Laserfiche WebLink
PANEL SCHEDULE:08/17/2017 (E) PANEL 'PORT6' PROJECT:Eisenhower MS-Portables <br /> CLASSIFICATION:NORMAL VOLTAGE:208/120V 10,3-WIRE SECTION:1 OF 1 <br /> FED FROM:(E)DIST.PANEL'MDS' MAINS:200A MAIN CIRCUIT BREAKER <br /> MOUNTING:FLUSH NEUTRAL:100%RATED AIC:22,000 <br /> CKT BREAKER LOAD LOAD BREAKER CKT <br /> NOTE ITEM DESCRIPTION NO. AMPS POLE (VA) 0 (VA) AMPS POLE NO. ITEM DESCRIPTION NOTE <br /> LIGHTING 1 20 1 792 A 7208 90 2 2 HVAC <br /> RECEPTS 3 20 1 1260 B 7208 - - 4 - <br /> RECEPTS 5 20 1 1080 A 500 20 1 6 HC CABINET 1 <br /> RECEPTS 7 20 _ 1 972 B 20 1 8 SPARE <br /> 1 NAC PANEL 9 20 1 200 A 20 1 10 SPARE <br /> SPACE 11 - 1 B 20 1 12 SPARE <br /> SPACE 13 - 1 A 20 1 14 SPARE <br /> SPACE 15 - 1 B 20 1 16 SPARE <br /> SPACE 16 - 1 A 20 1 17 SPARE <br /> SPACE 18 - 1 B 20 1 19 SPARE <br /> LOAD CALCULATIONS <br /> LOAD DESCRIPTION CONN.(VA) DEMAND FACTOR CALC.(VA) <br /> MISCELLANEOUS CONTINUOUS: - 125% - LOAD SUMMARY <br /> EQUIPMENT&MISCELLANEOUS: 15116 100% 15116 <br /> LIGHTING: 792 125% 990 TOTAL <br /> LARGEST MOTOR: - 125% - CONNECTED LOAD AMPS <br /> MOTORS: - 100% - <br /> RECEPTACLE: 3312 100% 3312 PHASE A: 9,780 VA 82 A <br /> RECEPTACLES OVER 10kVA: - 50% - <br /> PHASE B: 9,440 VA 79 A <br /> TOTAL CALCULATED LOAD: 19,418 VA <br /> TOTAL CALCULATED AMPS: 93 A <br /> TOTALS: 19,220 19,418 <br /> NOTES: HARGIS ENGINEERS,INC. <br /> 1.PROVIDE NEW BREAKER AS INDICATED IN AVAILABLE SPACE. 1201 THIRD AVENUE,SUITE 600 <br /> 2. SEATTLE,WA 98101 <br /> 3. <br /> 4. PH.(206)448-3376 <br /> 5. FAX.(206)448-4450 <br />