<br /> �`�� ���� �� � � ���� ����� �°������ �� �; �"�����°"
<br /> HVPSA24HP HVPSA30HP HVPSA36HP1 HVPSA42HP1 HVPSA49HP1 HYPSA6Q
<br /> MOtIEI NUt11581' HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD
<br /> .Gooting.BTUH�-2nd Stage . 23,000 29,004 35,000 39,000 47;000 57,000
<br /> EERz-'2nci Stage 10,50 10.54 10.00 10.20 11.04 10.90
<br /> Integrated Part Laad Value3 14A 14.0 14.00 13.60 15.0 14.80
<br /> High Temperature Heating4 22,000 26,000 31,400 37,600 39,040 SO,S00
<br /> Migh Temperature COPS 3.00 3.00 3.20 3,15 3.00 3.00
<br /> Rated Air Flow(CFM6) 800 1,000 1,200 1,300 1,750 1,750
<br /> 1Cooling is rated at 95°F(35°C)outdoor and 80°F DB/67°F WB(26.5°C DB/19.5°C WB) return air.
<br /> zEER= Energy Efficiency Ratio
<br /> 3Integrated Part Load Value is an integrated efficiency measure from Sst and 2nd stage capacity modulation.
<br /> QHigh Temperature Heating &COP is rated at 47°F DB/43°WB(8.3°C DB/6.1°C WB)outdoor and 70°F(21.1°C) return air.
<br /> SCOP= Coe�cient of Performance -
<br /> 6CFM = Cubic Feet per Minute
<br /> Ratings are with no outside air. Performance wili be afFected by altitude. Ratings are at 230 volts for 208/23Q volt units (`�A"&"C"
<br /> modefs)and 460 volts for"D"models.
<br /> Operation of units at a different voltage from that of the rating point wiil affect performance and air flow.
<br /> ������� ����� ���� ���� �_ ���"' ���� � � ����� ���" ' ' °�
<br /> ����� ���� ����� � ����
<br /> HVPSA24HP HVPS;430HP HVPSA36HP1 HVPSA42HP1 HVPSA49HP1 FiYPSA50
<br /> Model Number HPA �{PC HPD HPA HPC HPD HPA HPC HPD HPA kPG HPD HPA HPC HPD HPR HPC HPD
<br /> Tota)Capacity 23,000 29,000 35,O�Q 39,000 47,OOQ 57,000
<br /> Sensible F4eat Ratio 0.75 0.78 0.72 OJO 0.74 OJ1
<br /> Sensibie Capacity 17,315 22,525 25,485 27,460 34,710 40,605
<br /> Rated Air Flaw(CFM) 800 1,000 1,200 1,300 1,75Q 1,750
<br /> �CFM=Cubic Feet per Minute
<br /> Sensibie Heat Ratios based upon ANSI/AHRI std. 390 outdoar conditions of 95°F(35°C) outdoor and 80°F dB/67°F WB(26.5°C
<br /> DB/19.5°C WB) return air.
<br /> �����.�� ���'���"����� �.������' �� ���'���d� ������ ������"����"�� �
<br /> ����� ���� ����� °� ��'��� �;
<br /> Mudel Outdoar Temperature
<br /> Number 75°F/24°C 80°F/26.5°C 85°FJ29°C 90°F/32°C 95°F/35°C iQQ°F/38°C I05°P/40.5°C i10�F/43.3°C if5°F/46°C
<br /> HVPSA24HP 26,680 25,760 24,840 23,920 23,000 22,080 21,160 20,240 19,780
<br /> HVPSA30HP 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940
<br /> HVPSA36HP2 40,600 39,200 37,800 36,400 35,000 33,600 32,204 30,80Q 30,100
<br /> HVPSA42HP1 45,240 43,68Q 42,120 40,560 39,000 37,440 35,880 34,320 33,540
<br /> HVPSA49HP1 54,520 52,640 50,760 48,880 47,000 45,120 43,240 41,360 40,420
<br /> HVPSA6oHP 66,120 63,840 61,56Q 59,2&0 57,000 54,7Z0 52,440 50,160 49,02Q
<br /> Based upon ANSI/AHRI std, 390 return air conditions of 80°F DB/67°F WB(26.5°C DB/19.5°C WB). Return air at rated air flow.
<br /> �������� �����������f ���� ��:X:�• ��� ��������� ������ ������������ �
<br /> ����� ����� �� �:h� ���� ��������� ������������
<br /> Model Outdoor Temperatare
<br /> Number 1Q°E/-12.2�C 17�F/-8.3°C 20QF/-6.7�C 30�F/-l.t°C 4Q°F/4.4°C 47�F/$.3°C SQ�F/10�C 60�F/15.6°C 70�F/21.2QC
<br /> HVPSA24HP 10,285 12,1Od 13,090 16,555 19,525 22,000 22,660 23,650 24,750
<br /> HVPSA3oHP 12,155 14,300 15,470 19,565 23,075 26,000 26,780 27,950 29,250
<br /> HVPSk36HP1 14,620 I7,200 18,620 23,590 2�,850 31,400 32,342 33,755 35,325
<br /> HVPSA42HP1 17,680 20,800 22,420 28,090 32,950 37,OD0 38,110 39,775 41,625
<br /> HVPSA49HPi 18,700 22,000 23,700 29,650 34,750 39,000 40,170 41,925 43,875
<br /> HVP5A60HP 25,500 30,000 32,050 39,225 45,375 50,500 52,015 54,288 56,813
<br /> Based upon ANSI/AHRI std. 390 return air conditions of 70°F DB (21.1°C DB). Return air at rated air flov��.
<br /> Gassic AVPA24-3�7-36-4e-4R-60,HVPA243D-36-42-49-60&HVPSA3b-42-?9-60 PDS SOJ2D15 rev.E 18
<br />
|