My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
9224 HOLLY DR 2018-05-23
>
Address Records
>
HOLLY DR
>
9224
>
9224 HOLLY DR 2018-05-23
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/23/2018 1:51:12 PM
Creation date
5/23/2018 1:51:05 PM
Metadata
Fields
Template:
Address Document
Street Name
HOLLY DR
Street Number
9224
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
50
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
7. The stair detail on sheet 3 is for an interior staircase. The plans show work to be done <br /> on the exterior stairs. Provide detail of exterior stairs per section R311 IRC. <br /> 8. Define thermal envelope. If basement is unheated then the floor above the basement is <br /> required to be insulated per the Washington State Energy Code (WSEC). Show insulation <br /> requirements on the plans. <br /> 9. Specify U-Value for all fenestration per WSEC. Show on plans. <br /> 10. Provide lighting schedule to show how the great room is provided with artificial light as <br /> required per section R303 IRC. Show on plans. <br /> All required submittals shall be of sufFicient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Please prepare a response letter showing where each item in this <br /> correction letter is addressed on the plan set. <br /> Sincerely, <br /> .��%����.� _---, <br /> , <br /> Jeff Heilman <br /> Dcvclop���cnt Tcchnici�,n <br /> 425-257-8976 <br /> Email: iheilman@ci.everett.wa.us <br /> ;�1r � � <br /> S:\1Common\Clerical\JHeilman\BW1605-003(9224 HOLLY DR).doc <br />
The URL can be used to link to this page
Your browser does not support the video tag.