Laserfiche WebLink
Aboveground sprinkler piping shall be hydrostatically tested as established in NFPA <br /> Standard 13. Underground piping shail be hydrostatically tested and (lushed as <br /> established in NFPA Standard 24 for private fire mains. (Below-Qround pipinq must <br /> be installed bv Washin4ton State Patrol Licensed Underqround Sprinkler line <br /> certified "U" installers. For further information, contact the State Fire Marshal's <br /> Office at (360) 570-3134 or contact the Evei•ett Fire Department at (425) 257-81?.5.) <br /> All such tests shall be witnessed by a Fire Department inspector. Call (425) 257-8124 <br /> to make an appointment for inspection. <br /> Contractors' materials and test certificates shall be submitted to the Everett Fire <br /> Department prior to issuance of any Certificates of Occupancy. <br /> Call (425) 257-8125 for more information. <br /> 9. Construction and demolition of buildings shall be in compliance with the provisions of <br /> the 2003 International Fire Code, Chapter 14. <br /> 10. Permits are required from the Fire Department for removal and installation of <br /> underground fuel tanks. <br /> 11. All fire alarm control panels (FACP) and sprinkler valves shall be in heated rooms or <br /> closets with standard man door access. Locations shall be approved by the Fire <br /> MarshaPs O(fice. <br /> KJ:Iw <br /> cc: Kirk Brooks, Engr/Public Services � <br /> Dennis Roberson, EngrlPublic Services <br /> Benyam Stephanos, Engr/Public Services <br /> Gordon Witcher, Engr/Public Services <br /> Glen Martinsen, Fire <br /> �` <br /> � <br />