Laserfiche WebLink
,-. <br />HEATING AND COOLING LOAD <br />PROJECT DATA <br />Date ........................10/3/94 <br />Project Description..........BOSTON CHICKEN <br />Prepared For .................ROBERT LEE & ASSOC. <br />Project Location .............EVERETT, WA <br />Prepared By ..................Abossein Engineering Corp <br />Chec}ced By / Computed By.....V.A./G.R.W. <br />---------------- <br />DESIGN CONDITIONS <br />Latitude 47 degrees <br />Elevation 60 feet Daily Range, F 21 <br />Outside <br />InG=de <br />Difference <br />Summer Design <br />db F wb F <br />79 67 <br />78 65 <br />1 <br />Block Cooling Load <br />Peak Hour 17 <br />Peak Month 8 <br />Sensible (Btu/hr) <br />Roof 45C <br />Wall 1503 <br />Glass 65457 <br />Lights 12736 <br />People 11868 <br />Equipment 5619 <br />Infiltration -1 <br />Duct 1953 <br />Lacent (Btu/hr) <br />People .11400 <br />Equipment 8400 <br />Infi.ltration 6 <br />Ventilation (Btu/hr) <br />Sensible -1072 <br />Latent 5175 <br />Total Vent. 4103 <br />Winter Design <br />db F <br />23 <br />70 . <br />47 <br />Cooling Load Summary (Btu/hr) <br />----------------------------- <br />Safety Factor 5 <br />Net Sensible 104563 <br />Net Latent 20796 <br />Total Heat 125359 <br />Sen. Heat Ratio 0.83 <br />Grand Total 12q462 <br />Block Heating Load (Btu/hr) <br />--------------------------- <br />Roof 2200 <br />Wall 3021 <br />Glass 24851 <br />Floor z995 <br />Infiltration 2792 <br />Factors 2151 <br />Total Heating 38010 <br />Ventilation 50248 <br />Sldg. Tota1 88257 <br />