� DESIGN BUILD NOTES� GENERAL POWER/COMM. NOTES�
<br /> • PROJECT TO BE ELECTRICAL AND MECHANICAL DESIGN-BUILD. NEW LIGHTING SHALL MEEf 1. SEE ALSO A0.1 FOR WAREHOUSE POWER/DATA.
<br /> THE FOLLOWING MINIMUM REQUIREMENTS: 2. ALL SWITCHES, RECEPTACLES, COVER PLATES AND OTHER ELECTRICAL DEVICES SHALL
<br /> A. IBC 1006.1 - ILLUMINATION REQUIREMENT BE WHITE IN COLOR, U,N.O. DEVICES WHICH OCCUR IN STAINED MILLWORK OR ON
<br /> 1. THE MEANS OF EGRESS, INCLUDING THE EXITDISCHARGE, SHALL BE BLACK COLORED SURFACES SHALL BE BLACK IN COLOR. ALL EXISTING BEIGE
<br /> ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY THE SWITCHES, RECEPTACLES, COVER PLATES AND OTHER ELECTRICAL DEVICES SHALL BE ,
<br /> ' MEANS OF EGRESS IS OCCUPIED. CHANGED TO WHITE.
<br /> � B. IBC 1006.2 - ILLUMINATION LEVEL 3. ALL FURNITURE AND WORKSTATIONS PROVIDED AND INSTALLED BY OWNER. NEW
<br /> 1. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FURNITURE PANELS WILL BE POWERED. ELECTRICAL CONTRACTOR TO PROVIDE PANEL
<br /> FOOT-CANDLE (11 LUX) AT THE FLOOR LEVEL. TO PANEL ELECTRICAL CONNECTIONS, POWER CONNECTION TO WORKSTATIONS
<br /> . C. IBC 1006.3 - ILLUMINATION EMERGENCY POWER (WHIPS/BASE POWER INFEEDS) AND DUPLEX RECEPTACLE INSTALLATION. COORDINATE
<br /> � 1. THE POWER SUPPLY FOR MEANS OF EGRESS ILLUMINATION SHALL NORMALLY POWER, VGICE/DATA AND SECURITY LOCATIONS AND INSTALLATION REQUIREMENTS W/
<br />- BE PROVIDED BY THE PREMISE'S ELECTRIC SUPPLY. FURNITURE VENDOR, TYP.
<br /> 1.1 LOCATIONS INCLUDE: DEDICATED EGRESS ROUTES IN LARGER ROOMS OR 4. ALL WALL MOUNTED TELEPHONE AND ELECTRICAL OUTLETS TO BE INSTALLED 15° .
<br /> SPACES, PUBLIC OR COMMON EGRESS ELEMENTS, ESSENTIAL PORTIONS OF ABOVE FLOOR UNLESS OTHERWISE NOTED.
<br /> . THE INTERIOR EGRESS SYSTEM, INTERIOR EXIST DISCHARGE ELEMENTS, 5. ALL CORE DRILL LOCATIONS SHALL BE VERIFIED WITH DESIGNER PRIOR TO DRILLING.
<br /> AND EXTERIOR PORTIONS OF THE EXIT DISCHARGE, INCLUDING INTERIOR 6. MAINTAIN A FOUR INCH HORIZONTAL CLEARANCE IN ALL DIRECTIONS, MIN. FROM EDGE
<br /> EXIT STAIRWAYS & RAMPS. OF COVER PLATE, FOR WALL MOUNTED OUTLEfS, OR FROM EDGE OF MONUMENT FOR � �' C � I � E C � S
<br /> 2. EACH ROOM SHALL COMPLY WITH THE PROVISIONS OF C405.2.1.1 INTERIOR FLOOR MOUNTED OUTLEfS, WHEN ADJACENT TO A WALL, COLUMN, OR SIMILAR
<br /> LIGHTING CONTROLS. EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING ELEMENTS, U.N.O.
