Laserfiche WebLink
— Event initiation worked control units. An ARIES NETLink system can <br /> — Protected-premises local and/or remote event include only one Fiber Optic Converter Card per control <br /> annunciation unit. The network structure supports up to 5,280 ft long of <br /> — Occupant notification via audible and visible sig- 62.5/125 Nm or 100/140 �m multi-mode duplex media <br /> naling appliances fiber. <br /> — Process/equipment control to activate safety pro- <br /> cedures <br /> — Fire extinguishing system release FIBER OPTIC CONVERTER CARD-FOCC(FUTURE) <br /> — Off-premises transmissions to central station or Number of Cards: Max 1 in control u it <br /> fire department (requires NIC) <br /> The network provides several convenient interconnect Input Voltage: 24 VDC Nominal, Maxi- <br /> programming schemes wherein control panels can be mum 28 VDC <br /> configured individually or within created groups of control Data Ports: EIA/TIA-485 <br /> panels. When utilizing the grouping configuration, the gaud Rate: 38,400 Baud <br /> interconnection automatically provides shared alarm and Optical Link Distance: 5,280 ft. (1,609 m) <br /> trouble responses. The programmable shared responses <br /> are: acknowledge, silence, reset, event logging and logic Max allowable cable Not to exceed 4 dB/km <br /> statements. Operator events can be activated into the attenuation: <br /> interconnection via the control panels or any annunciator. Temperature Range: 0°to 50°F <br /> A location address and programmable description is Humidity Range: 0 to 93% RH, non-con- <br /> used to identify the panel initiating the event. densing <br /> Network InterFace Card—NIC (FUTURE� Digital Alarm Communicator Transmitter — DACT <br /> The Network Interface Card regenerates and boosts net- FUTURE <br /> work communications between control units and electri- The communication capabilities of the ARIES NETLink <br /> cally isolates the networked units from each other. All <br /> ARIES NETLink units must contain a NIC to be net- control unit are enhanced with an optional DACT which <br /> worked to one another. The NIC occupies a single slot in transmits system status over phone lines to a Central <br /> the Card Cage Assembly. Using the NIC,the control units Station. The DACT card includes a built-in modem and <br /> transmit and receive messages via RS485 format over a �o Loop Start Public Switched Telephone Network <br /> twisted pair. An optional Fiber Optic Converter Card �PSTN) connections. Status LEDs are provided to indi- <br /> (FOCC) in addition to the NIC allows connectivity via a cate data transmission (green)and reception (yellow).An <br /> fiber optic medium. The networking structure supports a ARIES NETLink system allows one DACT Card per con- <br /> mixture of fiber-optic and twisted-wire interconnections trol unit. The DACT card operates on 24 Vdc and sup- <br /> among networked control units. The network structure Ports SIA DC-05-1999.09 Ademco Contact ID and SIA <br /> also supports 4,000 ft long 18AWG of copper wire. DC-03-1990.01 (R2003.10) protocols. <br /> NETWORK INTERFACE CARD-NIC(FUTURE) DIGITAL ALARM COMMUNICATOR TRANSMITTER(DACT) <br /> Number of Cards: Max 1 in control unit Number of Cards: Max 1 in control unit <br /> Number of nodes in network: Maximum 64 Circuit Voltage: Nominal 24 VDC, maxi- <br /> Wiring Classes: Class A or Class B mum 28 VDC <br /> Data Ports: EIA/TIA-485 Electrical Interface: PSTN line using a <br /> RJ31X phone jack <br /> Baud Rate: 38,400 baud Supported Protocols: SIA DC-05-1999.09 <br /> Recommended Wiring: AWG 18, twisted, Ademco Contact ID <br /> shielded, pair SIA DC-03-1990.01 <br /> Maximum Recommended 4,000 ft. (1,219 m) (R2003.10) <br /> Length: <br /> Fiber Optic Converter Card—FOCC(FUTURE) <br /> The FOCC occupies a single slot in the Card Cage <br /> Assembly and is installed adjacent to the NIC. It converts <br /> electrical signals from the NIC into light pulses and per- <br /> mits distances of up to 1 mile (5,280 ft.) between net- <br /> -7- <br />