... <br /> STRUCTURAL NOTES _ <br /> (THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS). <br /> CODE CONCRETE NON-SHRINK GROUT GENERAL 4 <br /> ALL MATERIALS, WORKMANSHIP,DESIGN AND CONSTRUCTION SHALL CONFORM TO THE ALL CONCRETE SHALL BE MIXED,PROPORTIONED,CONVEYED AND PLACED IN NON-SHRINK GROUT SHALL BE CEMENT-BASED WITH A MINIMUM COMPRESSIVE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL, <br /> DRAWINGS, SPECIFICATIONS AND THE UNIFORM BUILDING CODE(UBC, 1997 ACCORDANCE WITH SECTION 1905 OF THE UBC AND THE AMERICAN CONCRETE STRENGTH OF 5000 PSI WHEN TESTED IN ACCORDANCE WITH ASTM C-109.GROUT CIVIL ELECTRICAL, AND MECHANICAL DRAWINGS FOR BIDDING AND CONSTRUCTIN. <br /> EDITION.SPECIFICATIONS AND STANDARDS WHERE REFERENCES 011 THE DRAWINGS INSTITUTE'S SPCCIFT:'ATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS SHALL BE MIXED AND PLACED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S CONTRACTOR SHLL VERIFY ALL DIMENSIONS AND CONDITIONS FOR COMPATIBILITY ENGINEERING <br /> ARE TO BE THE LATEST EDITION. (ACI 301). RECOMMENDATIONS. BEFORE PROCEEDING. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION 111 MAIN STREET,SUITE 106 <br /> OF THE ARCHITECT BEFORE PROCEEDING. EDMONDS,WASHINGTON 98020 <br /> DESIGN LOADS ALL CONCRETE SHALL YE STONE--AGGREGATE CONCRETE HAVING A UNIT WEIGHT OFSTRUCTURAL STEEL PHONE (425)778-8500 <br /> APPROXIMATELY 150 POUNDS PER CUBIC FOOT. FAX (425)776-5536 <br /> 1 CONTRACTOR TO SEE ARCHITECTURAL,CIVIL,ELECTRICAL AND MECHANICAL <br /> LIVE LOADS: STRUCTURAL STEEL DESIGN FABRICATION AND ERECTION SHALL BE IN ACCORDANCE DRAWINGS FOR SIZE AND LOCATION OF PIPE,VENT,DUCT AND OTHER OPENINGS <br /> ROOF(SNOW LOAD) DT LOADINCONCRETE S' NG •T : 1. ..0 . RIT1;RLO Q WITH THE AISC"SPECIFICATION FOR THE DESIGN,FABRICATION AND ERECTION OF AND DETAILS NOT SHOWN ON THESE DRAWINGS.EXIT FACILITIES (..z5:z.L.„..."- RIFSTRUCTURAL STEEL FOR BUILDINGS", LATEST EDITION. <br /> PRIVATE DECKS 40 PSF MAXIMUM WATER/ MINIMUM CEMENT CONTENT CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION STABILITY AND TEMPORARY <br /> CORRIDORS 100 PSF TYPE OF CONSTRUCTION f c CEMENT RATIO PER CUBIC YARD PLATES,SHAPES,ANGLES AND RODS SHALL CONFORM TO ASTM A36,Fy= 36,KSI. SHORING AS NECESSARY UNTIL PERMANENT SUPPORT AND STIFFENING ARE <br /> OFFICE 50 PSF INSTALLED. <br /> PARTITIONS 20 PSF ANCHOR BOLTS SHALL CONFORM TO ASTM A307. <br /> PARKING 100 PSF SLABS ON GRADE 3000 PSI 0.5 5 