<br /> � . � PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR THE LIGHTING 7, INDICATED DIMENSIONS ARE TO THE CENTER OF THE COVER PLATE OR MONUMENT: 2505 Third Avenue
<br /> SERVING THAT AREA. THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE CLUSTERS OF OUTLEfS ARE DIMENSIONED TO THE CENTER OF THE CLUSTER, U.N.O.: S u ite 324
<br /> p AREA SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT IDENTIFIES GANG COVER PLATES SHALL BE ONE-PIECE TYPE U.N.O. Seattle, WA 98'12'I
<br /> THE LIGHTS SERVED AND INDICATES THEIR STATUS. 8. ALL EXISTING ELECTRICAL/ TELEPHONE OUTLEfS NOT SHOWN ARE EXISTING TO
<br /> � C405.2.1.2 LIGHT REDUCTION CONTROLS. LIGHT REDUCTION CONTROLS NEED REMAIN. POWER & COMMUNICATION OUTLEfS ARE SHOWN IN IDEAL LOCATIONS. REUSE 206.720.7001 phone
<br /> NOT BE PROVIDED IN THE FOLLOWING AREAS AND SPACES: EXISTING ELECTRICAL/ TELEPHONE OUTLEfS WHEN LOCATED NEAR IDEAL LOCATIONS 206.720.2949 fax
<br />� 2. AREAS THAT ARE CONTROLLED BY AN OCCUPANT-SENSING DEVICE. AND RELOCATE EXISTING ELECTRICAL/ TELEPHONE OUTLETS WHERE POSSIBLE.
<br /> 3. CORRIDORS, EQUIPMENT ROOMS, STOREROOMS, RESTROOMS, PUBLIC www.craftarchitects.com
<br /> LOBBIES, ELECTRICAL OR MECHANICAL ROOMS.
<br /> � 6. DAYLIGHT SPACES COMPLYING WITH SECTION C405.2.2.3.2.
<br /> C405.2.2.1 AUTOMATIC TIME SWITCH CONTROL DEVICES. AUTOMATIC TIME SWITCH
<br /> CONTROLS NEED NOT BE IN SPACES CONTROLLED BY OCCUPANCY SENSORS.
<br /> C405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL BE INSTALLED POWER/COMM. LEGEND'
<br /> IN ALL CLASSROOMS, CONFERENCE/ MEETING ROOMS, EMPLOYEE LUNCH AND �
<br /> BREAK ROOMS, PRIVATE OFFICES, RESTROOMS, WAREHOUSE SPACES, STORAGE EXISTING WALL / PARTITION TO REMAIN �
<br /> . ROOMS AND JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEEf (28
<br /> . � M2) OR LESS ENCLOSED BY FLOOR-TO- CEILING HEIGHT PARTITIONS. THESE NEW PARTITION WALL �
<br />. AUTOMATIC CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY TURN �
<br />� OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND w
<br /> SHALL EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO AUTOMATICALLY �
<br /> TURN THE LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER. k� WALL MOUNTED DUPLEX OUTLE7 (DED = DEDICATED) CI� O
<br /> C405.2.2.3 DAYLIGHT ZONE CONTROL. DAYLIGHT ZONES SHALL BE DESIGNED k� WALL MOUNTED FOURPLEX RECEPTACLE OUTLET � W �
<br /> SUCH THAT LIGHTS IN THE DAYLIGHT ZONE AR CONTROLLED INDEPENDENTLY � ' �
<br /> OF GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH f� WALL MOUNTED VOICE/DATA PORT - (2) VOICE/(2) DATA �,
<br /> , SECTION C405.2.2.3.2. EACH DAYLIGHT CONTROL ZONE SHALL NOT EXCEED IN SINGLE GANG BOX, UNO � W Q
<br /> 2,500 SQUARE FEET (232 M2). CONTIGUOUS DAYLIGHT ZONES ADJACENT TO � > �
<br /> VERTICAL FENESTRATION ARE ALLOWED TO BE CONTROLLED BY A SINGLE
<br /> CONTROLLING DEVICE PROVIDED THAT THEY DO NOT INCLUDE ZONES FACING Q
<br /> �
<br /> A MORE THAN TWO ADJACENT CARDINAL ORIENTATIONS (I.E., NORTH, EAST, SOUTH, W
<br /> � WEST). THE PRIMARY DAYLIGHT ZONE SHALL BE CONTROLLED SEPARATELY FROM � � �
<br />_ THE SECONDARY DAYLIGHT ZONE. DAYLIGHT ZONES UNDER SKYLIGHTS MORE � � W
<br />' THAN 15 FEET (4572 MM) FROM THE PERIMEfER SHALL BE CONTROLLED CEILING LEGEND' � � �
<br /> SEPARATELY FROM DAYLIGHT ZONES ADJACENT TO VERTICAL FENESTRATION. �
<br /> CONTROL SHALL• --------- ELEMENT TO BE DEMOLISHED � � >
<br /> ' 1. CONTROL ONLY LUMINAIRES WITHIN THE DAYLIT AREA.
