GENERAL NOTES:
<br /> LEGEND
<br /> t. THE FOLLOWING NOTES APPLY TO ALL ELECTRICAL. ADDITIONAL NOiES MAY BE INDICATED ON
<br /> INDIVIDUAL DRAWINGS.
<br /> 2. DRAWINGS INDICATE CONNECTIONS FOR EQUIPMENT TO BE FURNISHED BY THE OWNER OR AS THE GENERAL SYMBOLS POWER
<br /> WORK OF OTHER TRADES. VERIFY LOCATION Of EQUIPMENT, ROUGH-IN LOCATIONS,AND TYPE OF
<br /> CDNNEC�IONS PRIOR TO PREPARATION OF SHOP DRAWINGS OR SUBMITTALS, AND PRIOR TO EXISTING UNDERGROUND CDNDUIT � EQUIPMENT CONNECTIDN
<br /> INSTALLATION OF SERVICE CONNECTIONS. DO NOT INTERFERE WITH ACCESS FOR MAINTENANCE AND m JUNCTION BOX
<br /> REMOVAL OR REPUCEMENT OF EQUIPMENT. LIGHT LINE INDICATES
<br /> EXISTING WORK �,30/20 FUSED DISCONNECT SWITCH
<br /> 3. COORDINATE THE PHASING AND MSTALLAiION OF NEW WORK WITH THE WORK OF ALL OTHER TRADES. HEAVY LINE INDICATES
<br /> BEAR THE TOTAL EXPENSE FOR ANY ADDITIONAL WORK WHICH MAY BE CAUSED BY IA�PROPER NEW WORK a30 NON-FUSED DISCONNECT SWITCH
<br /> SEQUENCING OF CONSTRUCTION ACTIVITIES.
<br /> 4. REFER TO ARCHffECTURAL AND STRUCiURAL DRAWINGS FOR GENER4L CONSTRUCTION INCLUDiNG, BUT SS;'1,'�,�i�iS�iSS EXISTING WORK 0 TRANSFORMER
<br /> TO BE REMOVED
<br /> NOT LIMITED TQ E�UIPMENT HOUSEKEEPING PADS, PENETRATION DEfAILS, FLASHING AND SEALING � DUPLEX RECEPTACLE
<br /> DETAILS, AND OTHER ELEMENTS 0� GENERAL CONSIRUCTION. COORDINATE THE SIZE AND LOCATION OF �1 FLAG NOTE
<br /> EQUIPMENT HOUSEKEEP�NG �ADS WITH APPROVED EQUIPMENT SO THAT HOUSEKEEPING PADS ARE CONDUITS CONCEALED IN CONSTRUCTION IN
<br /> NOMINALLY 4" HIGH UNLESS INDICATED OTHERWISE,AND EXTEND 6" MiNIMUM IN ALL DIRECTIONS NUMBER INDICATING DEfAIL FINISHED AREAS, EXPOSED IN UNRNISHED
<br /> FROM THE HORIZONTAL LIMITS OF THE EQUIPMENT WHICH THEY SUPPORT. r
<br /> � DEfAIL IDEMIFICATION AR,_AS
<br /> 5. CDORDINATE EQUIPA�ENT POWER CONNECiION REQUIREMENTS AND ELECTRICAL CHARACTERISTICS WITH E3 E4
<br /> ��SHEEf NUMBER WHERE Sm MOTOR-RATED SWfTCH
<br /> MECHANICAL DRAWINGS AND CONNECTION REQUIREMENTS. DETAIL IS DR4WN
<br /> � ALARM LIGHT
<br /> 6. EQUIPMENT SHORT CIRCUIT CURRENT RATINGS (SCCR) SHALL BE NOT LESS THAN THE INTERRUPTING SHEET NUMBER WHERE
<br /> RATING OF THE BRANCH CIRCUIT OVERCURRENT PROiECTIVE DEVICE SUPPLYING POWER TO THE DETAIL IS TAKEN
<br /> EQUIPMENT. REFER TO ELECTRICAL SCHEDULES FDR BRANCH CIRCUIT OVERCURRENT DEVICE ABBREVIATIONS
<br /> INTERRUPTING RATINGS.
