Laserfiche WebLink
SPECIFICATIONS; MXZ�2C20NAHZ2 co�nrtd. <br /> OPERATING RANGE: ENERGY EFFICIENCIES: <br /> Outdoor Indoor Unit Type SEER EER HSPF CO7P I @ OPF <br /> Cooling D.B.14 to 115°F[D.B.-10 to 46°C]`1 Non-ducted <br /> 17.0 13.5 9.8 4.00 2.77 <br /> Heating W.B.-13to65°F[W.B.-25to18°C] (09+09) <br /> "1.D.B.5 to 115°F[D.B.-15 to 46°C], when an optional Air Outlet Ducted and 16.00 12.25 9.65 3.85 2.65 <br /> Guide is installed. Non-ducted <br /> Ducted 15.0 11.0 9.5 3.69 2.53 <br /> (09+12) <br /> NOTES: <br /> • Minimum of two Indoor Units must be connected to the MXZ-2C2ONAHZ2. <br /> • Minimum installed capacity cannot be less than 12,000 Btu/h. <br /> • Total connected capacity must not exceed 130%of outdoor unit capacity. <br /> • System can operate with only one Indoor Unit turned on. <br /> • Information provided at 208/230V. <br /> • For Reference: <br /> -MXZ-C Technical&Service Manual for detailed specifications and additional information per Indoor Unit Combination. <br /> -MXZ Series Multi-Zone Indoor/Outdoor Combination Table for allowed unit combinations. <br /> MVZ CONNECTION RULES: <br /> • Only 1 MVZ may be used on any system. <br /> • When an MVZ is connected,total connected capacity must be 100%or less. <br /> • When an MVZ is connected,no P-Series indoor units can be used(PCA,PLA,or PEAD). <br /> Notes: <br /> Specifications are subject to change without notice. ©2016 Mitsubishi Electric US,Inc. <br />