46. Fire apparatus roads shall have a minimum unobstructed width of 26 feet in the immediate <br /> vicinity of any building or portion of building more than 30 feet in height.At least one of the <br /> required access routes shall be located within a minimum of 15 feet and a maximum of 30 <br /> feet from the building and shall be positioned parallel to one entire side of the building. See <br /> 2012 IFC,Appendix D, D105.3. <br /> 47.Where elevators are provided in buildings, at least one elevator shall be provided for fire <br /> department emergency access to all floors. The elevator car shall be of such a size and <br /> arrangement to accommodate a 24-inch by 84-inch ambulance stretcher in the horizontal, <br /> open position and shall be identified by the international symbol for emergency medical <br /> services (star of life). The symbol shall not be less than 3 inches high and shall be placed <br /> inside on both sides of the hoistway door frame. Exception: If all stories within the building <br /> have direct, accessible egress to grade(EMC 16.01, Section L; IBC 3002.4,2012 Edition). <br /> 48. A building footprint and lot layout for this project shall be provided to the Fire Marshal's <br /> Office on CD/DVD. <br /> 49. Traffic Calming Devices(Speed Bumps) (Fire Marshal Policy) <br /> a. The length of installation should be approximately 12 feet from the beginning of rise from <br /> the pavement surface to return to,the pavement surface. <br /> b. Undulations should be approximately 4 inches in height at the highest point and a <br /> circular arc surface should be used from point of rise to the end of the undulation. <br /> Undulations approximately 3 inches in height can also be used. <br /> c. Undulations should be placed approximately 600-700 feet apart with minimum distance <br /> being approximately 400 feet for public streets. <br /> d. Design for private roads and complexes shall be approved by the Fire Marshal's Office. <br /> e. Warning signs must be posted providing notice of the undulations. <br /> 50. If required for the Lego building, a floor map shall be included at each stair landing (11"x <br /> 17"size) and at each elevator landing (16"x 20"size)showing the layout and room <br /> numbering of the floor Stairwell signs shall be designed per Everett Fire Marshal Policy. Go <br /> to www.everettfire.orq to view the policy. <br /> 51. Dumpsters over 1.5 cubic yards capacity shall be located a minimum of 5 feet from the <br /> building (IFC 304 3.3 and 304.3.4, 2012 Edition). <br />