<br /> 2. INCORPORATE TIME-DELAY CIRCUITS TO PREVENT CYCLING OF LIGHT LEVEL INTERNALLY LIGHTED EXIT SIGNAGE W/ BATTERY BACKUP PER IBC � w
<br /> CHANGES OF LESS THAN THREE MINUTES. EXIT Q EXIT D SECTION 1011, CONFIRM OPERATION FOR EXISTING. ADD WHERE � O
<br /> EXCEPTION: DAYLIGHT ZONES ENCLOSED BY WALLS OR CEILING HEIGHT NOT EXISTING. ARROW = DIRECTION INDICATOR, IF REQUIRED � r
<br /> , PARTITIONS AND CONTAINING TWO OR FEWER LIGHT FIXTURES ARE NOT
<br /> REQUIRED TO HAVE A SEPARATE SWITCH FOR GENERAL AREA LIGHTING. �
<br /> C405.2.2.3.2 AUTOMATIC DAYLIGHTING CONTROLS. SETPOINT AND OTHER
<br /> , CONTROLS FOR CALIBRATING THE LIGHTING CONTROL DEVICE SHALL BE READILY O
<br /> � ACCESSIBLE. DAYLIGHTING CONTROLS DEVICE SHALL BE CAPABLE OF
<br /> AUTOMATICALLY REDUCING THE LIGHTING POWER IN RESPONSE TO AVAILABLE 2X2 LAY-IN FLUORESCENT LIGHT, (2) T-5 LAMPS PER
<br />� DAYLIGHT BY EITHER ONE OF THE FOLLOWING MEfHODS: ">:<;� FIXTURE
<br /> � 1. CONTINUOUS DIMMING USING DIMMING BALLASTS AND DAYLIGHT-SENSING
<br /> AUTOMATIC CONTROLS THAT ARE CAPABLE OF REDUCING THE POWER OF HATCH INDICATES "NIGHT LIGHT' FOR EGRESS ILLUMINATION
<br /> • GENERAL LIGHTING IN THE DAYLIT ZONE CONTINUOUSLY TO LESS THAN 20 MIN. 1 FC W/ BATTERY BACKUP PER IBC SECTION 1003.2.9.
<br /> 4 PERCENT OF RATED POWER AT MAXIMUM LIGHT OUTPUT. CONSULTAtVT
<br /> 2. STEPPED DIMMING USING MULTI-LEVEL SWITCHING AND DAYLIGHT-SENSING SUSPENDED ACOUSTIC CEILING TILE AND GRID:
<br /> , CONTROLS THAT ARE CAPABLE OF REDUCING LIGHTING POWER AUTOMATICALLY. MATCH EXISTING ON SITE.
