Laserfiche WebLink
e <br />s <br />13 4�'. h,t H' 4F..� . <br />�l:K <br />rot +r , �••. . <br />.�� 4 <br />January 24, 1973 <br />Sunrise View Convalescent Center (Emergency Po�rer) <br />2520 14adison Avenue <br />Everett, 4:ashington 98201 <br />Review of: Idorking Drawinrs and Equipmenl• Data <br />Plnns dated: January 10, 1973 <br />Plans received: January 11, 1973 <br />Edited 6 P.eviewed IIy: J. Norri� Pearson, P.E.� }lealth Services Division <br />ProjecC Designer: Everett Sound Electric <br />RE�'IEId OF STATF. ELECTRICAL I:iSPF.CTOk <br />1, Yrovide nain disconnect s�ritch for energency as required Uy National <br />Electrical Code 384-16. <br />2. <br />3. <br />4. <br />5. <br />All wiring sliall be in a racecaay. <br />All iCems shall be U.L. listed, <br />Check Article Ii700-17 for circuit �airing. <br />Provide G feet separation between normal and emergency service <br />equipnenc. <br />REVITiG' OF STATE FIRE NJ�gSIlAL <br />1. The exhaust shall extend noC less than 2 feet above the hi�hest point <br />of the nursing home roof within 10 feet of L'ermination of the exhaust <br />pipe. <br />2. Provide [a•o (2) openings in the exterior wall for conbustion and ven- <br />tilation air. Each orening slialJ. supply .5 square foot of free air. <br />openinF for each 1000 watts capacity. <br />Locate one opening nor more than 12 inches from the cciling and one <br />not more Chan 12 inches aUove the floor. <br />JNP:ss <br />' �s;rt: <br />m <br />