1/2 SACK CONTRACTOR-INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT, <br /> FOUNDATIONS 3000 PSI 0.5 5 1/2 SACK STRUCTURAL TUBING SHALL CONFORM TO ASTM A500 GRADE B,Fy=46ksi STRUCTURAL ENGINEER AND BUILDING DEPARTMENT FOR APPROVAL PRIOR TO FABRICATION OR <br /> (LIVE LOADS ARE REDUCED WHERE PERMISSIBLE PER UBC SECTION 1607). CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL I;OT SATISFY THIS <br /> ALL OTHER STRUCTURAL 4000 PSI 0.5 6 1/2 SACK MASONRY REQUIREMEN I. <br /> EARTHQUAKE LOADS: C.I.P.CONCRETE <br /> CONCRETE MASONF<r'UNITS SHALL BE ASTM C90,MEDIUM WT,TYPE I fm=1500 PSI DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION.WHERE <br /> 2.5001 TH MI,•• •,+UN . C ' T LI D A:eVE M' BE CHANGED IFA CONCRETE MORTAR SHALL CONFORM TO ASTM C 270 TYPE S. CONDITIONS LS ARESHNOT SPECIFICALLY INDICATED FCONSTRUCTION BUT RE SHALLOF A SIMILAR CHARACTER,SUBJECT <br /> 1.4R PERFORMANCE MIX IS SUBMITTED TO THE ENGINEER FOR GROUT SHALL CONFORM TO ASTM C 476 f c=2000 PSI TO REVIEW AND APPROVAL, ADETAILS C CET BE USED,SUBJECT <br /> APPROVAL TWO WEEKS PRIOR TO PLACING ANY CONCRETE.THE PERFORMANCE MIX TO REVIEW BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. <br /> SEISMIC COEFFICIENT Ca) .36(ZONE 3,SOIL TYPE D) SHALL INCLUDE THE AMOUNTS OF CEMENT,FINE AND COARSE AGGREGATE,WATER AND <br /> IMPORTANCE FACTOR I) 1.00 ADMIXTURES AS WELL AS THE WATER-CEMENT RAT10, SLUMP,CONCRETE HELD AND WELDING <br /> ALLOWABLE STRESS D SIGN FACTOR 1.4 SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH UBC SECTION 1904 AND 1905. ', , <br /> LEGEND ""�'� <br /> STRUCTURE TYPE FACTOR(R) 4.5 WELDING SHALL CONFORM TO AWS 01.1 1996 EDITION. ALL WELDING SHALL BE DONE c,• �+ <br /> ALL CONCRETE EXPOSED TO WEATHER OR TO FFEEZING TEMPERATURES SHALL BE WITH 70 KSI LOW HYDROGEN ELECTRODES.WHERE NOT CALLED OUT, MINIMUM FILLET U.•:2.5(0.36)(1.0) AIR-ENTRAINED WITH AN AIR-ENTRAINING AGENT CONFORMING TO UBC STANDARD WELD SIZE SHALL BE PER TABLE 5.8 IN AWS STRUCTURAL WELDING CODE,1996 EDITION. SYMBOLS ABBREVIAl10NS Ca 8 <br /> 1.4(4.5) 0.14 W 19-4.TOTAL AIR CONTENT SHALL BE IN ACCORDANCE WITH UBC TABLE 19-A-1. �, <br /> W=TOTAL SEISMIC DEAD LOAD AS DEFINED PER UBC SECTION 1630.1. <br /> REINFORCING STEEL O WELDING OF REINFORCING BARS SHALL NOT BE PERMITTED UNLESS SPECIFICALLY is;rr 9 <br /> CALLED OUT ON DRAWINGS OR APPROVED BY STRUCTURAL ENGINEER. WELDING OFsjaN�. <br /> GRADE 60 REINFORCING BARS SHALL BE PERFORMED