May 5, 2011 <br />PUBL/C IYOl�/C5 <br />Mr. Ty Allan <br />Cosco Fire Protection <br />15000 Woodinville-Redmond <br />Woodinville, WA 98072 <br />Road, Suite B-800 <br />Project: Everett Clinic, drop sprinkler heads and lo�ver ceiling <br />Job Address: 7600 Evergreen Way <br />Plan Review No: K1104-006 <br />Sent via e-mail <br />5/�/ �� <br />Dear Mr. Allan, <br />In reviewing the scope of the renovations to the fire sprinkier lines in this permit application, it was <br />determined by our Technical Services Group that the threshoid had not been met to require the upgrade of <br />the current single check detectiun assembly to the Washington State requirement of a double check <br />detector assembly for 7600 Evergreen Way, see attachment. This permit application is being processed <br />and you will get a call from one of our Permit Technicians when it is available. <br />However any future sprinkler revisions may require an upgrade to a double check d�cector assembly. At <br />that timc, the followin9 revisions should first be submitted as a Public Works permit application, and the <br />same information should also be included in the future sprinkler permit application: <br />1. A double-check detector valve asserr�bly (DCDA) should be shown on the drawings. <br />2. Please clarify i.` the City of Everett or if a separate contractor will be providing the assembly. <br />3. This sprinkler submittal will require three copies of the foilowing: <br />• A catalog cut indicating the DC:UA manufaciurer's model in lhe 'BackFlow Prevention <br />Assemblies Approved for Installation in Washinglon State', published by the Washington <br />State Department of Health, current edition. <br />• A plan or section of the intended location and installation of the DCDA. The drawing should <br />indicate the DCDA located horizonially in a vault, and identify the model number on the <br />drawing. <br />4. The routing of the fire service from the city main shouid be shown relative to the property line of <br />the buiiding. <br />5. The riser room should be identified on the plans. <br />6. A PIV is required if there is not direct acce,s to the riser room from outside of the building. <br />Meg Haley, <br />Cc: <br />Attachment <br />Plans Examiner <br />Jim Venturo, Mike Ward, Tim Markham, microfiche file: City of Everett <br />Clinic LLC <br />County Blueshield <br />ENGIN�cRING %�UBLIC SERVICES DIVISION • 3200 Cedar SVeet • Everett, �NA 98201 •(425) 257-8800 • Fax (�125) 257-8856 �/'�!! <br />