DDC POINT LIST (CONT) LLI F,DDC POINT LIST (CONT) 4.) („:„!-5
<br /> CONTROL FUNCTION DEVICE INPUTS OUTPUTS ALARMS REMARKS CONTROL FUNCTION DEVICE INPUTS OUTPUTS ALARMS REMARKS
<br /> ANALOG DIGITAL ANALOG DIGITAL ANALOG DIGITAL ANALOG DIGITAL ANALOG DIGITAL ANALOG DIGITAL Z ---"'
<br /> EXHAUST AIR HANDLING UNIT EAU(TYP EAU-5 THRU EAU-11)(CONT) DUCT DISCHARGE TEMPERATURE TS X
<br /> EXHAUST FAN HIGH STATIC PRESSURE SHUTDOWN DPH X X HEATING WATER CONTROL VALVE TCV X ...
<br /> EXHAUST FAN LOW STATIC PRESSURE SHUTDOWN DPL X X
<br /> SMOKE DETECTOR (BY DIVISION 28) SD X SEND PAGER ALARM FAN COIL UNIT CONTROL(TYP) 0 ..,—L33
<br /> HEAT RECOVERY COIL SUPPLY WATER TEMPERATURE TS X ENABLE/DISABLE SS X
<br /> HEAT RECOVERY COIL RETURN WATER TEMPERATURE TS X FAN STATUS CS X X
<br /> FILTER STATUS DPS X X
<br /> PRESSURIZATION FAN CONTROL(TYP PF-1 THRU PF-8) SUPPLY AIR TEMP TS X X
<br /> ENABLE/DISABLE CR X X FROM FIRE CONTROL PANEL SPACE TEMPERATURE T X X SEE PLANS AND CONTROL DIAGRAMS
<br /> VFD FAN SPEED (%) (TYP) SOFTWR X X THRU BACNET INTERFACE CHILLED WATER CONTROL VALVE TCV X PRESSURE INDEPENDENT L. W3,„„ W
<br /> VFD STATUS (TYP) SOFTWR X X THRU BACNET INTERFACE HEATING WATER CONTROL VALVE TCV X FCU—R01 THRU FCU—R08 AND FCU—001 ONLY
<br /> PRESSURE SENSOR (BETWEEN SHAFT AND SPACE) DPS X X EXHAUST FAN DISCHARGE DAMPER MOD X FCU-402, 403 AND 404 ONLY Lao Ce 14.1
<br /> PRESSURE SENSOR (NEAR TOP OF SHAFT) DPS X MONITOR ONLY, BETWEEN SHAFT AND SPACE EXHAUST DAMPER POSITION ES X X FCU-402, 403 AND 404 ONLY
<br /> X SEND PAGER ALARM411111,1
<br /> MOD X
<br /> 2 POSITION SD
<br /> OUTSIDE AIR DAMPER OR BY DIVISION 28
<br /> SMOKE DETECT
<br /> OUTSIDE AIR DAMPER END SWITCH ES X MANUAL OVERRIDE PB X X
<br /> SMOKE DETECTOR (BY DIVISION 28) SD X SEND PAGER ALARM
<br /> COMPUTER ROOM UNIT(CRAC-1)
<br /> LOADING DOCK EXHAUST FAN EF-1 UNIT CONTROLS AUX WIRE BETWEEN SENSORS AND UNIT
<br /> VFD ENABLE/DISABLE (TYP) SOFTWR X X THRU BACNET INTERFACE STATUS CS X X EVERETT,WASHINGTON
<br /> VFD FAN SPEED CONTROL (TYP) SOFTWR X THRU BACNET INTERFACE GENERAL ALARM AUX X X SEND PAGER ALARM
<br /> VFD FAN SPEED (%) (TYP) SOFTWR X X THRU BACNET INTERFACE SPACE TEMPERATURE T X X .GUNS(/`
<br /> VVFD STATUS (TYP) SOFTWR X X THRU BACNET INTERFACE SPACE HUMIDITY H X X w� .,
