Sawn Energy Today Inc.''
<br /> N $,. PHOTOVOLTAIC SYSTEM AC DISCONNECT SOLAR
<br /> 4u' RATED AC OPERATING CURRENT 36,4 AMPS CAUTION
<br /> ELECTRIC SHOCK HAZARD AC NOMINAL OPERATING VOLTAGE 240 VOLTS
<br /> IF A GROUND FAULT IS INDICATED —
<br /> NORMALLY GROUNDED CONDUCTORS POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE 1001 Cooper Point Rd SW,
<br /> MAY BE UNGROUNDED AND ENERGIZED LABEL LOCATION: Suite 140-290
<br /> AC DISCONNECT,POINT OF INTERCONNECTION FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN Olympia,WA 98502
<br /> LABEL LOCATION: (PER CODE:CEC690.54) Phone:888-405-8689
<br /> AT:® MAIN SERVICE PANEL&UTILITY METER
<br /> DC DISCONNECT,INVERTER Fax:855-350-9430
<br /> (PER CODE:CEC690.35 F WARNING PRODUCTION METER
<br /> ()) � � support@smartenergylotlay.nel
<br /> [Tobe used when inverter is ungrounded] INVERTER OUTPUT CONNECTION DO NOT FUSED AC DISCONNECT
<br /> rm 4Tore._, ,,rt,,,..
<br /> SOLAR AC COMBINER /I� REVISIONS
<br /> a RELOCATE THIS OVERCURRENT DEVICE DESCRIPTION DATE REV
<br /> LABEL LOCATION: el INITIAL 7-21-2017 00
<br /> ELECTRIC SHOCK HAZARD POINT OF INTERCONNECTION
<br /> THE DC CONDUCTORS OF THIS (PER CODE:CEC 705.12(D)(7)) W
<br /> PHOTOVOLTAIC SYSTEM ARE UNGROUNDED [Not required f pa elboa d s rated not less than sum of ampere ratings >
<br /> AND MAY BE ENERGIZED of all overcu ent devices supplying ill 50
<br /> `````� S alar¢with Seal
<br /> LABEL LOCATION ' ( ",-;•:,.. 0 7 ro F,
<br /> (P DISCONNECT,INVERTER .4 A x -.A ft ( ` r
<br /> (PER CODE CEC 690.35(F)) Mitei ,.a' .. d ''-,..',.--,:?...:,:,-","1 & - z
<br /> [To be used when inverter is ungrounded] LABEL LOCATION: Q
<br /> MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT,RACEWAYS,ENCLOSURES, J
<br /> g b .+ >, AND CABLE ASSEMBLIES AT LEAST EVERY 10 FT,AT TURNS AND ABOVE/BELOW PENETRATIONS >^--
<br /> v`=�sf*. AND ALL COMBIINER/JUCTION BOXES.(PER CODE:IFC605.11.1.4) L.�
<br /> ELECTRIC SHOCK HAZARD SOLAR DISCONNECT
<br /> DO NOT TOUCH TERMINALS PROJECT NAME&ADDRESS
<br /> TERMINALS ON BOTH LINE AND 1,-41 I'
<br /> LOAD SIDES MAY BE ENERGIZED LABEL LOCATION:
<br /> IN THE OPEN POSITION DISCONNECT,POINT OF INTERCONNECTION
<br /> DC VOLTAGE IS ALWAYS PRESENT (PER CODE:CEC690.13(B)) (E)MAIN SERVICE PANEL
<br /> (INSIDE)
<br /> WHEN SOLAR MODULES ARE °( `�.j i-f m
<br /> (E)UTILITY METER
<br /> EXPOSED TO SUNLIGHT
<br /> J y r 1; 11 s (N)FUSED AC DISCONNECT
<br /> LABEL LOCATION: �� s,. (N)PV PRODUCTION METER Q
<br /> AC DISCONNECT,POINT OF INTERCONNECTION LABEL LOCATION: /^ ;CO W
<br /> (PER CODE:CEC 690.17(E)) POINT OF INTERCONNECTION (N)SOLAR AC COMBINER ANEL V
<br /> (PER CODE:CEC 70512(0)(4)) H
<br /> <
<br /> M r,
<br /> o
<br /> ELECTRIC SHOCK HAZARD -r „y - < Q n
<br /> LABEL LOCATION-.
