T f <br /> ��`����� r���d' � . . . . <br /> The economizer reduces the cost of air conditioning by using outside air when acceptable to cool the room. The <br /> factory installed Marvair'� econamizer has integral pressure relief. On a signal from a thermostat that cooiing is <br /> required, either mechanical cooiing with the compressor or free caoling with the economizer is provided. The Marvair <br /> economizer is capable of bringing in outside air equai ta 100% of the rated coofing capacity of the unit and has built <br /> in pressure relief. <br /> An internal enthalpy contraller determines whether the outside air is sufficiently cool and dry to be used with cooling. <br /> If suitable, the campressor is locked out and the economizer damper opens to bring in outside air. The temperature at <br /> which the economizer opens is adjustable from approximately 55°F (13°C} to 73°F (23°C} at 54% RH. If the outside <br /> air becomes too hot or humid, the economizer damper closes completely or to a minimum position and mechanical <br /> cooling is activated. When used with minimum position potentiometer (optional), the Marvair� economizer can meet <br /> requirements of ASHRAE Std. 62. <br /> ��"�������� �� �������� � �'�� ���� � �a . .�� <br /> The Marvair GreenCube� ERV is an enthalpy plate heat exchanger that transfers both sensible and latent energies <br /> between outgoing and incoming air streams in a cross flow arrangement. Except for two air movers, it has no moving <br /> parts. It can introduce up to a maximum of 300 cfm of outside air into the cfassroom. Two MERV 6 type filters are <br /> used on both sides of the enthalpy core. The fresh air and exhaust motors have indspendent speed controllers to <br /> permit each of the motors to be reguiated independently. <br /> The media is impregnated with a RC134 polymeric desiccant that exchanges water by direct vapor transfer using <br /> mafecular transport without the need af candensation. The GreenCube° ERV will operate at temperatures as low as <br /> 10°F with no defrost mechanism. In addition, the desiccant is a bactericide. <br /> The'GreenCube° ERV isonly avaiiable on HVPSA units {2-stage carnpressor}. All HVPSA units wi#h the GreenCube� <br /> ERV, inciuding the HVPSA35 and HVPSA42, are in t�e F�VPSA49/60 cabinet (see page 28). <br /> ��� ��� ������ ������ <br /> Marvair-�a heat pumps equipped with Hot Gas Reheat (HGR) alfow the indaor humidity of the controlled environment <br /> to be maintained at or below a certain humidity set point. These units do not have the ability to add humidity to the <br /> classroom. Dehumidification is achieved by aperating mechanical cooling in conjunction with a hot gas reheat coil. <br /> Operatian - If the humidity rises above the set point on the humidity controller and th.e temperature in the classroom <br /> is satisfied, both mechanical cooling and the HGR coil operate to temper the air and lower the humidity. If the <br /> temperature in the classroom rises above (or falls below} the set point of the thermostat and the unit is operating in <br /> the dehumidification mode, the call for coofing (or heating) will override the call for dehumidification and the coil is <br /> disengaged until the thermostat is satisfied. This assures the environment temperature is maintained as first priority <br /> and humidity control is second. <br /> ���� ���� �� �� � <br /> Each Classic heat pump has a PC baard that contrals the operatian of the indoar blower, the compressor and the <br /> reversing valve while providing high refrigerant pressure and loss of refrigerant pratection with an integral defrost <br /> funetion. In addition, tiie board has user selectab[e pins and patentiometers for multi-function control. <br /> Ffigh&loss of refrigerant protection— If either of these fault conditions occur twice within an one hour, the control <br /> baard will enter into and indicate the lockout mode. In the lockout mode, the compressor will not operate, the alarm <br /> output is energized and the red LED will blink to indicate which fault has occurred. The user can select either Normally <br /> Open or Normally Closed contacts. <br /> Compressor anti-short cycle protection — An integral three minute delay prevents compressor from destructive <br /> short cycling. <br /> Loss of Refrigerant By-pass Timer — To prevent nuisance fault alarms, the board ignores a loss of charge fault for <br /> three minutes on start-up of the compressor. <br /> Defrost Control —The defrost cycle removes ice build-up an the outdoor coil during the heating cycle. If the defrost <br /> sensar senses a coil temperature of 32°F while in the heat mode, a 30, 60 or 90 minute (user selectable) delay period <br /> will begin. After the delay period if the sensor is still ca►ling far a defrost cycle, the outdoor fan will be stopped and <br /> the reversing valve energized. The defrost cycle will stop if the defrost sensor registers a temperature of 50°F or after <br /> 10 minutes. ' <br /> Classic AVPA2�-3�36-42-46-60,HVPA24-30-30-42-49-60&HVPSA36-42-44-00 PDS 1(1/2015 rev.6 4 � <br />