<br /> EXHAUST AIR FLOW SOFTWR CALCULATED & DISPLAY OUTPUT FROM VFD HIGH LIMIT HUMIDITY H X X �y
<br /> EXHAUST AIR DUCT STATIC PRESSURE DPS X X `f'
<br /> SMOKE DETECTOR (BY DIVISION 28) SD X SEND PAGER ALARM HOT WATER CABINET HEATER UNIT CONTROL(TYP) tJ
<br /> . ZG r f
<br /> EXHAUST DUCT AUTO DAMPER MOD X UNIT THERMOSTAT WIRE BETWEEN THERMOSTAT AND UNIT7 C
<br /> EXHAUST DAMPER POSITION ES X ENABLE/DISABLE CR X S.�
<br /> NITROGEN DIOXIDE SENSOR NO2 X X SEE FLOOR PLANS FOR LOCATION (3 TYP) STATUS CS X X 'ITECH
<br /> PUSH BOTTON OVER—RIDE PB X SPACE TEMPERATURE T X X
<br /> EXHAUST FAN DISCHARGE DAMPER MOD X TEMPERATURE CONTROL VALVE TCV X THREE—WAY OR TWO—WAY AS INDICATED Architecture/Planning/Interior Design
<br /> EXHAUST DAMPER POSITION ES X X Portland Seattle Los Angeles Washington DC
<br /> HOT WATER UNIT HEATER CONTROL(TYP) 925 Fourth Ave.,Suite 2400
<br /> ISOLATION EXHAUST FAN(TYP EF-2,&EF-3) UNIT THERMOSTAT WIRE BETWEEN THERMOSTAT AND UNIT Seattle,Washington 98104
<br /> VFD ENABLE/DISABLE (TYP) SS X THRU BACNET INTERFACE ENABLE/DISABLE CR X
<br /> VFD FAN SPEED CONTROL (TYP) SOFTWR X THRU BACNET INTERFACE STATUS CS X X (PH)206 623 9414
<br /> VFD FAN SPEED (%) (TYP) SOFTWR X X THRU BACNET INTERFACE SPACE TEMPERATURE T X X
<br /> (FAX)206 623 7868
<br /> VFD STATUS (TYP) CT X X THRU BACNET INTERFACE TEMPERATURE CONTROL VALVE TCV X THREE—WAY OR TWO—WAY AS INDICATED
<br /> EXHAUST AIR FLOW SOFTWR THRU BACNET INTERFACE BASED ON VFD
<br /> Consultants
<br /> EXHAUST AIR DUCT STATIC PRESSURE DPS X X
<br /> ELECTRIC UNIT HEATER CONTROL(TYP)
<br /> EXHAUST FAN DISCHARGE DAMPER MOD X UNIT THERMOSTAT WIRE BETWEEN THERMOSTAT AND UNIT LIFE SAFETY
<br /> EXHAUST FAN DAMPER POSITION ES X X ENABLE DISABLE CR X ROLF JENSEN& ASSOCIATES
<br /> SMOKE DETECTOR (BY DIVISION 28) SD X X SEND PAGER ALARM / 19125 North Creek Parkway Suite 120
<br /> STATUS CS X X Bothell,Washington 98011
<br /> SPACE TEMPERATURE T X X
<br /> KITCHEN EXHAUST UNIT&GREASE EXHAUST FAN(EF-4) KEU PROVIDED IN CONTRACT CIVIL ENGINEER
<br /> VFD ENABLE/DISABLE (TYP) SS X THRU BACNET INTERFACE CONDENSATE PUMP CONTROL(TYP CP-1,2&3) Magnusson Klemencic Associates
<br /> VFD FAN SPEED CONTROL (TYP) SOFTWR X THRU BACNET INTERFACE ENABLE DISABLE AUX X 1301 Fifth Avenue,Suite 3200