<br /> DO NOT TOUCH TERMINALS WEATHER RESISTANT MATERIAL,DURABLE ADHESIVE,
<br /> ELECTRICAL NOTES Q
<br /> } N
<br /> TERMINALS ON BOTH LINE AND UL969 AS STANDARD TO WEATHER RATING(UL LISTING
<br /> LOAD SIDES MAY BE ENERGIZED OF MARKINGS NOT REQUIRED),MIN 3 LETTER HEIGHT 1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL,AND Z H W
<br /> IN THE OPEN POSITION ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN
<br /> LABEL LOCATION: THE MAIN SERVICE DISCONNECT,PLACED ON THE LABELED FOR ITS APPLICATION. Q N O
<br /> AC DISCONNECT,POINT OF INTERCONNECTION OUTSIDE OF THE COVER WHEN DISCONNECT IS 2.) ALL CONDUCTORS SHALL BE COPPER,RATED FOR 600 V
<br /> I—PER CODE:CEC 690.17(E),CB OPERABLE WITH SERVICE PANEL CLOSED. AND 90 DEGREE C WET ENVIRONMENT. co w a
<br /> (PER CODE:CEC690.15,690.13(B)) 3.) WIRING,CONDUIT,AND RACEWAYS MOUNTED ON ROOFTOPS W
<br /> WARNING-Electric Shock Hazard SHALL BE ROUTED DIRECTLY TO,AND LOCATED AS CLOSE AS
<br /> No user serviceable parts inside /./ PHOTOVOLTAIC ARRAY AC POSSIBLE TO THE NEAREST RIDGE,HIP,OR VALLEY.
<br /> Contact authorized service provider for assistance DISCONNECT SWITCH 4.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING
<br /> LABEL LOCATION: ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.
<br /> INVERTER,JUNCTION BOXES(ROOF),AC DISCONNECT LABEL LOCATION: 5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF
<br /> (PER CODE:CEC690.13.G.3&CEC 650.13.G.4( AT ALL AC DISCONNECTS SYSTEMS.CONTRACTOR SHALL FURNISH ALL NECESSARY
<br /> WARNING:PHOTOVOLTAIC (PER CODE:CEC 690.14(C)(1)) OUTLETS,SUPPORTS,FITTINGS AND ACCESSORIES TO FULFILL
<br /> POWER SOURCE APPLICABLE CODES AND STANDARDS. SHEET NAME
<br /> LABEL LOCATION: "PV SYSTEM EQUIPPED WITH RAPID 6.) WHERE SIZES OF JUNCTION BOXES,RACEWAYS,AND CONDUITS
<br /> CONDUIT,COMBINER BOX SHUTDOWN" ARE NOT SPECIFIED,THE CONTRACTOR SHALL SIZE THEM PLACARDS
<br /> (PER CODE.CEC690.31(G)(3)(4)&CEC 690.13(G)(4) ACCORDINGLY.
<br /> 2016NEC 690.56(C) 7.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY SHEET SIZE
<br /> ADHESIVE FASTENED SIGNS LABELED AND READILY VISIBLE.
<br /> •THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT 8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN ANSI B
<br /> WHERE IT IS INSTALLED. MODULE FRAME AND MODULE SUPPORT RAIL,PER THE
<br /> •WHERE REQUIRED ELSEWHERE IN THIS CODE,ALL FIELD 11"X 17"
<br /> APPLIED LABELS,WARNINGS.AND MARKINGS SHOULD GROUNDING CLIP MANUFACTURER'S INSTRUCTION.
<br /> COMPLY WITH ANSI Z535.4[NEC 110.21(5)FIELD MARKING], 9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS SHEET NUMBER
<br /> •ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF
<br /> PROPERLY ADHERED.VINYL SIGNS SHALL BE WEATHER COPPER G.E.C.VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
<br /> RESISTANT[IFC 605.11.1.3] 10.) THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE PV-5