HEADER PER <br />STRUCTURAL <br />GWB <br />SIDING - SEE ELEVATIONS <br />FOR TYPE <br />W.R.B. (TYP.) <br />SEE DETAILS 8/11 AND <br />17/11 FOR INSTALLATION <br />SLOPE <br />10* MIN. <br />24 GAUGE PPM FLASHING <br />PROVIDE SEALANT END DAMS <br />AT EACH END <br />5/4 EXTERIOR TRIM (TYP.) <br />SEE ELEV. FOR WIDTH <br />SEALANT AND BACKER ROD <br />PROVIDE 2x8 BLOCKING PER MFR INSTALLATION <br />(FOR DRAPERY) EACH SIDE REQUIREMENTS <br />OF HEAD AT ALL BEDROOM VINYL SLIDING GLASS DO <br />AND GREAT ROOM WINDOWS <br />(TYP.) <br />PATIO DOOR HEAD <br />17 <br />SECTION <br />PROVIDE BLOCKING FOR <br />TRIM AND SIDING <br />GWB <br />2 2 SEALANT <br />al fin <br />OR <br />SIDING, <br />------------- ---------*---_�-------- <br />-= <br />- <br />SEE ELEV. <br />FOR TYPE <br />SHIM, PER DOOR <br />SEALANT PER SIDING <br />MFRS REQUIREMENTS <br />MFR INSTALLATION <br />SEALANT AND BACKER ROD <br />REQUIREMENTS <br />PER DOOR MFR INSTALLATION <br />FLASHING SYSTEM <br />REQUIREMENTS <br />SEE DETAILS 8/11 <br />5/4X5Y EXTERIOR TRIM (TYP.) <br />AND 17/11 <br />SEE ELEV. FOR WIDTH <br />SLIDING <br />PATIO DOOR JAMB <br />18013 <br />= 1'-0" <br />PLAN <br />INTERIOR <br />SEE STRUCTURAL <br />FOR HEADER SIZE <br />EXTERIOR <br />SIDING - SEE ELEVATIONS <br />FOR TYPE <br />W.R.B. (TYP.) <br />SEE DETAILS 8/11 AND <br />17/I1 FOR INSTALLATION <br />SHEATHING <br />/4" MIN. GAP <br />24 GAUGE PPM FLASHING <br />FIN. FL <br />EXTERIOR <br />SLOPE <br />10' MIN. <br />d- <br />HEA <br />FLASHIN <br />2x10 TRIM <br />V8" TYPE 'X' GWB <br />/2" GWB (MIN.) <br />S NEEDED <br />Z PER <br />2x HEAD TRIM <br />i <br />14 TYP. GARAGE HEADER <br />1-1/2" = 1'-0" SECTION <br />FOUNDATION OPENING �/2" GWB (MIN.) <br />OVERHEAD DOOR DOOR SIZE FPROVIDE <br />SYSTEM TRIM AN <br />D ND SIDING <br />r l FLASHING SYSTEM <br />2X TRIM <br />I SEALANT PER MFR <br />LNSTA A <br />DOOR FRAME <br />%X5Y2 EXTERIOR TRIM (TYP.) <br />IN -SWINGING SEE ELEV. FOR WIDTH <br />DOOR SEALANT PER DOOR MFR <br />INSTALLATION REQUIREMENTS <br />qu <br />EXTERIOR DOOR HEAD <br />19 <br />3" = 1'-0" SECTION <br />INTERIOR <br />PROVIDE BLOCKING FOR <br />TRIM AND SIDING <br />--FLASHING SYSTEM <br />6 6 SEE DETAILS 8/11 <br />AND 17/11 <br />ISIDING, SEE ELEV. <br />FOR TYPE <br />SHIM PER DOOR <br />FLASHING SYSTEM <br />MFRS REQUIREMENTS <br />SEE DETAILS 8/11 <br />SEALANT PER MFR <br />AND 17/11 <br />INSTALLATION <br />SEALANT PER SIDING <br />EXTERIOR REQUIREMENTS <br />MFR INSTALLATION <br />TRIM(TYP.)REQUIREMENTS ( ) <br />ELEV. FOR WIDTH <br />DOOR JAMB <br />*EXTERIOR <br />20 <br />3" = 1'-0" <br />PLAN <br />LL SIDING SEE ELEV. <br />REQUIREMENTS FOR TYPE, INSTALL PER <br />5/4 <br />X 5Y EXTERIOR TRIM (TYP.) <br />::7 <br />MFR REQUIREMENTS <br />SEE ELEV. FOR WIDTH <br />FLASHING SYSTEM <br />SEALANT PER MFR <br />EXTERIOR <br />INSTALLATION <br />REQUIREMENTS <br />15 GARAGE DOOR <br />JAMB <br />1-1/2" = 1'-0" <br />PLAN <br />EXTERIOR TRIM AT <br />GARAGE DOOR JAMB <br />SECTIONAL OVERHEAD <br />I DOOR TRACK AT SIDES <br />c OF OPENING <br />EXTERIOR <br />SEE DETAIL 11/D2 <br />FOR GARAGE SLAB <br />AND APRON <br />I � <br />i- <br />GARAGE DOOR THRESHOLD <br />16 <br />3" = 1'-0" SECTION <br />3/4" T&G PLYWOOD SUBFLOOR UNIT <br />OVER 2X FLOOR FRAMING <br />16" O.C. U.N.O.T <br />(1) LAYER 5/s" GWB UNIT <br />(5/a" TYPE 'X' GWB WITH <br />R-30 INSULATION WHEN <br />OVER GARAGE) <br />9 J <br />NTERMEDIATE STAIR LANDING <br />1 1/2" = 1'-0" SECTION <br />1Ys" FLOOR SHEATHING <br />2x12 STRINGERS <br />AT 12" O.C. <br />PROVIDE R-30 INSUL. <br />OVER UNHEATED <br />SPACES. <br />SEE UNIT STAIR <br />PLANS FOR RISER <br />AND TREAD <br />DIMENSIONS. <br />10 BOTTOM OF STAIR ® LANDING <br />1 1/2" = 1'-0" SECTION <br />1T. T <br />RIPPED 2x8 FRAMING @ i iii r ii <br />16" o.c. FOR LANDING IN' FLOOR <br />SEE STAIR PLANS FOR SHEATHING <br />LANDING HEIGHT <br />2x12 STRINGERS 1x8 <br />AT 12" O.C. <br />° <br />° <br />2x BLOCKING ° <br />(1) LAYER <br />° 5/s" GWB <br />HANGER PER <br />° STRUCTURAL <br />BEAM PER STRUCTURAL <br />° <br />° <br />\-2x BLOCKING <br />AS NECESSARY SEE UNIT STAIR <br />PLANS FOR RISER <br />5 PER PLANS AND TREAD <br />D1 DIMENSIONS. <br />BOTTOM LANDING 0 STAIR <br />11 <br />1-1/2" = 1'-o" SECTION <br />2x8 FRAMING I <br />® 16" o.c. <br />HANGER PER <br />STRUCTURAL <br />2x BLOCKING­4 <br />l ° <br />N <br />TOENAIL 2x6 © 16" o.c. <br />BEAM PER FOR CEILING FRAMING <br />STRUCT RAL ° <br />° (1) LAYER <br />V8" G WB <br />°_ . 2x BLOCKING <br />PER PLANS <br />12 RAISED FLOOR 0 STAIR CEILING <br />1-1/2" = V-0" SECTION <br />T 1" <br />2 X 12 STRINGERS''%"'�"%�''��''' <br />AT 12" <br />1X8 <br />GARAGE <br />1Y" FLOOR SHEATHING <br />PROVIDE R-30 INSUL. <br />OVER UNHEATED <br />2 <br />SPACES. <br />SEE UNIT STAIR 2 <br />PLANS FOR RISER <br />AND TREAD s 4 <br />(1) LAYER <br />DIMENSIONS. 2 s <br />%" TYPE X GWB <br />2 <br />R-21 INSUL. <br />5 STAIR DETAIL AT GARAGE <br />1 1/2" = 1'-0" SECTION <br />T <br />1Ys" FLOOR <br />SHEATHING <br />PROVIDE R-30 <br />2 X 12 STRINGERS <br />INSUL. OVER <br />AT 12" O.C. <br />UNHEATED <br />1 X8. 20A <br />SPACES. <br />D1 <br />2xl2 P.T. <br />(1) LAYER -Ys" GWB <br />BOTTOM PLATE <br />° <br />4 <br />�Eff��MEME;II�T�Ti I ff lll►T�TTiITT��1iTTIl�T��I� (�IIT�' <br />� I I - <br />SEE UNIT STAIR <br />PLANS FOR RISER <br />AND TREAD <br />DIMENSIONS. <br />6 BOTO F STAIR @ CO NC <br />. <br />= 1'-0" SECTION <br />UNIT <br />IN' FLOOR SHEATHING—, <br />1x8. T <br />2x12 STRINGERS <br />AT 12" O.C.—� <br />Pe \—PROVIDE R-30 INSUL. <br />OVER UNHEATED <br />SPACES. <br />(1) LAYER <br />Vs" GWB <br />SEE UNIT STAIR <br />PLANS FOR RISER <br />AND TREAD <br />DIMENSIONS. <br />1 TOP OF STAIR DETAIL <br />1 1/2" = 1'-0" SECTION <br />T <br />1Ys" FLOOR <br />SHEATHING <br />1" <br />2x12 STRINGERS <br />AT 12" O.C. <br />1Tx8 <br />D1 2x BLOCKING PROVIDE R-30 INSL <br />5 <br />OVER UNHEATED <br />SPACES. <br />(1) LAYER <br />° %" GWB <br />° BEAM PER STRUCTURAL <br />° <br />11 <br />SEE UNIT STAIR <br />PLANS FOR RISER <br />AND TREAD <br />DIMENSIONS. <br />2 BOTTOM OF STAIR <br />SECTION <br />INSULATION AND ENERGY NOTES <br />hpJaHm - canard <br />All insulation materials shall be installed according to the manufacturer's <br />instructions to achieve proper densities, and maintain uniform R-values. <br />Substantial contact of the insulation with the surface being insulated is required. <br />Where required, insulation shall be installed with clearances according to <br />manufacturer's specifications. Insulation shall be installed so that required <br />ventilation is unobstructed. For blown or poured loose fill insulation clearances <br />shall be maintained through installation of a permanent retainer. <br />Slab on erode <br />R-10 slab on grade insulation shall be installed inside the foundation wall and <br />shall extend down vertically 24' or to the top of the footing whichever is less <br />per WSEC section R402.2.9. <br />Wated P1=8 <br />Floor insulation shall be installed in a permanent manner in substantial <br />contact with the surface being insulated. Insulation supports shall be installed so <br />spacing is no more than twenty-four inches on center. <br />Floors separating conditioned space from unconditioned space shall have a <br />vapor barrier installed. Vapor barrier shall be installed on the warm side of the <br />insulation. The vapor barrier shall have a one perm dry cup rating or less (i.e. <br />four mil. polyethylene or kraft faced material) The floor sheathing may be used <br />as the vapor barrier if rated (and so stamped) at one perm (max.) Otherwise <br />place vapor barrier on top of joists before placing sheathing. <br />Exterior Wak <br />All wall insulation shall fill the entire cavity. Exterior wall cavities isolated <br />during framing shall be fully insulated to the levels of the surrounding walls. All <br />faced insulation shall be face stapled to avoid compression. <br />Walls separating conditioned space from unconditioned space shall have a <br />vapor barrier installed. Faced Batt insulation shall be face stapled. Vapor <br />barrier shall be installed on the warm side of the insulation. <br />Air Leakage <br />These air leakage notes apply to those locations separating outdoor <br />ambient conditions from interior spaces that are heated or mechanically cooled. <br />Exterior joints around windows and door frames, between wall cavities and <br />window or door frames, openings between walls and foundation, between walls <br />and roof and wall panels; openings at penetrations of utility services through <br />walls, floors and roof; and all other openings in the building envelope shall be <br />sealed, caulked, gasketed, or weatherstripped to limit air leakage in a manner <br />approved by the building official. <br />Dws <br />All exterior doors or doors serving as access to an enclosed unheated <br />area shall be weatherstripped to limit leakage around their perimeter when in a <br />closed position. <br />The thermal transfer characteristics of insulated doors shall be U-value 0.30 <br />or better per WSEC section R402.1.1. <br />Wndows: <br />Glazing U-values for windows and SGD shall be U-value 0.30 or better per <br />WSEC section