Laserfiche WebLink
CONSULTATION & CONSTRUCTION REVIEW SECTION <br /> PUBLIC HEALTH AJohn�R.STemplar�RS�I��S1 REVIEW <br /> (360) 705-6786 <br /> Facility • BETHANY AT PACIFIC CAMPUS <br /> DeBcription Z PROPOSED NURSING HOME <br /> CCRS ,� � 96-4580-001 <br /> Date � April 10, 1996 <br /> 1. Wardrobe size shall comply with WAC 388-97-445(3) . <br /> Z, Provide a two compartment sink in each soiled utility/soiled <br /> lined rooms. WAC 388-97-435(2) (b) (i) <br /> 3, Provide grab bars on each side of resident use waterclosets. <br /> The grab bar configuration show on typical A-2 is not <br /> acceptable. WAC 388-97-450(1) (d) <br /> 4. Clothes washing in the soiled linen room is not acceptable. <br /> WAC 388-97-205 WAC 388-97-455(4) <br /> 5. Provide a functional program. WAC 388-97-400(1) (a) <br /> 6. Describe the proposed activities for kitchen 509/609. WAC <br /> 388-97-400(1) (a) <br /> 7. Verify a mop sink is located in Custodian 506/606. WAC 386- <br /> 97-325(10) <br /> g, Provide manufacturer's labeled carpet specifications and <br /> radiant panel test report for our review. WAC 388-97-400(3) (c) <br /> 9. A properly vented, approved reduced pressure backflow assembly <br /> shall be provided between copper pipe or tubing and carbonated <br /> beverage dispensing machines. WAC 246-215-120(4) <br /> 10. Provide indirect drains for pop �nachine and ice machines. WAC <br /> 388-97-370 (4) <br /> 11• sanitization by 180F hot9water or approvedschemicalCa�9AC124of <br /> 215-100 (4) <br /> lZ, Provide a two compartment sink in kitc:hen 509/609. WAC 246- <br /> 215-090(5) (a) • <br /> page 1 of 2 <br />