USING LOW HYDROGEN DIRECTION OF FRAMING ALT. ALTERNATE 11.1 <br /> WIND LOADS: ELECTRODES.WELDING OF GRADE 40 REINFORCING BARS SHALL BE PERFORMED USING A.B. ANCHOR BOLT <br /> DESIGN WIND PRESSURE(P),P=CeCgQs1 REINFORCING STE SHALL BE DEFORMED BILLET STEEL CONFORMING TO ASTM E70XX ELECTRODES.SEE REINFORCING NOTES FOR MATERIAL REQUIREMENTS OF WELDED < > EXTENT OF FRAMING BM. BEAM : 7 6 <br /> BASIC WIND SPEED 80 MPH A-6).5,AND SHALL BE GRADE 60(Fy=6000 PSI),UNLESS NOTED OTHERWISE. BARS.WELDING WITHIN 4"OF COLD BENDS IN REINFORCING BARS IS NOT PERMITTED. DOT. BOTTOM <br /> ' EXPOSURE B A706(Fy=60,000 PSI)SHALL BE USED AlT CMU BOUNDARY ELEMENTS. in 0 COLUMNS BRG. BEARING <br /> IMPORTANCE FACTOR 1.0ALL WELDING SHALL BE DONE BY WASHINGTON ASSOCIATION OF BUILDING OFFICIALS P CENTEui�E <br /> D •:RIC ALL ONFORM TO AS • :5. --I o 'r o 1 • FABRIC (WABO)CERTIFIED WELDERS. COL.BEARING ON BEAM OL. COLUMN <br /> SEE PLANS FOR ADDITIONAL DESIGN LOADS. IN SHEETS NOT ROLLS. CONC. CONCRETE <br /> REINFORCING STEEL SHALL BE DETAILED INCLUDING HOOKS AND BENDS IN PLYWOOD BEAM CONTINUOUS OVER SUPPORT CONT. CONNECTION <br /> CONT. CONTINUOUS <br /> ACCORDANCE WITH SP66(94)AND ACI 318R-95.PROVIDE ELBOW BARS TO LAP 5- 5 CMU WALL DBL. DOUBLE <br /> SPECIAL INSPECTION HORIZONTAL WALL AND FOOTING REINFORCEMENT AT ALL CORNERS AND PLYWOOD SHEATHING SHALL BE GRADE C-D INT-APA WITH EXTERIOR GLUE OR 0 I"ifAMETER <br /> INTERSECTIONS.LAP WELDED WIRE FABRIC 12"AT SIDES AND ENDS.UNLESS STRUCTURAL II WITH EXTERIOR GLUE IN CONFORMANCE WITH UBC STANDARD 23-2 ///r/i, SHEAR WALL DIM. DIMENSION <br /> CONCRETE CONSTRUCTION,MASONRY CONSTRUCTION AND REINFORCING STEEL SHALL RECEIVE OTHERWISE NOTED,REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS OR 23-3. DIR. DIRECTION <br /> SPECIAL INSPECTION IN ACCORDANCE WITH SECTION 1701 OF THE UBC AND THE PROJECT SHALL BE PER SCHEDULE. DWG. DRAWING <br /> SPECIFICATIONS BY A QUALIFIED TESTING AGENCY DESIGNATED BY THE OWNER.THE ARCHITECT LtinII:=1f lf_ NATIVE SOIL DM.. DOWEL <br /> ..ti ECT 'S Q ;i1-ir�r,n=ir EA. EACH <br /> AND STRUCTURAL ENGINEER SHALL BE FURNISHED WITH COPIES OF ALL TEST RESULTS. MECHANICAL SPLICING OF REINFORCING BARS,WHERE INDICATED ON THE DRAWINGS, N. �=�."