<br /> THE SYSTEM SHALL PROVIDE A MINIMUM OF TWO CONTROL CHANNELS PER
<br /> � � ZONE AND BE INSTALLED IN A MANNER SUCH THAT AT LEAST ONE CONTROL ���� ���
<br /> �?�Gl�"iTs r��.� �
<br /> I STEP IS BETWEEN 50 PERCENT AND 70 PERCENT OF DESIGN LIGHTING �`'�>� ����,�;�;;;;'t'
<br /> ' POWER AND ANOTHER CONTROL STEP IS NO GREATER THAN 35 PERCENT OF � .�
<br /> DESIGN POWER, AND THE SYSTEM IS CAPABLE OF AUTOMATICALLY TURNING GWB �� ` �
<br /> ' THE SYSTEM OFF. GYPSUM BOARD CEILWG �i � - � �
<br /> � CLOSET C408.3,1 FUNCTIONAL TESTING. TESTING SHALL ENSURE THAT CONTROL HARDWARE x�r�H`` ��� �t C���f
<br />. 119 AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER WORKING �TATE �b`!%�'�H�'�`����` '`a
<br />� �� � CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND � �����'/���r�
<br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. R RELOCATED LIGHT FIXTURE
<br /> , CONFERENCE ROOM 3. NEW HVAC SOLUTION SHALL MEEf THE FOLLOWING MINIMUM REQUIREMENT:
<br /> i 112 A. NEW MECHANICAL ELEMENTS, INCLUDING BUT NOT LIMITED TO PACKAGED UNITS, N NEW LIGHT FIXTURE
<br /> ��a CONTROLS, DAMPERS, DUCTING, COMMISSIONING; TO FULLY COMPLY WITH THE
<br /> �-----------� PROVISIONS OF WSEC SECTION C403. O NEW RECESSED COMPACT FLUORESCENT DOWNLIGHT FIXTURE
<br /> ��o�
<br /> i D. VENTILATION REQUIREMENTS FOR RESTROOMS PER WASHIN�TON STATE
<br /> ' MECHANICAL CODE (WAC 51-52) �� NEW SUSPENDED LOW VOLTAGE TRACK LIGHT SYSTEM
<br /> E. ALL OCCUPIED SPACES SHALL BE VENTILATED BY MECHANICAL MEANS IN
<br /> ACCORDANCE WITH SECTION 403 IN THE 2012 INTERNATIONAL MECHANICAL
<br /> �� CODE. THE VENTILATION SYSTEM SERVING THE SPACE SHALL BE DESIGNED �EY NOTES'
<br /> • ---- ------� ti J TO PROVIDE VENTILATION OVER AND ABOVE THAT REQUIRED BY TABLE O
<br /> . � �-� 403.3 IN ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICE.
<br />_ I 4. NEW EXIT SIGNAGE SHALL MEEf THE FOLLOWING MINIMUM REQUIREMENTS:
<br />' j A. ALL REQUIRED EXIT SIGNS SHALL HAVE LETfERS SIX INCHES HIGH 1. POWER/SIGNAL/SECURITY DEVICE - FLUSH FLOOR BOXES TO SUPPORT
<br /> MINIMUM AND SHAL VIDEO CONFERENCING. NEW CONDUITS IN SLAB FOR DATA/TELE & POWER. Submittals�Revisions:
<br /> B. L CONFORM WITH ALL APPLICABLE CODES.
<br /> � 5. THE BUILDING IS FULLY SPRINKLERED. THE FIRE PROTECTION CONTRACTOR SHALL 2. NEW/RELOCATED LIGHT FIXTURE.
<br /> N PROVIDE FIRE PROTECTION DRAWINGS AS REQUIRED BY THE GOVERNING AUTHORITY. THE 11/03/16 FOR PRICING & PERMIT
<br /> POV�ER-f-COI!!IM FIRST FLOOR FIRE PROTECTION CONTRACTOR SHALL SUBMIT DRAWINGS TO THE ARCHITECT FOR REVIEW 3. NEW ACP CEILING.
<br /> � PRIOR TO COMMENCING WITH THE WORK.
<br /> 1/8" = 1'-0" 4. RELOCATED TRACK LIGHT FIXTURE.
<br /> GENERAL CEILING NOTES' 5. EXISTING GWB SOFFIT, TO REMAIN � 9'-6".
<br /> 1. SEE ALSO ENGINEERING DRAWINGS (IF PROVIDED) FOR ADDITIONAL INFORMATION. WHEN 6. NEW/EXTEND SOFFIT TO MATCH EXISTING ADJACENT.
<br /> � THERE ARE DISCREPANCIES BETWEEN ARCHITECTURAL, ELECTRICAL, MECHANICAL OR
<br /> � 4 PLUMBING DRAWINGS OBTAIN CLARIFICATION FROM ARCHITECT IN WRITING BEFORE
<br />. PROCEEDING WITH ANY WORK IN QUESTION OR RELATED WORK. IF WORK IS PERFORMED
<br /> ' PRIOR TO OBTAINING CIARIFICATION, CONTRACTOR SHALL CORRECT CONFLICTING WORK AT
<br /> I HIS EXPENSE AND AT NO ADDITIONAL COST TO THE OWNER OR THE ARCHITECT.
