MITSUBISHI EQUIPMENT SCHEDULE <br /> CFM AMPS BTUH - HTG BTUH - CLG GB SYSTEMS, �NC. <br /> NAME LOCATION SEaVES MAKE MODEL # MAX OA MIN ESP VOLT PH MCA FUSE HP DB INPUT OUTPUT TOTAL SENS. IEER TONS WEIGHT REMARKS <br /> HEATING * AIR CONDITIONING <br /> AIR AND WATER BALANCING <br /> CU-1 OUTSIDE �ASEMENT MITSUBISHI PURY-P168TLMU-A N/A (2) N/A 208 3� 68 110 N/A 61 129.9 MBH N/A 170.4 MBH N/A 15.9 14 702 3,6 7202 NE 17�th <br /> BC-1 STORAGE B08 6ASEMENT MITSUBISHI CMB-P108NU-GA N/A (2) N/A 208 1� .85 15 N/A N/A N/A N/A N/A N/A N/A N/A 122 4,6 Pno e�425*V482 0584 <br /> AC-1 CLASSROOM B19 CLASSROOM 619 MITSUBISHI PVFY-P30EOOA 815 (2) .50 208 1� 2.5 15 .53 41 21.0 MBH N/A 27.5 MBH 17.6 MBH N/A 2.5 115 5,6 �'ox 425�482*0586 <br /> AC-2 CLASSROOM B03 CLASSROOM B03 MITSUBISHI PVFY-P30EOOA 815 (2) .50 208 1� 2.5 15 N/A N/A 21.0 MBH N/A 27.5 MBH 17.6 MBH N/A 2.5 1 15 5,6 <br /> AC-3 CLASSROOM B15 CLASSROOM B15 MITSUBISHI PVFY-P30EOOA 815 (2) .50 208 1� 2.5 15 N/A N/A 21.0 MBH N/A 27.5 MBH 17.6 MBH N/A 2.5 115 5,6 <br /> AC-4 CLASSROOM B14 CLASSROOM B14 MITSUBISHI PVFY-P30EOOA 815 (2) .50 208 1� 2.5 15 N/A N/A 21.0 MBH N/A 27.5 MBH 17.6 MBH N/A 2.5 115 5,6 <br /> AC-5 CLASSROOM B11 CLASSROOM B11 MITSUBISHI PVFY-P30EOOA 815 (2) .50 208 1� 2.5 15 N/A N/A 21.0 MBH N/A 27.5 MBH 17.6 MBH N�A 2.5 115 5,6 <br /> AC-6 LOBBY 101, RECEPTION LOBBY 101, RECEPTION MITSUBISHI PEFY-P36NMHU-E2 1340 (2) .50 208 1� 4.7 15 N/A N/A 24.7 MBH N/A 32.9 MBH 22.2 MBH N/A 3.0 155 5,6 <br /> CU-2 OUTSIDE MAIN FLOOR MITSUBISHI PURY-P120TLMU-A N/A (2) N/A 208 3� 42 60 N/A 63 183.4 MBH N/A 236.4 MBH N/A 19.0 2p 695 1,6 <br /> PU RY-P240TSKM U-A � <br /> MITSUBISHI PURY-P120TLMU-A N/A (2) N/A 208 3� 42 60 N/A 63 695 1,6 � <br /> BC-2 STOaAGE B08 MAIN FLOOR MITSUBISHI CMB-P108NU-GA N/A (2) N/A 208 1� 2.3 15 .87 45 N/A N/A N/A N/A N/A N�A 122 4,6 � <br /> AC-7 CORRIDOR (LOBBY B01) CORRIDOR (LOBBY B01) MITSUBISHI PEFY-P36NMHU-E2 1340 (2) .50 208 1� 4.7 15 N/A N/A 40.0 MBH N/A 36.0 MBH 28.8 MBH N/A 3.0 155 5,6 � � (f' <br /> AC-8 CAFETERIA 106 CAFETERIA 106 MITSUBISHI PEFY-P96NMHU-E 2540 (2) .50 208 1� 7.9 15 N/A N/A 108.0 MBH N/A 96.0 MBH 76.8 MBH N/A 8.0 221 5,6 � � � <br /> AC-9 CAFETERfA 106 CAFETERIA 106 MITSUBISHI PEFY-P96NMHU-E 2540 (2) .50 208 1� 7.9 15 N/A N/A 108.0 MBH N/A 96.0 MBH 76.8 MBH N/A 8.0 221 5,6 � !