Page 26 of 51 08/24/2012 <br /> � Job: Boeing 40-30(53 Upper Deck AHU <br /> �� EQ Number: 16383 _ <br /> Date:Aug 24, 2012 <br /> CusfomAirHandfars . . ReV.. <br /> Cooling Coil Schedule <br /> Face <br /> Air Flow 9ize Sensible Total Model F�n *Handin <br /> � Unit No. Coil Tag (CFM) iFP�,y No.Coils H x L Each Rows Fins per in. Cooling Cooling Manufacturer Design g <br /> Right <br /> AC-1-4 CC-1-4 12000 499 1 33x105 8 10 654 850 Heatcraft SWC1008A A (1,2,3) <br /> Left(4) <br /> Ent Temp <br /> Ent Temp Ent Temp Lvg Temp Lvg Temp Lvg Temp Fluid Air Aititude <br /> Fluid Flow Rate <br /> Unit No. Coil Tag (Air) (Air) (Air) (Air) Fluid Press Drop Fluid Turbulators <br /> (GPM) Press Drop (F#) <br /> DB(F) WB(F) DB(F) WB(f) (F� (f) (Ft Hz0) (�n HZO) <br /> AC-1-4 CG1-4 76.9 63.8 52 51.56 44 54 177 9.93 0.68 0 Propylene Not Included <br /> Intermediate <br /> Unit No. Coil Tag Fin Materiai Tube Material Casing Material Coating Flange Size <br /> Drain <br /> Aluminum heavy(.0075" 5/8 Copper standard wall Stainless Steel No None 3/4"" <br /> AG1-4 CG1-4 thickness) (.020thickness) <br /> * Heatcraft—Hand is determined by facing the coil with air hitting in back of head. <br /> Tratte 9900 Aire Circle,Fort Smith,AR 72916 Phone:(479)648-7402 Fax:(479)648-7499 <br />