<br /> ENABLE/
<br /> DISABLE
<br /> VFD FAN SPEED (%) (TYP) SOFTWR X X THRU BACNET INTERFACE SYSTEM GENERAL ALARM AUX X X Seattle,Washington 98101-2699
<br /> VFD STATUS (TYP) CT X X THRU BACNET INTERFACE CONDENSATE PUMP HIGH LEVEL AUX X X LANDSCAPE ARCHITECT
<br /> EXHAUST AIR FLOW SOFTWR THRU BACNET INTERFACE Site Workshop
<br /> EXHAUST AIR DUCT STATIC PRESSURE DPS X X927 Post Alley
<br /> SUMP PUMP CONTROL(TYP SP-1&SP-2) _
<br /> SMOKE DETECTOR (BY DIVISION 28) SD X X SEND PAGER ALARM ENABLE/DISABLE AUX X Seattle,Washington 98101
<br /> FILTER DIFFERENTIAL PRESSURE (4 TYP) DPS X X PROVIDE DPS FOR EACH FILTER BANK SYSTEM GENERAL ALARM AUX X X
<br /> A
<br /> STRUCTURAL ENGINEER
<br /> SUMP PUMP HIGH LEVEL AUX X X Magnusson Klemencic Associates
<br /> KITCHEN HOOD EXHAUST FAN CONTROL(TYP EF-5&EF-6)
<br /> 1301 Fifth Avenue,Suite 3200
<br /> EXHAUST FAN START/STOP SS X DOMESTIC WATER HEATING SYSTEM Seattle,Washington 98101-2699
<br /> EXHAUST FAN STATUS CS X X WATER HEATER (5 TYPICAL)
<br /> EXHAUST FAN DISCHARGE DAMPER MOD X ENABLE/DISABLE CR X MECHANICAL ENGINEER
<br /> EXHAUST DAMPER POSITION ES X X m
<br /> . STATUS CS X X 19203 36th Ave.W,Suite 200
<br /> ALARM STATUS AUX X X Lynnwood,Washington 98036
<br /> EXHAUST FAN CONTROL(TYP EF-7) ISOLATION CONTROL VALVE ICV X 4 TYP, DO NOT PROVIDE ON DWH-1
<br /> EXHAUST FAN START/STOP SS X HOT WATER SUPPLY TEMPERATURE TS X X ELECTRICAL ENGINEER
<br /> EXHAUST FAN STATUS CS X X SPARLING
<br /> 720 Olive Way,Suite 1400
<br /> EXHAUST FAN DISCHARGE DAMPER MOD X PIPING SYSTEM (3 TYP) Seattle,Washington 98101-1853
<br /> EXHAUST DAMPER POSITION ES X X HOT WATER SUPPLY TEMPERATURE TS X X
<br /> OUTSIDE AIR DAMPER MOD X HOT WATER CIRC TEMPERATURE TS X GENERAL CONTRACTOR
<br /> OUTSIDE AIR DAMPER POSITION ES X X COLD WATER SUPPLY TS X X M.A.Mortenson Company
<br /> SPACE TEMPERATURE T X STORAGE TANK SUPPLY WATER TEMPERATURE TS X 14719 N.E.29th Place
<br /> Bellevue,Washington 98007
<br /> STORAGE TANK RETURN WATER TEMPERATURE TS X
<br /> EXHAUST FAN INTERLOCKED WITH AHU CONTROL(TYP EF-8&EF-9)
<br /> EXHAUST FAN START/STOP SS X CIRC PUMP (6 TYP) Revisions
<br /> EXHAUST FAN STATUS CS X ENABLE/DISABLE CR X
<br /> EXHAUST FAN DISCHARGE DAMPER MOD X PUMP STATUS CS X X
<br /> EXHAUST DAMPER POSITION ES X X DOCUMENT RELEASE 09 11/03/08
