Technical Data:
<br /> Sensitivity: Quick-response
<br /> Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional
<br /> Maximum Working Pressure: 175 psi (12 bar)- 100% Factory tested hydrostatically to 500 psi (34.5 bar)
<br /> SIN RA1425, RA1414& RA1435 cULus listed for 250 psi (17 bar)
<br /> Design and Installation Information
<br /> Nominal Nominal
<br /> Nominal Listings
<br /> Model K-factor Orifice Deflector/ Sprinkler Installation SIN and Approval
<br /> Diameter Orientation Height Wrench Approvals Notes
<br /> US Metric inches mm inches mm
<br /> Pendent 2.25 57 D RA1411 cULus 2
<br /> F1FR28 2.8 40 3/8 10 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2
<br /> Upright 2.25 57 D RA1421 cULus 1,2
<br /> F1FR40 4.0 57 3/8 10 Pendent 2.25 57 D RA1418 VdS
<br /> Recessed Pendent 2.25 57 GFR2 RA1418 VdS
<br /> Pendent 2.25 57 D RA1413 cULus 2
<br /> F1 FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
<br /> Upright 2.25 57 D RA1423 cULus 1,2
<br /> F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 D RA1410 cULus,NSF
<br /> Recessed Pendent 2.25 57 GFR2 RA1410 cULus,NSF
<br /> F1FRXLH Pendent 2.25 57 D RA1413 cULus 2
<br /> (F1FR42 4,2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
<br /> with Pintle) Upright 2.25 57 D RA1423 cULus 1,2
<br /> Pendent 2.25 57 D RA1414 cULus,FM, 1,2,3,4
<br /> LPCB,VdS,EC
<br /> Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM, 1,2,3,4
<br /> LPCB,VdS, EC
<br /> F1FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6
<br /> Upright 2.25 57 D RA1425 cULus,FM, 1,2,3,4
<br /> LPCB,VdS,EC
<br /> "Conventional
<br /> 2.25 57 D RA1475 LPCB,VdS,EC 4
<br /> (Pendent or Upright)"
<br /> Pendent 2.25 57 D RA1415 cULus,NSF 1
<br /> F1FR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 GFR2 RA1415 cULus,NSF
<br /> Concealed Pendent 2.25 57 RC1 RA1414 cULus,NSF 6
<br /> Horizontal Sidewall 2.63 67 D RA1435 cULus,FM 1,2,3,7
<br /> F1FR56 5.6 80 1/2 15 Recessed Horizontal
<br /> Sidewall 2.63 67 GFR2 RA1435 cULus,FM 8
<br /> F1FR56 5.6 80 1/2 15 Vertical Sidewall 2 25 57 D RA1485 cULus,FM, 1,2,3,9
<br /> (Pendent or Upright) LPCB
<br /> (1)cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating.
<br /> (2)cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating.
<br /> (3)Available with FM approved Polyester coating in black or white.
<br /> (4)Available with LPCB and VdS approved Polyester coating.
<br /> (5)VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F(68°C)temperature rated sprinklers only.VdS approved sprin-
<br /> klers must use Norbulb brand glass bulbs with the 1/2-inch(12.7mm)adjustment Model CCP cover plate only.
<br /> (6)Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates,
<br /> available as either standard depth with 1/2-inch(12.7mm)of adjustment or low profile with 5/16-inch(8.0 mm)of adjustment.
<br /> (7)cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1FR56 Hori-
<br /> zontal Sidewall sprinkler is for Light Hazard occupancies only.
<br /> (8)cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only.
<br /> (5)The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil-
<br /> ing distance shall be 4 inches to 12 inches(102mm to 305mm).LPCB approval of the F1FR56 Vertical Sidewall sprinkler is for installation in the
<br /> Pendent position only.
<br /> 3.
<br />
|