<br /> , O NORTH ARROW (E) EXISTING
<br /> 7. COORDINATE THE LOCATION OF WORK TO PROVIDE CLEARANCES OVER LIGHTING FIXTURES AND OTHER
<br /> CANOPY MOUNTED DEVICES AS REQUIRED TD ALLDW FOR REMOVAL AND MAINTENANCE ACCESS. G GROUND
<br /> 8. PROVIDE SUPPDRTS AND SEISMIC RESTRAINTS FOR CONDUIT AND E4UIPMENT AS SPECIRED, AS iYP 1YPICAL
<br /> REQUIRED, AND AS SHOWN ON THE DRAWINGS. IF REQUIRED FOR INSTALLATION OF CONDUIT AND HP HORSE POWER
<br /> EQUIP�IENT, DESIGN AND PROVIDE ADDITIONAL STRUCTURAL MEMBERS BEfWEEN COLUMNS, JOISTS, AND
<br /> STRUCTURAL FRAME TO MEET SUPPORT AND SEISMIC RESTRAINT REACTIONS (FDRCES, MOMENTS,
<br /> DEFLECTIONS). STRUCTURAL MEMBERS AND ANCHORAGES SHALL BE DESIGNED BY A PROFESSIONAL
<br /> ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED. REFER TO STRUCTURAL
<br /> DRAWINGS FDR DESIGN CRITERIA. SUBMIT STRUCTURAL MEMBER SHOP DRAWINGS AND CALCULATIONS
<br /> FOR REVIEW. STRUCTURAL MEMBERS, BOLTS, AND WELDS SNALL BE IN ACCORDANCE WfTH THE
<br /> REQUIREMENTS SHOWN ON THE STRUCTURAL DRAWINGS AND INDICATED IN THE SPECIFICATIONS. NO
<br /> WELDING, BOLTING, OR OTHER MEANS OF ATTACHMENT TO iHE STRUCTURAL MEMBERS SHALL BE MADE
<br /> ON PORTIONS Of STRUCTURAL MEM9ERS AT OR NEAR CONNECTIONS BEfWEEN STRUCTURAL MEMBERS
<br /> ON ANY ELEMENTS DESIGNATED IN THE SEISMIC LOAD RESISTING SYSTEMS UNLESS APPROVED B`! THE
<br /> STRUCTURAL EN6INEER SUPPORTS SHALL NDT INDUCE TORSIONAL LOADS INTO SUPPORTING
<br /> STRUCTURAL FRAMING.
<br /> 9. COORDINATE THE LAYOUT OF EQUIPMENT, CONDUfi SO THAT IT FITS INTO THE SPACE ALLOTTED.
<br /> PROVIDE SERVICE ACCESS AND CLEARANCES AS INDICATED ON DRAWINGS, AS R=QUIRED BY CODES,
<br /> AND AS RECOMMENDED BY THE MANUFACTUR�R FOR THE INSTALLATION, REMOVAL, ENTRY, SERVICING,
<br /> AND MAINTENANCE OF EQUIPMENT. PRIOR TO INSTALLATION, COORDINAiE LAYOUT OF EQUIPMENT AND
<br /> CONDUIT WITH ALL OTHER TRADES TO AVDID BLOCKING SERVICE OR REPLACEMENT ACCESS fOR NEW
<br /> AND EXISTING EQUIPMENT INSTALLED BY DTHERS.
<br /> 10. DRAWINGS ARE DIAGRAMMATIC AND SHOW APPROXIMATE LDCATIONS OF EQUIPMENT AND CONDUIT.
<br /> 11. PROVIDE lAAXIMUM HEADROOM AND CLEARANCE BELOW CONDUff AND EQUIPMENT AND ASSOCIATED
<br /> SUPPORTS.
<br /> E
<br /> z
<br /> 3
<br /> Q I
<br /> Ua
<br /> W �I
<br /> �
<br /> O I
<br /> �
<br /> (:
<br /> �
<br /> _____._. ��� �_W00d e�n���wnoeoo< o- _. . _ ..C o , Xv1��1��� Drv�irq rro.
<br /> E �1 f pF KRS/�A.O prpNn
<br /> �. o,,. COMMUNITY TRANSIT
<br /> s S � ,,, <1,E,aboo communitytransit ,,� ,�;,,�h BID SET � °`�1B� INDUSTRIAL WASTEWATER PRE—TREATMENT SYSTEMS EO.O
<br /> ` „ii�►a�,�Harbin er „o�,„,,,�ge,�om •���.��,t, � �''� KASCH PARK SITE ��'°'i
<br /> �'� , „
<br /> � � � � � �� �a� �c a '""°"°'�' � o'�,�� ELECTRICAL GENERAL NOTES, LEGEND AND ABBREVIATIONS e „T�,,