� " - — <br /> SHALL BE BY AN ICED APPROVED SYSTEM,SHALL DEVELOP 125%OF THE SPECIFIED ALL NAILS SHALL BE COMMON. NAILING SCHEDULE SHALL BE PER 1997 UBC TABLE 'i'a s! GRANULAR FILL EL. ELEVATION <br /> YIELD STRENGTH OF THE BAR,AND SHALL BE INSTALLED IN ACCORDANCE WITH THE •• r'- •`• E.W. EACH WAY <br /> SHOPNO.23-II-B-1 UNLESS OTHERWISE NOTED ON PLANS. <br /> DRAWINGS MANUFACTURER'S RECOMMENDATIONS. SrTRUCTURAL STEEL EXP. EXPANSION <br /> iJ ri/J Jl JJ <br /> SHOP DRAWINGS FOR REINFORCING STEEL,STRUCTURAL STEEL, i 3• S 1 1a J FIN. FOUNDATION <br /> OPEN WEB STEEL JOISTS SHALL BE SUBMITTED TO THE STRUCTURAL MINIMUM LAPS AND EiIBEDMENT 5"`� ��S PLYWOOD SHEATHING FIN. FINIFLOSR <br /> HED <br /> ENGINEER FOR REVIEW PRIOR TO THE FABRICATION OF THESE ITEMS. HEADED STUDS FOR CONNECTION OF STRUCTURAL STEEL TO CONCRETE SHALL BE MANUFACTURED SW_ SHEAR WALL SEE SCHEDULE ,FLR. FOOTING <br /> UNLESS OTHERWISE NOTED,REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS ( ) GLB GLUE-LAMINATED BEAM 1 <br /> ENGINEER'S SHOP DRAWING REVIEW IS FOR GENERAL CONFORMANCE WITH THE DESIGN SHALL BE AS TABULATED BELOW: FROM MATERIAL CONFORMING TO ASTM A 108 AND SHALL BE WELDED IN CONFORMANCE WITH AWS HORIZ. HORIZONTAL <br /> CONCEPT AND CONTRACT DOCUMENTS. MARKINGS OR COMMENTS SHALL NOT BE REQUIREMENTS. C_ COLUMN MARK(SEE SCHEDULE) MAX. MAXIMUM <br /> CONSTRUED AS RELIEVING THE CONTRACTOR FROM COMPLIANCE WITH THE PROJECT DEVELOPMENT LENGTH TENSION LAP LENGTH OFOOTING MARK(SEE SCHEDULE) MIL METAL <br /> PLANS AND SPECIFICATIONS.THE CONTRACTOR REMAINS RESPONSIBLE FOR DETAILS ADHESIVE ANCHORS MIN. MINIMUM <br /> AND ACCURACY,FOR CONFORMING AND CORRELATING ALL QUANTITIES AND SIZE TOP BARS OTHER BARS TOP BARS OTHER BARS l CHEVRON BRACING NTS. NOT TO SCALE o <m <br /> DIMENSIONS,FOR SELECTING FABRICATION PROCESSES,FOR TECHNIQUES OF BASE ANCHOR MINIMUM ALLOWABLE ALLOWABLE O.C. ON CENTER t= o'a <br /> ASSEMBLY AND FOR PERFORMING THE WORK IN A SAFE MANNER. #3 19 14 25 19 MATERIAL SIZE EMBEDMENT TENSION SH AR PL. PLATE 6, au. <br /> ENGINEER'S SHOP DRAWING REVIEW OF STRUCTURAL COMPONENTS DESIGNED BY OTHERS 18 <br /> 24 24 32 24 CONC. 1/2"ROD 4 1/2" 2,880 1,940 PSL PARALLAM c. <br /> Q. <br /> 5/8" REINF. REINFORCING V> �``' <br /> IS FOR LOADS IMPOSED ON THE BASIC STRUCTURE.THE COMPONENT DESIGNER IS S 29 29 38 29 CONC. 5/8"ROD 5 4,795 3,040 w a. <br /> #6 35 35 46 35 CONC. 3/4"ROD 6 3/4" 6,700 4,380 SCHED. SCHEDULE a cc.O_ <br /> SIM. SIMILAR <br /> RESPONSIBLE FORCODE CONFORMANCE. #7 62 62 81 62 CONC. #4 BAR 6" 4,415 2,780 --- , <br /> " STD. STANDARD Q,c <br /> SHOP DRAWINGS SHALL BE REVIEWED AND STAMPED BY THE CONTRACTOR PRIOR TO #8 72 72 ' 94 72 CONC. #5 BAR 7 1/2" 6,580 4,415 STL, STEEL <br /> REVIEW BY THE ENGINEER. #9 81 81 106 81 CONC. #6 BAR 9" 9,200 6,335 SYMM. SYMMETRICALa ,-- <br /> CONC. #7 BAR 10 1/2" 12,195 8,640 TYP. TYPICAL o 0 <br /> SOLDIER PILE WALL_ NOTES: 1. ALL LENGTHS ARE IN INCHES. 