<br /> DOMESTIC WATER PRESSURE BOOSTER SYSTEM
<br /> CART WASHER EF(2 TYP) ENEABLE/DISABLE CR X DOCUMENT RELEASE 11 02/09/09
<br /> EXHAUST FAN STATUS CS X PUMP STATUS CT X X DOCUMENT RELEASE 13 03/09/09
<br /> SUPPLY TERMINAL UNIT RELAY MOD X OPENS MAKE—UP AIR TU MOD SYSTEM LOW PRESSURE PS X
<br /> A DR 14 ADDENDUM 1 03/16/09
<br /> SYSTEM HIGH PRESSURE PS X X
<br /> TERMINAL UNIT CONTROL(TYP) WATER METER AUX X DAILY / MONTHLY / ANNUAL TRENDING
<br /> A WORK CHANGE PROPOSAL 025.4 2/01/10
<br /> SPACE TEMPERATURE T X X WATER FILTER COMMON INTAKE PRESSURE PS X
<br /> WORK CHANGE PROPOSAL 87.1 R1 3/10/11
<br /> PRIMARY AIR FLOW DPS X X WATER FILTER DISCHARGE PRESSURE (TYP EA FILTER) PS X 2 WATER FILTERS
<br /> PRIMARY AIR DAMPER MOD X TRI—STATE ACTUATOR ACCEPTABLE
<br /> DUCT DISCHARGE AIR TEMPERATURE TS X MEDICAL AIR/MEDICAL VACUUM SYSTEMS
<br /> HEATING WATER CONTROL VALVE TCV X TRI—STATE ACTUATOR ACCEPTABLE A MEDICAL AIR SYSTEM
<br /> MEDICAL AIR FLOW FM X X INSERTION HOT—WIRE TYPE
<br /> EXHAUST TERMINAL UNIT CONTROL(TYP) MEDICAL AIR COMMON ALARM AUX X X FROM CONTROL PANEL, SEND PAGER ALARM
<br /> EXHAUST AIR FLOW AUX X BASED ON VALVE POSITION
<br /> PANDEMIC CFM OFFSET (LEVEL 10 PATIENT ROOMS) AUX X SIGNAL BY DDC THROUGH TU CONTROLLER MEDICAL VACUUM SYSTEM
<br /> MEDICAL VACUUM FLOW FM X X INSERTION HOT—WIRE TYPE
<br /> DUCT HOT WATER HEATING COILS(TYP) MEDICAL VACUUM PUMP COMMON ALARM AUX X X FROM CONTROL PANEL, SEND PAGER ALARM
<br /> SPACE TEMPERATURE T X X
<br /> DUCT DISCHARGE AIR TEMPERATURE TS X BULK OXYGEN SYSTEM CLOSEOUT PRINTING 04/01/12
<br /> HEATING WATER CONTROL VALVE TCV X TRI—STATE ACTUATOR ACCEPTABLE ALARM — 55 PSIG SYSTEM AUX X X FROM CONTROL PANEL, SEND PAGER ALARM
<br /> 55 PSIG SYSTEM 02 FLOW FM X X SIERRA FLOW METER
<br /> DUCT STEAM HUMIDIFIER CONTROL(MRI) ALARM — 70 PSIG SYSTEM AUX X X FROM CONTROL PANEL, SEND PAGER ALARM Drawing Title
<br /> SPACE HUMIDITY (MRI PROCEDURE ROOM) HS X X WALL MOUNTED HUMIDISTAT IN ROOM 70 PSIG SYSTEM 02 FLOW FM X X SIERRA FLOW METER
<br /> STEAM CONTROL VALVE FCV X CONTROLLED BY SPACE HUMIDISTAT DDC
<br /> HIGH HUMIDITY LIMIT SENSOR HHL X X 5 FT DOWNSTREAM OF DUCT HUMIDIFIER COMPRESSED AIR SYSTEM POINTS LIST
<br /> COMPRESED AIR FLOW METER FM X INSERTION HOT—WIRE TYPE
