Laserfiche WebLink
Manger (Suspension) Wires (figurv6 Su and 5b) <br />• Hanger and perimeter wires must be plumb within 1 in 6 unless (figure 5a) <br />counter sloping wires are provided (figure 5b). Source: ASTM C W8 3eCtlotl V.1.4 <br />• Hanger wires shall be 12 gage and spaced 4 feet on center or 10 gage <br />spaced 5 feet on center. Source; ASTM c 036 <br />• Any connection device at the supporting construction shall be capable of car- <br />rying not less than 100 pounds. source: CISCA zorr„ 3-4 <br />• PowderLdriven shot -in anchors (PAFs) are an approved method of attachment <br />for hanger wires. ^ou,Cr.: St:ttr. or Oregon, t3ulldleg Codrr. Olvi%ion <br />• Terminal ends of each main beam and cross tee must be supported within 8 <br />inches of each wall with a perimeter wire (see figure 4 & 5 b). Smircr: CISCA nxtr..:1�1 <br />• Wires shall not attach to or bend around interfering material or equipment. A <br />trapeze or equivalent device shall be used where obstructions preclude direct <br />suspension. Trapeze suspensions shall be a minimum of back-to-back 1'/4 inch <br />cold -rolled channels for spans exceeding 48 inches. Sowcc: CISCA /onto 3-4 <br />Electrical fixtures <br />• bight fixtures weighing less than 10 pounds shall have one 12 gage hanger <br />wire connected from the fixture to the structure above. This wire may be slack. <br />term: C63CA Sci.-,uric zones 3-4 <br />• Light fixtures weighing more than 10 pounds and less than 56 lbs. shall have <br />two 12 gage wires attached at opposing corners of the light fixture to the <br />structure above. These wires may be slack. Swrcc; CISCA Sorsrttic zones 3.4. <br />• Light Fixtures weighing more than 56 lbs. shall be supported directly from the <br />structure above. Those wires must be taut. Source- CISCA Soi umlc :ones 3.4 <br />• Pendant mounted fixtures shall be directly supported from the structure above <br />using a 9 gage wire or an approved alternate support without using the ceiling <br />suspension system for direct support. source; CISCA Sciomic zones 3-4 <br />• Tandem fixtures may utilize common wires. <br />Mechanical Services <br />• Terminals or services weighing 20 Ibs. but not more than 56 lbs. must have two <br />12 gage wires connecting them to the ceiling system hangers or the structure <br />above. These wires may be slack. solYce: C!.^,CA Sgi,mir 7onoL 3-4 <br />• Terminals or senrlcft weighing more than 56 fibs. must be independently <br />supported directly from the structure above. These wires must be taut, Source; <br />CISCA Seismic Lone* 3-4 <br />SeiStnio Separation Joints Viguro 7) <br />• For telling areas exceeding 2.600 square feet, a seismic separation joint or full <br />height wall partition that breaks the ceiling shall be provided unless analyses <br />are performed of the ceilings bracing system, closure angles and penetrations <br />to provide sufficient clearance. source: ASCE 7-05 mertion Section 13_S.li.2.2 d <br />• The layout and location of the seismic separation joint shall be per the design- <br />er of record and noted on the plans. H a seismic separation joint Is required by <br />the designer, the designer may use the generic joint detailed in this document <br />or a proprietary joint The amount of free movement (gap design) shall be a <br />minimum of 44 inch. sourer.; Stato of Oregon. Bwitlrng code.,!; Division <br />• In lieu of seismic separation joints, the ceiling may be divided into areas less <br />than 2500 square feet by the use of partitions or soffits as follows: partitions shall <br />extend a minimum of 6 Inches above the Level of the plane of the grid and shall <br />be independently braced to the structure above. Soffits shall extend to a point at <br />least level with the bottom plane of the grid and shall be independently supported <br />and laterally braced to the structure above. source st:,tr. p• orlon Building Codes Division <br />• Other than partitions and soffits, seismic joints may not be used as pan of a <br />fire rated ceiling assembly unless substantiating. documentation is provided. <br />.niourdr: Stato of Orogon Building CsSdra Dlviolon <br />Sprinklers <br />For ceilings without rigid bracing. sprinkler head penetrations shall have a 2 inch <br />oversize ring, sleeve or adapter through the ceiling file to allow free movement of at <br />least 1 inch in all horizontal directions. Flexible head design that can accommodate <br />1 inch free movement shall be permitted as an alternate. Sourco: ASCE i-os f:r. s.6.a.P o <br />figure 5b Counteralloping. <br />flqure 6a <br />Vw nl h•np•r wlr• •ir mol•n•nt <br />Shot -In anchor .-............._.....,..__...._..__ <br />Strue4,m1 concrete -..,...,,,.I <br />Coifing cilp -- —.� S/u <br />-- Max. <br />3 turns .__�.�..._...__............. •. <br />VArti(W hwpur wire -.•.....-- <br />Nguro 6b <br />so" -i-we tar•rinp �n aR•oltn•fR <br />drill-InAkpw)e5ori.v,rhor tf;; <br />WIN <br />Structural eoArryty <br />Stuel elrap t' widn x P1 long x 1 <br />12 ljaer. minimum <br />3 tvrng _____..__..—_._._............. ' <br />�. <br />f3010Yr.O ;rplaml c bracing Wite ---�' <br />f/gure 7 <br />i I � <br />Mangoyrs ._J Rlyat <br />Pop <br />0Z00/bT00 1A <br />NUN IMWE:rT WALL K C910NQ'RUri .4( • SUSPENSION SY,,,,TFMS FOR ACOUSTICAL LAY.IN CFILINa3 <br />X1RJTsa00M1U?x'8u?ass ZTM96C2Z XVd Rd ST: C TTOZ/5T/TT <br />