Laserfiche WebLink
� ' ;: .� <br /> -.. <br /> .� <br /> :;�. <br /> Plan Check Nc. B-39803 <br /> April 19, 1993 <br /> Page Five of Five <br /> l� 39. The following azeas require duct dampers per Item 38 above: I <br /> �) L.evel C1 between grids 18, 19, and E, D crossing corridor at exam N163. <br /> ✓b) L.evel C2 south - twelve places throoghout level when ductwork passes thro�gh corridor <br /> walls and is servin� comdor and adjacent spaces. <br /> �c) Level C2 north between grids 17, 18 and C, D. <br /> ✓40. The storm drain line shown within the alley right-of-way on sheets P1 and P2 must be located <br /> within the project property lines. <br /> In order for the processing of your applicadon to continue, it will be necessary to provide the <br /> . Building Division with two complete new sets of drawings reflecting the corrections requested. <br /> � Upon resubmittal of the drawings, your application will be given priority and plan review <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure that <br /> the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, Ci��'�'L <br /> S. Mc all <br />, Associate Engineer/Building <br /> 1SM:cQlpl�nok-1 <br />