<br /> ISOLATION ROOMS(TYP) LOW PRESSURE ALARM DP X X SET AT 100 PSIG
<br /> SPACE TEMPERATURE T X X SECONDARY LOW PRESSURE ALARM IN CS DEPT. DP X X SET AT XX PSIG
<br /> DUCT DISCHARGE AIR TEMPERATURE TS X n
<br /> HEATING WATER CONTROL VALVE TCV X 1 LAB AIR COMPRESSORS AND LAB VACUUM PUMP
<br /> EXHAUST AIR TERMINAL UNIT PRESSURE SWITCH DPL X PROVIDE ADDITIONAL 6 ON LEVEL 6 ETU'S ALARM STATUS AUX X X FROM CONTROL PANEL, SEND PAGER ALARM
<br /> EXHAUST AIR TERMINAL UNIT PRESSURE SWITCH DPH X
<br /> SUPPLY AIR TERMINAL UNIT PRESSURE SWITCH DPL X PROVIDE ADDITIONAL 6 ON LEVEL 6 TU'S MISCELLANEOUS
<br /> SUPPLY AIR TERMINAL UNIT PRESSURE SWITCH DPH X ELECTRICAL ENERGY INSTANT. CONSUMPTION (KW) C X CONTINUOUS TRENDING 4., , iii,
<br /> w ,,',
<br /> ROOM PRESSURE MONITOR DPS X X ELECTRICAL ENERGY CONSUMPTION (KWH) AUX X DAILY / MONTHLY / ANNUAL TRENDING ' i'`'' '4
<br /> SOFTWR X X X X X X SEE CONTROL DIAGRAM AND SOR
<br /> ISOLATION ROOM DIGITAL INTERFACE MONITOR GAS METER AUX X PULSE SIGNAL *,, 1: tit..„:4
<br /> ;'„
<br /> 1 . 0
<br /> WATER METER AUX X PULSE SIGNAL �,a
<br /> OPERATING ROOMS(TYP) OUTSIDE AIR TEMPERATURE TS X a"ow,,,,e,,,, � .:'
<br /> SPACE TEMP T X X 'ONiL"
<br /> PRIMARY AIR FLOW — SUPPLY TU DPS X X
<br /> PRIMARY AIR DAMPER — SUPPLY TU MOD X HIGH/LOW VOLUME
<br /> DUCT DISCHARGE AIR TEMPERATURE TS X
<br /> HEATING WATER CONTROL VALVE TCV X Date: NOVEMBER 03,2008
<br /> EXHAUST AIR FLOW DPS X X
<br /> tub No: 580613.01
<br /> EXHAUST AIR DAMPER MOD X
<br /> ROOM PRESSURE MONITOR DPS X X
<br /> Drawn By: CDi
<br /> ROOM SMOKE DETECTOR SD X X Checked By: FJ
<br /> EXH DUCT HUMIDITY H X X HOURLY TRENDING TO DDC, EACH OR
<br /> OR DIGITAL INTERFACE MONITOR SOFTWR X X X X X X SEE CONTROL DIAGRAM AND S00
<br /> Drawing No.
<br /> ANTE ROOM NIC, FOR FUTURE REFERENCE ONLY
<br /> ROOM PRESSURE MONITOR DPS X X
<br /> ANTE ROOM DIGITAL INTERFACE MONITOR SOFTWR X X X X X X SEE CONTROL DIAGRAM AND SOR
<br /> M10PANDEMIC TERMINAL UNITS(4 TYP) /2\ 10.0
<br /> AUTO AIR DAMPER MOD X OPENS UPON PANDEMIC OPERATION
<br /> FLOW SWITCH FS X X ALARMS WHEN NO FLOW IN PANDEMIC OPER
<br /> PRIMARY AIR FLOW AUX X BASED ON VALVE POSITION SHEET ISSUED FOR REFERENCE
<br /> SPACE TEMPERATURE T X X 1700 13th St—PGMC 2nd Floor Surgery—B1406-017
<br />
|