CHCSC Rucker Ave July 12,2017 (2/3 <br /> original 1973 drawings for the building,the masonry is not detailed to take lateral loads from the <br /> building structure and are not detailed to have masonry lateral loads transferred to the building's steel <br /> moment frame system. The current upgrade design is based on new braced frames taking diaphragm <br /> loads, including tributary masonry wall seismic forces. Since the braced frames are inset from the <br /> exterior wall lines,the goal is to limit forces reaching the exterior masonry by collecting diaphragm <br /> forces before the exterior wall line. The braced frame drift,with deflection amplification,is 0.58%and <br /> does not take into account stiffness added by the existing building frame. <br /> See the attached comparison of wall pier shear stresses,without and with braced frames. The masonry <br /> maximum shear stress is roughly 151 psi. Per ASCE 41-13,table 11-2(b)the default lower bound shear <br /> strength of reinforced masonry can be taken as those determined from TMS Section 3.3.4.1.2 which <br /> would be 4 sqrt( m)or roughly 155 psi. <br /> The walls are modelled as concrete in the ETABS model using the effective thickness of 8"masonry <br /> grouted at 48"oc(effective thickness 4.6") <br /> Item 8. <br /> See supplemental calculations for calculations relating to the out-of-plane strength and anchorage of <br /> existing reinforced masonry walls. <br /> Item 9. <br /> Please see revised footing details. The anchor bolt details have changed to use steel plates at the base <br /> end to engage the concrete rather than using anchor rod pullout. <br /> Item 10. <br /> See added detail showing protected zones of the braced frames. <br /> Item 11. <br /> The brace reinforcing requirements of AISC 341-10 Sec. F2.5b are to account for lost section due to <br /> over-slotting of the brace at the gusset connection leaving a hole or gap. In detail 6/S3.1 where the <br /> brace is continuously welded,there are no holes or gaps,thus reinforcing is only required at the gusset <br /> plate edges where over-slotting is possible. <br /> Item 12. <br /> See general structural notes revised note 44 identifying demand critical welds. <br /> Item 13. <br /> See supplemental calculations for brace reinforcing and welding per AISC 341-10 Sec. F2.6. <br /> Reinforcing plate length revised for welds to develop plates. <br /> Item 14. <br /> See supplemental calculations for beam verification. Beams as shown are adequate. <br /> Item 15. <br /> Please see pages 10-15 of the submitted structural calculations in which the requirements of ASCE 341- <br /> 10 Table D.1.1 are checked and verified. <br /> Item 16. <br /> The column splice shown meets the requirements of ASCE 341-10. The columns are spliced using <br /> complete penetration welds which will develop the full flexural strength of the column as well as the <br /> full shear strength of the column. <br />