, �_ - � �_ <br /> F[RE AND LIFE SAEETY PROGRAM MANAGER'S REVIEW COMMENI'S <br /> MIKE PADDOCK <br /> Phone: (360)705fi784 <br /> FA?�: (360)705fi654 <br /> NET: MTp0303 Qhub.doh.wa.gov <br /> FACILITY: Bethany u Pacific Campus <br /> PROJECT: Can�:�csion of 4 Floors From Hospital to NH Functions � <br /> CItSN: 98-827i�5142-004 <br /> DATE: May 26, 1998 <br /> E'[RE AND LIFE SAFETY PLAN REV�W <br /> i. Door openings 342M,342BA,342D,381M,381BA.38ICA,449C,449D,449AA.536A, <br /> 536C,536D,and 5366A are tequited to be protected by at least 20-minute smoke and draft <br /> control assemblies becwu a common atmosphere ezists betwern the cortidors they open to and <br /> main cortidor through the nurses' station. WAC 388-97-410(I): Sec. 1005.8.1,Uniform <br /> Building Code <br /> 2. Please verify that the glazing between med 381 B and nurse station 381, 342B and the <br /> corridor, office 450 and the corridor,and 536A,536B,and 536D and the cortidor will be fized <br /> glazing listed and labeled for a fire-protection rating of at least three-fourths hour. This <br /> requirement is applicable to all glazing in one hour walls separating rooms and cotridors. Fixed <br /> fully tempercd or laminated glass in woad or metal frames may be used in corridor walls. <br /> provided the glazed area does not exceed 25 percent of the area of the cortidor wall of the room. <br /> The total area of glass in cotridor walls is not limited when t!rc glazing is fized 1/4-inch-thick <br /> wired glass in steel frames and the siu of individual glazed panel does not exceed 1,296 square <br /> inches. WAC 388-97-410(1): Sec. 1005.8.2, IOI93,Uniform Building Code <br /> 3. All storage rooms, including,utility,linen and supply rooms, mme than 100 square feet <br /> storing combustible material are required to be protected by a one-hour smoke and drak control <br /> assembly. WAC 388-97-410(I): Sec. 308.8 Unifotm Building Code <br /> 4. Exit doors frcm dining 316,dining 411,and dining S 10 are requircd to be placed a distance <br /> apan equal to not less than onc half of the length of the muimum overall diagonal dimension of <br /> the area to be served measured in a straight line between eaits. WAC 388-97-410(1): Sec. <br /> 1003.3 Uniform Building Code <br /> 5. Please specify the type of elevator door opening protection that will be pmvided for exh <br /> opening. WAC 3R8-97-410(I): Sec. 1005.10,Unifortn Building Code,Wuhington State <br /> Amen�lments <br /> 6. Please verify that staitway enclosures include a corridor or ezit passageway on the ground <br /> floor leading from the stairway to the exterior of the building of at least two hour consttuction. <br /> WAC 388-97-410(I): Sec. 1009.4, Uniform Building Code <br /> •r+t«srr NOT APPROVED �"������ <br />