�1 � � <br /> AC-10 CLASSROOM 102 CLASSROOM 102 MITSUBISHI PVFY-P30EOOA 815 (2) .50 208 1� 2.5 15 N/A N/A 34.0 MBH N/A 30.0 MBH 24.0 MBH N/A 2.5 1 15 5,6 � v � �J � <br /> Q � <br /> NOTES: � � <br /> 1. 10 TON TWINNED VRF HEAT PUMP WITH HEAT RECOVE�Y A <br /> 2. SEE ERV EQUIPMENT SCHEDULE W � � <br /> 3. 14 TON VRF HEAT PUMP WITH HEAT RECOVE�Y <br /> 4. 8 PORT BRANCH CONTROLLER, 6 USED. PROVIDE CONDENSATE, BY OTHERS <br /> 5. MODIFY TO UPFLOW CONFIGURATION � � �' <br /> 6. COMPLIES WITH WSEC 2015 SECTION C406.1.1 AND C406.1.5 � � <br /> � cn N � <br /> ERV EQUIPMENT SCHEDULE LOUVER SCHEDULE � � O <br /> � Q O <br /> CFM ESP AMPS EFFECTIVENESS j� <br /> NAME AREA MAKE MODEL # SUPPLY EXHAUST SUP XH VOLT PH MCA FUSE HP TEMPERATURE WEIGHT REMARKS NAME AREA MAKE STYLE DIMENSIONS TYPE MAfiERIAL REMARKS � V � <br /> ERV-1 CLASSROOM B03, CORRIDOR (LOBBY), CONF 607 MITSUBISHI LGH-F600RX5-E 540 485 .25 208 1� 3.6 15 .52 63.0� 132 2 L-1 CLASSROOM 603 RUSKIN ELF375DX 18"Wx18"H OSA INTAKE ALUMINUM 1,2 � <br /> BASEMENT LEVEL LOSSNAY ,50 BASEMENT LEVEL <br /> ERV-2 CLASSROOM 611, OFFICE 609, T�ACHERS B08 MITSUBISHI LGH-F470RX5-E 440 395 .25 208 1� 3.6 15 .52 64.4� 132 2 L-2 CLASSROOM B11 RUSKIN ELF375DX 18"Wx18"H RELIEF/EXHAUST ALUMINUM 1,2 W <br /> BASEMENT LEVEL LOSSNAY .25 BASEMENT LEVEL <br /> ERV-3 CLASSROOM 619 MITSUBISHI LGH-F470RX5-E 390 350 .25 208 1� 3.1 15 .52 �4.4� 119 2 L-3 CLASSROOM 611 RUSKIN ELF375DX 18"Wx18"H OSA INfiAKE ALUMINUM 1,2 <br /> BASEMENT LEVEL LOSSNAY .25 BASEMENT LEVEL <br /> E�V-4 CLASSROOM B15 MITSUBISHI LGH-F470RX5-E 405 370 .25 208 1� 3.1 15 .52 64.4� 119 2 L-4 CLASSROOM B19 RUSKIN ELF375DX 18"Wx18"H RELIEF/EXHAUST ALUMINUM 1,2 <br /> BASEMENT LEVEL LOSSNAY .25 BASEMENT LEVEL <br /> ERV-5 CLASSROOM 614, STORAGE B12 MITSUBISHI LGH-F470RX5-E 435 390 .25 208 1� 3.1 15 .52 66.7� 119 2 L-5 CLASSROOM B19 RUSKIN ELF375DX 18"Wx18"H OSA INTAKE ALUMINUM 1,2 <br /> BASEMENT LEVEL � LOSSNAY .25 BASEMENT L EL <br /> � � � <br /> ERV-6 CLASSROOM 102 