1 THESE VALUES ARE BASED ON THE POWER-FAST EPDXY INJECTION GEL BY POWERS RAWL. T.D.C. TOP OF CONCRETE Y <br /> 2. "TOP BARS"ARE HORIZONTAL REINFORCEMENT SO PLACED THAT 2 ROD STEEL IS A36, fy=36 ksi Fu=58ksi T.O.W. TOP OF WALL <br /> NO MORE THAN 4 FEET OF EXCAVATION SHALL BE EXPOSED BEFORE INSTALLJNG LAGGING. MORE THAN 12 INCHES OF CONCRETE IS CAST IN THE MEMBERU.N.O. UNLESS NOTED OTHERWISE a <br /> 3 REBAR STEEL IS A615, fy=60ksi Fu=90ksi <br /> BELOW THE BAR. VERT. VERTICAL I <br /> 4)ALLOWABLE SHEAR AND TENSION <br /> CONCRETE SHALL NOT BE ALLOWED TO FREE-FALL TO THE BOTTOM OF THE DRILLED LOADS ARE THE LESSER OF THE BOND STRENGTH W.W.F. WELDED WIRE FABRIC DESIGN: <br /> OR THE STEEL STRENGTH. FU <br /> HOLE,BUT EITHER BE TREMIED OR PUMPED INTO THE HOLE. CONCRETE COVER ON REINFORCING 5)EXISTING CONCRETE IS ASSUMED TO HAVE A COMPRESSIVE STRENGTH,f'c=2,000 psi DRAWN: SK <br /> TIMBER LAGGING SHALL BE HEM-FIR#2,Fb= 1,020 PSI,Fv=70 PSI.ALL LAGGING CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3" CHECK: CCC <br /> SHALL BE PRESSURE TREATED IN ACCORDANCE WITH UBC 2303.1,ITEM 3. <br /> CONCRETE EXPOSED TO EARTH AND WEATHER: OPEN VEB,TI +ffi <br /> JOB NO: 98072 <br /> DRAINAGE MATTING TO BE MIRADRAIN OR ENKADRAIN OR APPROVED EQUAL #6 BARS AND LARGER 2" <br /> #5 BARS AND SMALLER 1 1/2" OPEN WEB STEEL JOISTS SHALL BE DESIGNED IN ACCORDANCE WITH THE STEEL JOIST <br /> REFER TO SOILS REPORT FOR ADDITIONAL INFORMATION. INSTITUTE(SJI)AND AMERICAN INSTITUTE OF STEEL CONSTRUCTION(AISC), "STANDARD <br /> CONCRETE NOT EXPOSED TO EARTH OR WEATHER: SPECIFICATIONS FOR OPEN WEB STEEL JOISTS"AND'LOAD TABLES". LIVE LOAD DEFLECTIONS <br /> SLABS,WALLS AND JOISTS 1" SHALL BE LIMITED TO 1/360 OF SPAN. <br /> FOUNDATIONS COLUMN TIES OR SPIRALS AND BEAM STIRRUPS 1" ALL OPEN WEB JOISTS SHALL HAVE HORIZONTAL OR DIAGONAL BRIDGING SPACED IN ACCORDANCE <br /> SOILS REPORT: J-142 BY ZIPPER ZEMAN ASSOCIATES,INC.DATED SEPTEMEBER 11,1998 CONCRETE WALL REINFORCING WITH SJI AND AISC. <br /> PROVIDE THE FOLLOWING MINIMUM REINFORCING UNLESS NOTED OR DETAILED POWDER-ACTUATED)FASTENERS SHALL NOT BE DRIVEN THROUGH ANY PART OF AN OPEN WEB <br /> ALLOWABLE SOIL PRESSURE: 2500 PSF