Laserfiche WebLink
� <br />Finley Architects <br />1812 Hewitt Ave. <br />Everett, WA 98201 <br />Dear Mr. Finley: <br />CITV OF <br />everett <br />7801 OAKES � t59�8787 <br />EVEflETT, WASHINGTON <br />aezo, <br />FIRE OEP�RTMENT <br />This letter is written in response to the findings of the Appeals <br />Board. <br />The Fire Department will require extension of the fire detection <br />system and alarm system to the furniture store portion of the <br />building at 9700 Evergreen Way. The use of the same rate of <br />rise/fixed temperature detectors that were indicated in the <br />original fire alarm proposal will be adequate. One manual pull <br />station should be included near the front door of the furniture <br />store. We would recommend that one smoke detector be installed <br />in each of the asembly areas of the bingo hall. These could serve <br />as trade-offs for rate of rise detectors. We would further recommend <br />that these be the spot photoelectric type to minimize false alarming. <br />I am enclosing a copy of the shop drawing requirements to assist <br />you in the preparation of the revisions of the fire alarm system. <br />If we may be of further assistance, please feel free to call. <br />Sincerely, <br />/����G� <br />Wal.ter H. Cooper <br />Fire Marshal <br />Attachment <br />c^c: Leonard Nash <br />Larry Callah�n ✓ <br />WHC:dv <br />