MITSUBISHI LGH-F470RX5-E 330 295 .25 208 1� 3.1 15 .52 64.4� 119 2 L-6 CLASSROOM B15 RUSKIN ELF375DX 18"Wx18"H OSA I�ITAKE ALUMINUM 1,2 v�i � � <br /> MAIN LEVEL LOSSNAY .25 BASEMENT LEVEL `� � ° <br /> � \ � <br /> ERV-7 CAFETERIA 106 WEST MITSUBISHI LGH-F600RX5-E 600 540 .25 208 1� 3.6 15 .52 68.7� 132 1,2 L-7 CLASSROOM 615 RUSKIN ELF375DX 18"Wx18"H RELIEF/EXHAUST ALUMINUM 1,2 O � °C <br /> MAIN LEVEL LOSSNAY .25 BASEMENT LEVEL <br /> ERV-8 �AFETERIA 106 EAST MITSUBISHI LGH-F600RX5-E 600 425 .25 208 1� 3.6 15 .52 56.8� 132 1,2 L-8 CLASSROOM B14 RUSKIN ELF375DX 18"Wx18"H OSA I�ITAKE ALUMINUM 1,2 <br /> MAIN LEVEL LOSSNAY .25 BASEMENT LEVEL <br /> ERV-9 LOBBY 101, RECEpTION 109 MITSUBISHI ILGH-F470RX5-E 460 460 •25 208 1� 3.1 15 .52 69.0� 119 2 L-9 CLASSROOM B14 RUSKIN ELF375DX 18"Wx18"H RELIEF/EXHAUST ALUMINUM 1,2 <br /> MAIN LEVEL LOSSNAY .25 BASEMENT LEVEL <br /> L-10 CAFETERIA 106 WEST RUSKIN ELF375DX 24"Wx18"H OSA INTAKE ALUMINUM 1,2 <br /> NOTES: MAIN LEVEL <br /> 1. PROVIDE CO2 CONTROLS, MOUNT IN RETURN AIR DUCT <br /> 2. COMPLIES WITH WSEC 2015 SECTION C406.1.1 AND C406.1.5 L-11 CAFETERIA 106 IEAST RUSKIN ELF375DX 24"Wx18"H OSA INTAKE ALUMINUM 1,2 <br /> MAIN LEVEL <br /> NOTES: <br /> 1. RUSKIN OR EQUIVALENT, PROVIDED IBY GENERAL CONTRACTOR <br /> EXHAUST FAN SCHEDULE 2. GENERAL CONTRACTOR TO DEfERMINE FRAME CONFIGUIRATION <br /> � z <br /> AMPS � � <br /> NAME AREA MAKE MODEL # CFM ESP VOLT PH HP RPM WEIGHT REMARKS <br /> MCA FUSE � � <br /> � <br /> EF-1 JANITOR 107 BROAN L100 75 .25 120 1� 1.1 15 .1 1 650 23 1,2 O � � <br /> MAIN LEVEL <br /> � � <br /> w w � <br /> NOTENTERLOCK WITH LIGHT SWITCH, BY ELECTRICAL CONTRACTOR Northshore Buiiding F Ou.�tsicie Air Calculations N � W <br /> 2. FACTO�RY �BACKDRA�T' DAMPER INC�UDED N � � <br /> z <br /> _ ___ <br /> _ -- - <br /> UNIT ZONE AREA SQ FT, SQ FTPER PEOPLE�F'ER VENTILATION VENTILATION OSA OSA � <br /> PERSON ZONE PER PERSON PER ZONE �! REQUIRED PROVIDED a a a a a a Q o <br /> �� �� pz � Rp Fta z � <br /> BACKDRAFT DAMPER SCHEDULE � <br /> ERV-3 Z1 Classroo�,,B7,9 899 32. . _ 28.1 10.0 107.9 388.8 . 