JOIST WITHOUT PRIOR WRITTEN APPROVAL OF THE ENGINEER. <br /> 6000 PSF FOR FOOTINGS BEARING ON OTHERWISE(GRADE 60): <br /> VERY DENSE OR HARD GLACIAL TILL THICKNESS REINFORCING PLACEMENT SEE JOIST SCHEDULE ON SHEET S-6 FOR ADDITIONAL DESIGN LOADS. <br /> PER SOILS REPORT. <br /> LATERAL EARTH PRESSURE: •' 'DINED 42 ' 6"WALLS 4®13"O.C. EACH WAY CENTERED <br /> Q 8 WALLS 5 0 15 O.C. EACH WAY CENTERED <br /> 10"WALLS 4 0 16"O.C. EACH WAY, EACH FACE klIALOM <br /> CANTILEVER SOLDIER PILE RETAINING WALLS ARE DESIGNED FOR Ah ACTIVE PRESSURE OF CONCRETE GENERAL NOTES METAL FLOOR AND ROOF DECKING SHALL CONFORM TO DISI"SPECIFICATION FOR THE DESIGN OF <br /> 15 PCF FOR TEMPORAPY CONDITIONS AT TIMBER LAGGING&40 PCF FOR PERMANENT COLD-FORMED STEEL STRUCTURAL MEMBERS"AND THE STEEL DECK INSTITUTE. <br /> CONDITIONS AND AN ALLOWABLE PASSIVE PRESSURE OF 300 PCF. VERTICAL BARS SHALL START FROM TOP OF FOOTING. HORIZONTAL BARS SHALL <br /> START A DISTANCE OF 1/2 THE NORMAL BAR SPACING FROM TOP OF FOOTING AND TOP <br /> FOOTING 'AL R IR DISTURBED SOIL OR 12" COM' CTED STRUCTURAL OF FRAMED SLABS. IN ADDITION,THERE SHALL BE A HORIZONTAL BAR AT A METAL DECK SHALL CONFORM TO ASTM A 446 GRADE A OR A792 GRADE 33,MINIMUM YIELD STRESS <br /> FILL AT LEAST 18"BELOW ADJACENT EXTERIOR GRADE.ANY FOOTING ELEVATIONS MAXIMUM OF 3 INCHES FROM TOP OF WALL AND BOTTOM OF FRAMED SLABS. 33,000 PSI. SIZE,TYPE,GAUGE AND ATTACHMENT SHALL BE AS NOTED BELOW UNLESS NOTED <br /> SHOWN IN THE DRAWINGS REPRESENT MINIMUM DEPTHS AND ARE FOR BIDDING ONLY. ;THERWISE. PROVIDE SHORING WHERE REQUIRED PER MANUFACTURER. 1 <br /> ACTUAL FOOTING ELEVATIONS ARE SUBJECT TO SITE CONDITIONS AND MUST THEREFORE PROVIDE CORNER BARS TO MATCH THE HORIZONTAL REINFORCING WITH TENSION <br /> BE ESTABLISHED BY THE CONTRACTOR.FOOTINGS SHALL BE CENTERED COLUMNS SPLICE AT EACH SIDE,OR BEND ONE SIDE OVER TO PROVIDE TENSION SPLICE. <br /> OR WALLS ABOVE,UNLESS NOTED OTHERWISE. ALL CONSTRUCTION JOINTS SHALL BE THOROUGHLY CLEANED AND PROPERLY PREPARED W <br /> THE ON-SITE NATIVE SILTY SANDS MAY BE USED FOR STRUCTURAL FILL A5 NOTED IN IMMEDIATELY PRIOR TO POURING OF CONCRETE. DOWEL STEEL SHALL BE THE SAME MINIMUM SECTION PROPERTIES >- Z I- <br /> THE SOILS REPORT.IMPORTED STRUCTURAL FILL AND BACKFILL MATERIAL SIZE AND SPACING AS MAIN REINFORCING DETAILED BEYOND JOINT. Q <br /> SHOULD CONSIST OF CLEAN,WELL GRADED GRANULAR MATERIAL FREE OF DEBRIS OR ORGANICS LOCATION GAGE IMD1H DEPTH