Laserfiche WebLink
530.18-TG1Y <br /> RATINGS <br /> CAPACITY RATINGS-Coolin /Electric Heatin <br /> ARI RATINGS NOMINAL <br /> MODEL COOLING CAPACITY SOUND ELECTRIC HEAT CAPACIlY3 <br /> 80/67-95°F RATINGZ �� <br /> MBH SEER EER bels 240V 480V 600V <br /> DCE036 40 10.10 9.30 g.g 5 7,10, 7,10, 10, <br /> 15&20 15&20 15&20 <br /> DCE048 48 10.35 9.45 g,g 5 7,10, 7,10, 10, <br /> 15&20 15&20 15&20 <br /> DCE060 59 10.15 9.40 g,g 5,7,10, 7,10,15 10,15, <br /> 15 20&30 20&30 20&30 <br /> DCE072 72 - 9.00 g,4 5,7,10, 7,10,15, 10,15, <br /> 15 20&30 20&30 20&30 <br /> CAPACITY RATINGS-Cooling/Gas Heating <br /> ARI RATINGS GAS HEAT CAPACITY <br /> MODEL COOLING CAPACITY SOUND TEMP. GAS <br /> 80/67-95°F RATINGZ INPUT OUTPUT AFUE S.S.E. S.E. RISE LINE SIZE <br /> MBH SEER EER (bels) �MBH) (MBH) (%) (%) (%) oF in.OD) <br /> DCG036N040 40 10.10 9.30 8.6 50 40 80.9 81.6 75.9 15-45 1/2 <br /> DCG036N079 40 10.10 9.30 8.6 100 79 80.5 80.8 73.6 40-70 1/2 <br /> DCG048N060 48 10.35 9.45 8.6 75 59 80.9 81.6 77.3 25-55 1/2 <br /> DCG048N099 48 10.35 9.45 8.6 125 99 80.3 80.6 77.9 45-75 1/2 <br /> DCG060N079 59 10.15 9.40 8.6 100 79 80.5 80.8 73.6 25-55 1/2 <br /> DCG060N099 59 10.15 9.40 8.6 125 99 80.3 80.6 77.9 35-65 1/2 <br /> � DCG072N079 72 - 9.00 8.4 100 79 80.5 80.8 73.6 25-55 1/2 <br /> DCG072N099 72 9.00 8.4 125 99 80.3 80.6 77.9 35-65 1/2 <br /> �Ratings are in accordance with ARI Standard 210. ZSound ra6ngs are in accordance with ARI Standard 270. 3Heaters are available as accessories-all with single point power supply. <br /> SEER=Seasonal Energy Efficiency Ratio-ihe total cooling output in BTU's during a normai anrnal usage period for cooling divided by the total electric power input in wa&hours during he same period. <br /> EER=Energy Efficiency Ratio-the cooling capacity in Btu's per hour(Btuh)divided by the power input in watts at any given set of rating conditions,expressed in BTUH per watt(BTUFIMratt). <br /> AFUE=Mnual Fuel Utilization Efficiency-determined in accordance with DOE test procedure. <br /> S.S.E.=Steady State Efficiency.(Percent Output). <br /> S.E.=Califomia Seasonal Efficiency-detertnined in accordance with test procedures as speciied by the State of Califomia Energy Commission.Fumaces are available with a low NOx accessory. <br /> =NotARI Listed. <br /> PHYSICAL DATA - BASIC UNITS <br /> MODELS E/DCG <br /> EVAPORATOR CENTRIFUGAL BLOWER Dia.x Wd.in.) 12 x 10 12 x 10 12 x 10 12 x 11 <br /> BLOWER FAN MOTOR HP DIRECT- RIVE) 1/2 3/4 1 1 <br /> FAN MOTO -D VE 1 5 1. <br /> EVAPORATOR ROWS DEEP 3 3 3 4 <br /> COIL FINS PER INCH 13 13 13 13 <br /> FACE AREA S .Ft. 3.6 4.3 5.1 5.1 <br /> CON ANSER AN�MOTOR DI�A.(in.) ��2 ��2 1/2 1 2 <br /> NOM.CFM TOTAL 4 500 4 200 4 500 4 500 <br /> CONDENSER ROWS DEEP 1 1 1 2 <br /> COIL FINS PER INCH 16 19 22 16 <br /> FACE AREA S .Ft. 17.1 17.1 17.1 16.7 <br /> AIR QUANTITY PER UNIT 14"X 20"X 1" 2 2 2 2 <br /> FILTERS QUANTITY PER UNIT�14"X 25"X 1"; 1 1 1 1 <br /> SEE NOTE TOTAL FACE AREA(sq.ft.) 6.3 6.3 6.3 6.3 <br /> NOTE: Filter racks are adapted for 1"or 2"thick filters. <br /> COMPONENT WEIGHTS .,� <br /> COMPONENT MODELS DCE&DCG <br /> DCE Coolin onl 545 585 6 0 670 <br /> 40 Mbh 605 <br /> Basic Unit DCG(Gas/Electric) 60 - 645 - - <br /> 79 Mbh 615 6 725 <br /> 99 Mbh 655 80 735 <br /> Economizer 5 <br /> Motorized OutdoorAir Dam er 48 <br /> ' Electric Heat -� W 18 <br /> �atnd S Nominal KWj 10-15 KW 23 <br /> Accessories �DCE only) 20-30 KW 28 <br /> Roof Moun in Curb 92 <br /> Relief/Fixed Air Dam er <br /> Belt-Drive BI wer 5 <br /> NOTE:Weights are given in pounds. <br /> Unitary Products Group t'��� Q � �C�"L� "`" " 3 <br /> �� <br />