390 <br /> NAME AREA MAKE STYLE DIMENSIONS FUNCTION MATERIAL REMARK - -- ' - - - - - <br /> - - - - - - ----- <br /> ERV-1 ZZ Classroom B03 899 32 28.1 10.0 107.9 388.8 390 <br /> BDD-1 STORAGE 105 RUSKIN BCR2 12"� RELIEF GALYANIZED ERV-4 Z3 Classroom B15 930 32 29.1 10.0 111.6 402.2 405� <br /> • --- - �, <br /> MAIN LEVEL ERV-5 �Z� �Classroom B14 930 32 29.1 10.0 111.6 402.2 405 � <br /> BDD-2 CLASSROOM 102 RUSKIN BCR2 10"� RELIEF GAILVANIZED . �ERV-Z �Z5 �Classroom 811 �899 �32 �28.1 �10.0 ;� �107.9 �388.8 �390 ( <br /> MAIN LEVEL ERV-5 �Z6 [Storage �364 �364 �1.0 �5.0 �21.8 �26.8 �30 � <br /> ��RV-1 �Z6 �Lobby (corridor� �1390 �0 �0.0 ,0.0 �83.4 �83.4 (85 � <br /> ERV-2_ Z6 Office ` _ 130 _--�130--- 1.0 _ T�- �5.0 __ _ �7.8 �12.8 �15 � <br /> ERV-2 Z6 Teacher 195 49 4.0 5.0 11J 3�..6 35 <br /> _ _ _ <br /> ERV-1 Z6 Conf 180 18 10.0 5.0 10.8 60.8 65 <br /> �R� SC H E D U LE ERv-�,8 Z7 Cafeteria 3286 12.4 265.0 5.0 197.2 1522.2 1530 <br /> �ERV-6 �Z8 (Classroom 7t72 �7�4 ,32 �23.6 �10.0 �90.5 �326.'I �330 � <br /> NAME MAKE STYLE DIMENSIONS NECK SIZE TYPE REMARK �ERV-9 �Z9 f Lobby 101 �1120 �1120 �1.0 'S.0 i 67.2 �72.2 �75 � rawn : a�__a_ _y: <br /> �ERV-9 Z9 Rece�tion 117 117 1.0 5.0 7.0 1Z0 15 i SK GB <br /> -� _ �--- -- - _� ,_.�z�. _ __w ,ro----- --�--�� --v��,_�-. _ �- '1 <br /> SD-1 TITUS MCD 24"x24" SEE D'iRAWING METAL �J..AY-IN WHITE �N/A �Z10 iKit�l'�et� �37� '• �125 . �3 0 �.0 �22.6 �37.7 �40 � Start3n9 Date: ProJect Number. <br /> �N I ( � � I � � � I � 12/6/16 326 <br /> SWG-1 TITUS 300RS SEE DRAWING SEE D'RAWING SIDE WALL GRILLE WHITE /A Z10 IVlens,�Vomens 532 Q 0.0 0.0 0.0 0.0 - a No►tn: scaie: <br /> �� __ � __ _ � -�� _ �- ___ � -�� �r N 1/8"-1'-p» <br /> RG-1 TITUS EGGC�RATE 24"x24" SEE DRAWING MIETAL LAY-IN WHITE Totals: 4200 <br /> 1 I I I I I � I � I �D �,le: <br /> RWG-1 TITUS 350RL SEE DRAWING SEE DIRAyyING SIDE 1NALL GRILLE WHITE � . <br /> EG-1 TITUS EGGC�RATE 12"x12" SEE D'RAINING METAL SURIFACE MOUNTED WHITE -'--' <br /> SCHEDULES 8c <br /> NOTES HVAC <br /> s <br /> �L SCHEDULE 8c LEGEND HVAC <br /> Ln <br /> N <br /> �� SCALE: N/A <br /> � <br /> o� <br /> � <br /> � � � � � R � � N � � R �J � � I � N • <br /> U <br /> N <br /> \ <br /> �� <br />