUNTIES. . PERMIT SET
<br /> �§� 5. INSULATION NOT REQUIRED fOR DUCTNORK WITHIN EQUIPMENT.
<br /> �,i w
<br /> �5:W 0 3S 1 � /� 017
<br /> � 6. FOR EXAMPLE, ABOVE CEIIJNG PLENUMS WITH DUCTED REfURN ARE CONSIOERED UNCONDITIONED SPACE; HOWEVER, WHERE DESIGN TEMPERATURE DIFfERENCE �
<br /> Si BEPNEEN THE INTERIOR AND EXTERIOR OF THE DUCT OR PLENUM DOES NOT EXCEED 15 F, NO INSULATION IS REQUIRED. Q
<br /> �
<br /> 7. INSULRTION FOR PLFNUMS SHALL 2E THE SAME AS ABOVE FOR DUCTS, DFpENDING ON SERVICE. REFER TO OUTSIDE AIR, SUPPLY, REfURN, OR EXHAUST SERVICE. M�M � XXXXX �
<br /> � 8. PROVIDE ALL SERVICF JACKET FOR ALL DUCTS, EXCEPT PROVIDE WEATHERPROOF ALUMINUM JACKEi FOR DUCTS OUTSIDE THE BUILDING.
<br /> +?7
<br /> �..
<br /> 9. PROVIDE VAPOR-RF_TARDER MASTIC ON SUPPLY AIR AND OUTSIDE AIR DUCTS AND PLENUMS.
<br /> i:3
<br /> c:�_
<br /> 10. RETURN AIR PLENUMS WITH PERMANENT 0?ENINGS TO CONDITIONED SPACE ARE CONSIDERED CONDITIONED SPACE. NO. DESCRIPTION DATE
<br /> E
<br /> �;a
<br /> �>
<br /> �"�
<br /> s
<br /> ,� �
<br /> �3
<br /> n;.
<br /> t.�` Z
<br /> %�.
<br /> ( �
<br /> t;.3
<br /> C3 '
<br /> r"�
<br /> [�;
<br /> £v �
<br /> tI3 >c�l
<br /> �
<br /> '�;s �
<br /> „
<br /> s;j
<br /> .,'
<br /> t::)
<br /> .�.,
<br /> C7
<br /> iJ
<br /> ✓''
<br /> �q� This drawing and the design shown is the property of the
<br /> architect. The reproduction,copying or use of this drawing
<br /> 'i�
<br /> without their written consent is prohibited and any
<br /> -s
<br /> infringement will be subject to legal action.
<br /> ✓'�
<br /> r''
<br /> MECH.ANICAL
<br /> ��� SCHEDULES
<br /> .�
<br /> �
<br /> � �
<br /> P,�� �
<br /> �h
<br /> f`� � / w
<br /> �,.,
<br /> `� � �
<br /> r�� M,.
<br /> r.� � �
<br />
|