• Boein 40-31 Phase 1 Jul 12,2012 <br /> drain pan shall include downspo direct condensate to the primary drain p he outlet shall be located at the <br /> � lowest point of the pan and shall be sufficient diameter to preclude drain pan overflow under any normally expected <br /> operating condition. <br /> Water Coils(UW, UU, UA,W, 5W, 5A,WD,5D, D1, D2, P,or TT) <br /> The coils shall have aluminum fins and seamless copper tubes. Copper fins may be applied to coils with 5/8-inch tubes. <br /> Fins shall have collars drawn,belled, and firmly bonded to tubes by mechanical expansion of the tubes.The coil casing <br /> may be galvanized or stainless steel. Refer to the Product Data section of the submittal for the coil casing material. <br /> The coils shall be proof-tested to 300 psig and leak-tested under water to 200 psig. Coil performance data and coils <br /> containing water or ethylene glycol shall be certified in accordance with AHRI Standard 410. Propylene glycol and <br /> calcium chloride, or mixtures thereof, are outside the scope of AHRI Standard 410 and, therefore, do not require AHRI <br /> 410 rating or certification. <br /> Headers are constructed of round copper pipe or cast iron. <br /> Tubes are 5/8"[16mm]OD 0.020"[0.508 mm]thick copper. <br /> ACCESS/INSPECTION/TURNING SECTION <br /> A section shall be provided to allow additional access/inspection of unit components and space for field-installed <br /> components as needed. An access door shall be provided for easy access. All access sections shall be complete with <br /> a double-wall, removable door downstream for inspection,cleaning,and maintenance. Interior and exterior door panels <br /> shall be of the same construction as the interior and exterior wall panels, respectively. All doors downstream of cooling <br /> coils.shall be provided with a thermal break construction of door panel and door frame. <br /> BELT-DRIVE PLENUM FAN SECTION <br /> The fan type shall be provided as required for stable operation and optimum energy efficiency. The fan shall be a <br /> single-width, single-inlet, multiblade-type, belt-driven plenum fan. <br /> The fan blades shall be backward-inclined airfoiL <br /> Plenum fans shall be equipped with self-aligning,antifriction, pillow-block bearings with an L-50 life of 200,000 hours as <br /> calculated per ANSI/AFBMA Standard 9. For any bearing requiring relubrication, the grease line shall be extended to <br /> the fan support bracket on the drive side. The fan shall be statically and dynamically balanced at the factory as a <br /> complete fan assembly(fan wheel, motor, drive, and belts).The fan shaft shall not exceed 75 percent of its first critical <br /> speed at any cataloged speed. Fan wheels shall be keyed to the fan shaft to prevent slipping. The fan shafts shall be <br /> solid steel. The fan section shall be provided with an access door on the drive side of the fan. <br /> Fans that are selected with inverter balancing shall first be dynamically balanced at design RPM.The fans then will be <br /> checked in the factory from 25%to 100% of design RPM to insure they are operating within vibration tolerance <br /> specifications,and that there are no resonant frequency issues throughout this operating range. Inverter balancing that <br /> requires lockout frequencies inputted into a variable frequency drive to in order to bypass resonant frequencies shall not <br /> be acceptable. If supplied in this manner by the unit manufacturer, the contractor will be responsible for rebalancing in <br /> the field after unit installation. Fans selected with inverter balancing shall have a maintenance free, circumferential <br /> conductive micro fiber shaft grounding ring installed on the fan motor to discharge shaft currents to ground. <br /> Motor Frame <br /> The motor shall be mounted integral to the isolated fan assembly and furnished by the unit manufacturer. The motor is <br /> mounted inside the unit casing on an adjustable base to permit adjustment of drive belt tension(not applicable for direct <br /> drive plenum fans). The motor shall meet or exceed all NEMA Standards Publication MG 1 requirements and comply <br /> with NEMA Premium efficiency levels when applicable except for fractional horsepower motors which are not covered <br /> by the NEMA classification. The motor shall be T-frame, squirrel cage with size,type, and electrical charaeteristics as <br /> � shown on the equipment schedule. Refer to the Product Data section for selected fan motors within each unit. <br /> Two-Inch Spring Isolators <br /> The fan and motor assembly(on sizes 10 to 120)shall be internally isolated from the unit casing with 2-inch (50.8 mm) <br /> deflection spring isolators,furnished and installed by the unit manufacturer.The isolation system shall be designed to <br /> resist loads produced by external forces, such as earthquakes, and conform to the current IBC seismic requirements. <br /> Fans sections with plenum fans shall be provided with an expanded-metal guard screen for the access door, mounted <br /> on the door opening,to deter unauthorized entry and incidental contact with rotating components. Refer to the Product <br /> Data section for fans with access door guards. <br /> FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 8 of 26 <br /> Mstalled by Others <br />