R402.1.1 as indicated on the unit plans. <br />Windows shall be furnished with outdoor air inlets as indicated on the Unit <br />Electrical plans. Inlets shall have a controllable and secure opening and be <br />capable of a total opening area of not less than four (4) square inches and <br />tested by a nationally recognized standard or approved agency and located <br />to avoid drafts. Inlets shall be screened or otherwise protected from entry by <br />insects, leaves, or other material. <br />Roof/Ce&QX <br />Roof/Ceiling insulation: Open -Blown or poured loose fill insulation may be <br />used in attic spaces where the slope of the ceiling is more than 4 in 12 and <br />there is at least 44 inches of clear distance from the top of the bottom chord <br />of the truss or ceiling joist to the underside of the sheathing. When eave vents <br />are installed, baffling of the vent openings shall be provided so as to deflect <br />the incoming air above the surface of the insulation. Baffles shall be rigid <br />material, resistant to wind driven moisture. When feasible, the baffles shall be <br />installed from the top of the outside of the exterior wall, extending inward, to a <br />point six inches vertically above the height of noncompressed insulation, and <br />twelve inches vertically above loose fill insulation. Baffles shall be in place at <br />the time of framing inspection. <br />Where the ventilation space above the insulation is less than an average of <br />twelve inches roof ceiling assemblies shall be provided with a vapor barrier <br />having a 0.5 perm cup rating or less. Faced batt insulation where used as a <br />vapor barrier shall be face stapled. <br />Vapor barriers shall not be required in roof/ceiling assemblies where the <br />ventilation space above the insulation averages twelve inches or greater. <br />Vapor barriers shall be installed on the warm side of the insulation. <br />FlrepbM <br />Fireplaces shall be provided with each of the following: <br />a) Tightly fitting flue dampers, operated by a readily accessible manual or <br />approved automatic control. <br />b) An outside source for combustion air ducted into the firebox. The duct <br />shall be at least six square inches, and shall be provided with an <br />operable outside air duct damper. <br />c) Tightly fitting glass or metal doors, or flue draft induction fan or as <br />approved by the Building Official for minimizing backdrafting. <br />d) Include elbows for offsets to framing as necessary. <br />Sheet Order: A B U F R E S <br />5052 REGISTERED <br />ARCHITECT <br />ROBERT E. WEIBLE <br />STATE OF WASHINGTON <br />o. <br />a N <br />o <br />to <br />L <br />o <br />a N <br />o <br />o <br />O <br />■� <br />4 <br />�L <br />T <br />m <br />Q� <br />•a�+ <br />a <br />0 <br />'s. <br />c <br />x � <br />> <br />Q) <br />E >% <br />C <br />0 <br />4) Q. <br />W = 0 <br />W , C) <br />0 0)_ <br />N <br />J am <br />= L <br />V 0 <br />W 0 Z <br />I- w r. <br />0 <br />0 <br />o a <br />Li <br />Q <br />Li <br />Job No.: 13-47 <br />zSheet No.: <br />0 <br />D5 <br />