Laserfiche WebLink
,• � <br /> , � <br /> PUBL/C WO/PK5 <br /> hlarch 20, 2013 <br /> �ir. Peter Schroeder Architects <br /> 3838 48°i Ave NE <br /> Seattle, �NA 98105 <br /> Project: Change of Usc From SFR lo Office-Field Inspection Correction <br /> Job Address: 3232 Oakes Ave <br /> Plan Review No: 61211-006 <br /> Dear Mr. Schroeder, <br /> During field inspection yesteiday on plun�bing permit P1303-007, it was noted that additionjl <br /> information is mquired on the permit drawings than what had been previously submitted. �fhe <br /> additional �nformation required and the codes that apply are noted below. Please be advised that <br /> `ederal requirements for accessibility, per the Americans with Disabilities Act, enforced by the <br /> Department of]ustice, may be more restrictive than what is listed on this corrections letter. <br /> Please provide drawing revisions and a response letter, which shows where each item in this correction <br /> letter is addressed on the plan set. To expedite processin9, this information can be sent to me <br /> electronically through e-ir.ail. <br /> General <br /> 1. When walls are exposed to the stud during renovation, the walls should be shown as new on <br /> the drawings. If drywall only is being replaced on an existing stud wall, tiiat should also be <br /> noted on the dra�vings submitted i`or permit, per IBC section 105.2. Additional code <br /> requirements may appl'/. <br /> 2. Elevation changes in Floor level should be noted on the drawings. <br /> Accessibility <br /> 1. The accessible route to the primary function areas shoulJ include the toilet room, per IIiC <br /> 3411.7. <br /> a. The cost of providing an accessible route to the toilet room are not required to exceed <br /> 20 percent of the costs of the alterations affecting the area of primary function, per IBC <br /> section 3411.7, exception 1. <br /> �nergy <br /> 1. Existing wall or floor cavities exposed during construction should be sl �wn �vilh full depth of <br /> insulation with a minimum value of R-3.0, per WSEC section 1132.1. <br /> Deferred PermiYs <br /> 1. Exterior business signage should be submilted separately on a deferred permit for review by <br /> the planning and building departments. <br /> Applicable codes include the 2009 International Building Code (IBC), the 2009 Internationai Fire Code <br /> (IFC), the 2009 Internafional Mechanical Code (IMC), lhe 2009 Washington State Energy Code (WSEC), <br /> as amended by the by the State of Washington and adopted by the City of Everett. The cwrent IBC <br /> referenced standard for accessible design is the 2003 Accessible and Usable Buildings and Facilities <br /> A117.1-2003 (ICC/ANSI). FederalADA reg�dations and standards ma}�Ge more iestrictive. <br /> � ��I � <br />