SECTION MODULUS MOMENT OF INERTIA O Z <br /> WITH A MAXIMUM PARTICLE DIAMETER OF THREE INCHES AND NO MORE THAN SEE ARCHITECTURAL DRAWINGS AND MECHANICAL DRAWINGS FOR EXACT LOCATIONS CO <br /> 10%FINES(PASSING THE#200 SIEVE). AND DIMENSIONS OF OPENINGS IN CONCRETE WALLS,FLOORS AND ROOF.UNLESS ROOF 20 36" 1 1/2' 0.271 IN^3 FT 0.233 IN^4 FT Q Z Z <br /> INDICATED OTHERWISE,REINFORCE AROUND OPENINGS GREATER THAN 16"IN EITHER / / �"W m Q <br /> DIRECTION WITH 2-#5 EACH SIDE AND 1 -#5 x 4'- 0"DIAGONAL AT EACH _ <br /> FILL AND BACKFILL MATERIAL SHOULD BE PLACED IN LEVEL LIFTS NOT EXCEEDING CORNER.EXTEND BARS 2'-0"BEYOND EDGE OF OPENING.IF 2'-0"IS FLOORS 20 36" 2" 0.361 IN",3/FT 0.423 I;1^4/FT 0 IX -1 Q �/ <br /> EIGHT(8)INCHES IN LOOSE THICKNESS AND COMPACTED TO A MINIMUM OF 95% UNAVAILABLE,EXTEND AS FAR AS POSSIBLE AND HOOK. HOOK ALL REINFORCING 0 <br /> OF ITS MAXIMUM DRY DENSITY AS DETERMINED BY ASTM TEST METHOD D1557-78. INTERRUPTED BY OPENINGS. W 3 <br /> ROOF DECK SHALL BE VERCO TYPE HSB-36 AND FLOOR DECK SHALL BE VERCO TYPE W2 0> " ~ <br /> BACKFILL BEHIND ALL RETAINING WALLS WITH WELL-DRAINING,GRANULAR FILL AND PROVIDE CONTROL OR CONSTRUCTION JOINTS IN SLABS ON GRADE TO BREAK UP SLAB FORMLOK UNLESS NOTED OTHERWISE ON PLANS. z W 0 <br /> PROVIDE FOR SUBSURFACE DRAINAGE AS NOTED IN THE SOILS REPORT. INTO RECTANGULAR AREAS OF NOT MORE THAN 400 SQUARE FEET EACH.AREAS TO BE <br /> AS SQUARE AS PRACTICAL AND HAVE NO ACUTE ANGLES.JOINT LOCATIONS TO BE D w i <br /> PROVIDE DAMPPROOFiNG AT EXTERIOR FACE OF ALL FOUNDATION WALLS EXPOSED TO APPROVED BY THE ARCHITECT.PROVIDE ADDITIONAL CONTROL JOINTS AT INSIDE p c�D W , k <br /> (RE-ENTRANT)CORNERS TO NEXT ADJACENT CONTROL JOINT.IF JOINTS ARE SAWCUT, 0 CO W I- I <br /> EARTH. SAWCUT AS SOON AS PRACTICAL,BUT NO LATER THAN 24 HRS.AFTER SLAB PLACEMENT. <br /> 1 <br /> WHERE NO REINFORCEMENT IS OTHERWISE INDICATED: PROVIDE4 0 18"O.C. <br /> HOOKED DOWELS TO TOP OF CONCRETE SLABS FROM PERIMETER CONCRETE SHEET: <br /> WALLS AND BEAMS. <br /> NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL BE FIELD BENT B6.033) <br /> UNLESS SO DET: ED OR APPRI i D BY E STRUCTURAL ENGIN R. • Siiimil <br /> SEE ARCHITECTURAL DRAWINGS FOR ALL GROOVES,NOTCHES,CHAMFERS,FEATURE <br /> STRIPS,COLOR,TEXTURE AND OTHER FINISH DETAILS AT ALL EXPOSED CONCRETE <br /> SURFACES.ALL EXPOSED CORNERS SHALL HAVE 3/4"CHAMFER U.N.O. 0 6816 Evergreen Way OF: 13 SHEETS <br /> • <br /> • r 1 - ,. <br />