<br /> • i2. BEFORE STARTING ANY WORK, CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS. IF
<br /> , THERE ARE EXISTING BUILDING OBSTRUCTIONS AND CEILING FIXTURES, LEVEL CHANGES,
<br /> SOFFITS, ETC., CANNOT BE INSTALLED WHERE INDICATED, OR IF THERE ARE ANY
<br /> CONFLICTS OR DISCREPANCIES, CONTRACTOR SHALL NOTIFY AND OBTAIN CLARIFICATION REFLECTED CEILING
<br /> , .�� �GLOSET � FROM THE ARCHITECT IN WRITING BEFORE PROCEEDING WITH ANY PART OF THE CEILING �
<br /> � :._ ��g: �:� �� WORK OR RELATED WORK.
<br /> �� � � � 3. REWORK EXISTING FIRE, LIFE, SAFETY SYSTEM AS REQUIRED PER NEW WALL LAYOUT AND Sheet �(�W�ER+COMMUNICATIONS PLAN
<br /> 9 � �� �� 6� �� � � � �� � � � � CURRENT CODE. ENGINEERING AND INSTALLATION BY BUILDING RECOMMENDED
<br /> A8.1 . C NFE EN E OOM SUB-CONTRACTOR.
<br /> . � � 2 � 3 ' 4. PROVIDE SMOKE DEfECTORS THROUGHOUT TENANT AREAS IN ACCORDANCE WITH LOCAL
<br /> CODES AND MANUFACTURER'S RECOMMENDATIONS.
<br />-, � � o 0 0 5. LOCATE ALL LIGHT FIXTURES, SPFAKERS, LIFE-SAFETY DEVICES, ETC., IN STRAIGHT LINES Date: 10/24/16
<br /> � � � � AND IN CENTER OF CEILING TILES, U.O.N.
<br /> ° �p � 6. ALL CEILING MOUNTED DEVICES SHALL BE WHITE. Design:
<br /> • W A8.1 7. LOCATE ANY CONTROLS THAT NEED ACCESSING OVER ACOUSTICAL CEILING TILE AREAS. DO
<br /> � � NOT PL4CE ANY ABOVE GYPSUM BOARD CEILINGS, UNLESS APPROVED BY ARCHITECT. Drawn:
<br /> a, � � ' � � ' ' ' 8. ALL ACCESS PANELS IN GYPSUM BOARD CEILINGS SHALL BE FRAMELESS; LOCATIONS
<br /> Q -___ -_-_-_� SHALL BE COORDINATED WITH ARCHITECT. GROUP DEVICES TO MINIMIZE THE NUMBER
<br /> a
<br /> AND SIZE OF ACCESS PANELS. Project No: 16-144
<br /> � � '
<br /> 9. ALL CONDUITS, BOXES, DUCTS, HVAC UNITS, PIPES, ETC., SHALL BE INSTALLED AS HIGH
<br /> N I AS POSSIBLE NOT LOWER THAN 8" ABOVE LINE OF HIGHEST FINISHED CEILING. Approved: KCR
<br /> �' � 10. THERE SHALL BE NO COMBUSTIBLE MATERIALS IN THE PLENUM SPACE.
<br /> �
<br /> � 11. WHEN MULTIPLE SWITCHES OCCUR IN CLOSE PROXIMITY GANG UNDER SINGLE SWITCH Building No:
<br /> . `� PLATE.
<br /> � � N 12. FURNISH AND INSTALL NEW THERMOSTATS AS REQUIRED. INSTALL CLOSE TO DOOR
<br /> r OPENINGS, DO NOT INSTALL IN CENTER OF WALL. ARCHITECT AND CLIENT TO APPROVE
<br />-� � i REFLECTED CEILING PLAN - FIRST FLOOR ALL LOCATIONS.
<br /> � 13. ALL LIGHTS TO BE CONTROLLED BY MOTION SENSOR. PROVIDE OVERRIDE SWITCH AT ALL Sheet No: ■
<br /> �, 1 ��8.� = 1'-0»
<br /> , e CONFERENCE ROOMS
<br /> r 14. ALL LAMPS SHALL BE IDENTICAL FROM ONE MANUFACTURER IN SAME TEMPERATURE, COPYRIGHT CRAFT ARCHITECTS 2016
<br /> U.N.O.