Laserfiche WebLink
Pocock Racing Shells <br />September 15, 2016 <br />JN 16391 <br />Page 3 <br />outside of the work area. Soil and mud should not be tracked off the site, and silty runoff should be <br />prevented from leaving the property. <br />The dense to very dense, glacially -compressed soils beneath the site are essentially impervious. <br />This makes on -site infiltration of storm water infeasible. <br />SEISMIC CONSIDERATIONS <br />In accordance with the International Building Code (IBC), the site class within 100 feet of the <br />ground surface is best represented by Site Class Type C (Very Dense Soil Class). <br />The dense soils are not susceptible to seismic liquefaction under the Maximum Considered <br />Earthquake (MCE), which has a theoretical probability of 2 percent in 50 years (once in 2,475 <br />years). <br />CONVENTIONAL FOUNDATIONS <br />We recommend that new continuous and individual spread footings have minimum widths of 16 <br />and 24 inches, respectively. Exterior footings should also be bottomed at least 18 inches below the <br />lowest adjacent finish ground surface for protection against frost and erosion. The local building <br />codes should be reviewed to determine if different footing widths or embedment depths are <br />required. Footing subgrades must be cleaned of loose or disturbed soil prior to pouring concrete. <br />Depending upon site and equipment constraints, this may require removing the disturbed soil by <br />hand. <br />An allowable bearing pressure of 3,500 pounds per square foot (psf) is appropriate for footings <br />supported on competent native soil. This can also be assumed for existing perimeter foundations <br />that surround the existing concrete slab in the western portion of the planned addition. A one-third <br />increase in this design bearing pressure may be used when considering short-term wind or seismic <br />loads. For the above design criteria, it is anticipated that the total post -construction settlement of <br />footings founded on competent native soil will be about one inch, with differential settlements on <br />the order of one-half inch in a distance of 25 feet along a continuous footing with a uniform load. <br />Lateral- .loads _due. to wind -or seismic -forces may .be_..r_esisted.by__friction_between the -foundation -and. <br />the bearing soil, or by passive earth pressure acting on the vertical, embedded portions of the <br />foundation. For the fatter condition, the foundation must be either poured directly against relatively <br />level, undisturbed soil or be surrounded by level, well -compacted fill. We recommend using the <br />following ultimate values for the foundation's resistance to lateral loading: <br />Coefficient of Friction 0.45 <br />Passive Earth Pressure 300 pcf <br />Where: (1) pcf is pounds per cubic foot, and (il) passive earth <br />pressure Is computed using the equivalent fluid density. <br />GEOTECH CONSULTANTS, INC. <br />